Alabama Journeyman Electrician Practice Test

20 questions in the style of the Alabama journeyman exam (Prov): NEC rules, code navigation and calculations. Pick an answer, check it, and read why — with the section to look up.

The real Alabama exam: 80 questions in 4 h, open book, 2023 NEC. Full Alabama exam guide →

Question 1 of 20Conductors & ampacity
PUT IT INTO PRACTICE

A 250 kcmil THWN-2 copper feeder lands on switchboard lugs that carry no temperature marking. There are three current-carrying conductors at a 30 °C ambient. What ampacity may be used for this conductor?

Select your answer
Report a problem with this question

Describe the content issue. Do not include private patient or workplace information.

Pick an answer and check it.

See all 20 questions with answers and explanations
  1. A 250 kcmil THWN-2 copper feeder lands on switchboard lugs that carry no temperature marking. There are three current-carrying conductors at a 30 °C ambient. What ampacity may be used for this conductor?

    • 205 A
    • 215 A
    • 230 A
    • 255 A

    Answer: 255 A

    Why: For conductors larger than 1 AWG (or circuits over 100 A), 110.14(C)(1)(b) lets you use the 75 °C column even without a marking. 250 kcmil copper is 255 A at 75 °C in Table 310.16. The 90 °C value of 290 A is not usable at these terminations. (NEC 110.14(C)(1)(b), Table 310.16)

  2. A 20 A multioutlet branch circuit supplies lighting outlets and fastened-in-place equipment. What is the maximum total rating of the fastened-in-place equipment, other than luminaires?

    • 7.5 A
    • 10 A
    • 12 A
    • 16 A

    Answer: 10 A

    Why: 210.23 limits the total rating of utilization equipment fastened in place, other than luminaires, to 50 % of the circuit rating when the circuit also supplies lighting or cord-and-plug equipment. 50 % of 20 A is 10 A. (NEC 210.23)

  3. A 30 A branch circuit uses 10 AWG THHN copper. Neither the breaker nor the receptacle terminals carry any temperature marking. Which ampacity column of Table 310.16 limits this conductor?

    • The 60 °C column
    • The 75 °C column
    • The 90 °C column
    • Any column, if the load is noncontinuous

    Answer: The 60 °C column

    Why: For circuits rated 100 A or less, or conductors 14 through 1 AWG, 110.14(C)(1)(a) assumes 60 °C terminations unless the equipment is listed and marked for a higher rating. 10 AWG copper is 30 A in the 60 °C column, which happens to match this 30 A circuit. (NEC 110.14(C)(1)(a), Table 310.16)

  4. A 4,500 W water heater element runs 3 hours a day for 30 days. Electricity costs $0.15 per kWh. What is the energy cost for the month?

    • $2.03
    • $20.25
    • $60.75
    • $60,750

    Answer: $60.75

    Why: Energy is power × time, billed in kilowatt-hours. Convert to kW first: 4,500 W = 4.5 kW. Energy = 4.5 kW × 3 h × 30 days = 405 kWh. Cost = 405 × $0.15 = $60.75.

  5. A new in-ground pool is installed at a single-family home. At least one 125 V, 15 or 20 A general-purpose receptacle is required near the pool. Between what distances from the inside wall of the pool must it be located?

    • 5 ft and 10 ft
    • 5 ft and 20 ft
    • 6 ft and 10 ft
    • 6 ft and 20 ft

    Answer: 6 ft and 20 ft

    Why: 680.22(A)(1) requires at least one general-purpose receptacle at a dwelling pool so nobody runs an extension cord across the deck. It must sit no closer than 6 ft and no farther than 20 ft from the inside wall, and no higher than 6 ft 6 in. above the deck. It is also GFCI protected because it is within 20 ft. (NEC 680.22(A)(1))

  6. A 60 A circuit breaker protects 6 AWG copper feeder conductors to a subpanel in the same building. The conductors are not upsized. What minimum size copper equipment grounding conductor is required?

    • 12 AWG
    • 10 AWG
    • 8 AWG
    • 6 AWG

    Answer: 10 AWG

    Why: Table 250.122 sizes the EGC from the rating of the overcurrent device ahead of the circuit. The 60 A row calls for 10 AWG copper. The size of the circuit conductors doesn't set the EGC unless they were upsized (250.122(B)). (NEC 250.122(A), Table 250.122)

  7. A balanced three-phase, 208 V load draws 150 A on each line. How many kVA does it draw?

    • 18.0 kVA
    • 31.2 kVA
    • 54.0 kVA
    • 93.6 kVA

    Answer: 54.0 kVA

    Why: Three-phase kVA = 1.732 × line volts × line amps ÷ 1,000 = 1.732 × 208 × 150 ÷ 1,000 = 54.04 kVA, which rounds to 54.0 kVA. The same answer comes from 3 × 120 V × 150 A per phase.

  8. A 20 A multioutlet branch circuit supplies lighting and receptacles. What is the maximum rating of one cord-and-plug-connected appliance that is not fastened in place?

    • 10 A
    • 12 A
    • 16 A
    • 20 A

    Answer: 16 A

    Why: 210.23 limits a single cord-and-plug-connected item not fastened in place to 80 % of the branch-circuit rating. 80 % of 20 A is 16 A. (NEC 210.23)

  9. Which receptacle ratings are permitted on a 40 A branch circuit with more than one receptacle?

    • 40 A only
    • 30 A or 40 A
    • 50 A only
    • 40 A or 50 A

    Answer: 40 A or 50 A

    Why: Table 210.21(B)(3) lists the receptacle ratings for each circuit size: 15 A → 15 A; 20 A → 15 or 20 A; 30 A → 30 A; 40 A → 40 or 50 A; 50 A → 50 A. A 40 A circuit takes 40 A or 50 A receptacles. (NEC Table 210.21(B)(3))

  10. An inspector finds the neutral bonded to the enclosure in a feeder-supplied panelboard downstream of the service, in the same building. With that bond in place, where does part of the normal neutral current return to the service?

    • On the EGCs, raceways, and other bonded metal
    • Only into the earth through the ground rods
    • Nowhere, since a bond carries only fault current
    • Back through the ungrounded feeder conductors

    Answer: On the EGCs, raceways, and other bonded metal

    Why: The extra bond puts the feeder EGC, metal raceways, and any bonded piping in parallel with the neutral. Current divides among parallel paths, so part of the normal neutral current flows on metal that people touch. That's objectionable current under 250.6, and it's why 250.24(A)(5) and 250.142(B) prohibit the bond. (NEC 250.6(A), 250.24(A)(5), 250.142(B))

  11. A resistive heater is moved from a 120 V circuit to a 240 V circuit. If its resistance stays the same, how does its power compare with before?

    • One-quarter as much
    • One-half as much
    • Twice as much
    • Four times as much

    Answer: Four times as much

    Why: With resistance fixed, P = E² ÷ R. Doubling E makes E² four times larger, so the heater makes four times the watts. Current doubles too (I = E ÷ R), and twice the volts times twice the amps is four times the power. That is why a 120 V heater on 240 V fails fast.

  12. A ceiling box with internal clamps and a luminaire stud has two 14/2 NM cables with ground entering it. The luminaire's two 18 AWG fixture wires and its grounding conductor come in from a domed canopy. What minimum box volume is required?

    • 12.00 in.³
    • 14.00 in.³
    • 16.00 in.³
    • 17.00 in.³

    Answer: 14.00 in.³

    Why: Four 14 AWG conductors take 8.00 in.³. Grounds, clamps and the stud each take one 2.00 in.³ allowance, adding 6.00. The fixture wires and the luminaire ground from a domed canopy may be left out (exception to 314.16(B)(1)). Total 14.00 in.³. (NEC 314.16(B)(1) Exception, 314.16(B)(3), Table 314.16(B))

  13. Under the 2023 NEC optional method for a one-family dwelling (220.82), the first 10 kVA of the general load is taken at 100 %. At what percentage is the rest of the general load taken?

    • 25 %
    • 35 %
    • 40 %
    • 65 %

    Answer: 40 %

    Why: 220.82(B) takes the first 10 kVA of the general load at 100 % and everything above that at 40 %. Heating and air conditioning are not in that pile; they are added separately under 220.82(C). (NEC 220.82(B)) Edition note: 2023 NEC numbering. In the 2026 NEC, load calculations moved from Article 220 to Article 120.

  14. A resistive water heater element has a resistance of 16 Ω and is connected to 240 V. How much current does it draw?

    • 0.067 A
    • 7.5 A
    • 15 A
    • 3,840 A

    Answer: 15 A

    Why: Ohm's law: current equals voltage divided by resistance, I = E ÷ R. Here 240 V ÷ 16 Ω = 15 A. Think of it as push divided by opposition: more volts push more amps, more ohms hold them back.

  15. A 75 kVA, three-phase, 480 V to 208Y/120 V transformer is protected on the primary side only. What is the largest standard primary breaker permitted by Table 450.3(B) and its notes?

    • 90 A
    • 100 A
    • 110 A
    • 125 A

    Answer: 125 A

    Why: Primary current is 75,000 ÷ (1.732 × 480) = 90.21 A. Primary-only protection for 9 A or more is 125 %: 90.21 × 1.25 = 112.77 A. Table 450.3(B) Note 1 permits the next higher standard size, 125 A. (NEC 450.3(B), Table 450.3(B), 240.6(A))

  16. A 2 hp, 115 V, single-phase motor drives a shop air compressor (not a hermetic refrigerant compressor). What minimum ampacity must its branch-circuit conductors have?

    • 15.0 A
    • 24.0 A
    • 27.6 A
    • 30.0 A

    Answer: 30.0 A

    Why: Single-phase motors use Table 430.248, which lists 24 A for 2 hp at 115 V. 430.22 requires 125 %: 24 × 1.25 = 30 A. (NEC Table 430.248, 430.22)

  17. You are sizing the branch-circuit short-circuit and ground-fault protective device for a general-purpose three-phase squirrel-cage motor. Which current do you start from?

    • The nameplate full-load current
    • The locked-rotor current on the nameplate
    • The full-load current from Table 430.250
    • The service-factor current on the nameplate

    Answer: The full-load current from Table 430.250

    Why: 430.6(A)(1) sends you to the FLC tables for conductor ampacity, switch ratings and the short-circuit and ground-fault device. Table values are conservative and let the circuit be designed before the exact motor arrives. The nameplate value is used for separate overload protection. (NEC 430.6(A)(1), 430.6(A)(2), Table 430.250)

  18. A 200 A service is supplied by 3/0 AWG copper service-entrance conductors. What minimum size copper grounding electrode conductor is required to the metal underground water pipe electrode?

    • 8 AWG
    • 6 AWG
    • 4 AWG
    • 2 AWG

    Answer: 4 AWG

    Why: Table 250.66 sizes the GEC from the largest ungrounded service-entrance conductor. 3/0 copper falls in the "2/0 or 3/0" row, which calls for 4 AWG copper. The water pipe isn't a rod, plate, concrete-encased electrode, or ground ring, so none of the 250.66(A)–(C) limits apply. (NEC 250.66, Table 250.66)

  19. A general-purpose branch circuit uses 12 AWG THHN copper with 75 °C terminations. No correction or adjustment applies, and no special exception (such as a motor circuit) is involved. What is the largest overcurrent device permitted?

    • 15 A
    • 20 A
    • 25 A
    • 30 A

    Answer: 20 A

    Why: Table 310.16 lists 12 AWG copper at 25 A (75 °C) and 30 A (90 °C), but 240.4(D) caps the overcurrent protection of 12 AWG copper at 20 A. The small-conductor rule wins unless a specific section such as 240.4(G) permits otherwise. (NEC 240.4(D), Table 310.16)

  20. A single PV string uses modules with a short-circuit current (Isc) of 9.6 A. Using the 125 % method, what is the maximum circuit current for this string? (Round to two decimals.)

    • 9.60 A
    • 11.04 A
    • 12.00 A
    • 15.00 A

    Answer: 12.00 A

    Why: 690.8(A)(1) sets the maximum current of a PV string at 125 % of the module Isc. The extra 25 % covers sunlight stronger than the standard test condition, such as cold, clear days with reflected light. 9.6 A × 1.25 = 12.00 A. A second 125 % is applied later, when you size conductors and overcurrent devices. (NEC 690.8(A)(1))

Original practice questions written for Ohmward on the 2023 NEC — not real exam items.