Journeyman exam formulas, on one page.
Every formula the journeyman exam's calculation questions rely on, with a worked example. The lessons let you move each one with a slider until it clicks.
| What | Formula | Example |
|---|---|---|
| Ohm's law | E = I × R · I = E ÷ R · R = E ÷ I | 120 V across 24 Ω → I = 5 A |
| Power (DC / resistive) | P = E × I · P = I² × R · P = E² ÷ R | 240 V × 20 A = 4,800 W |
| Series resistance | R_T = R1 + R2 + R3 … | 10 + 20 + 30 = 60 Ω |
| Parallel resistance | 1/R_T = 1/R1 + 1/R2 … (two: R1·R2 ÷ (R1+R2)) | 20 ∥ 30 = 600 ÷ 50 = 12 Ω |
| Single-phase AC power | W = E × I × PF · VA = E × I | 240 V × 30 A × 0.9 = 6,480 W |
| Three-phase power | VA = E × I × 1.732 · W = E × I × 1.732 × PF | 208 V × 50 A × 1.732 = 18,013 VA |
| Three-phase current | I = VA ÷ (E × 1.732) | 45 kVA at 208 V → 125 A |
| Wye / delta | Wye: E_L = 1.732 × E_P, I_L = I_P · Delta: E_L = E_P, I_L = 1.732 × I_P | 120 V phase (wye) → 208 V line |
| Power factor | PF = W ÷ VA = cos θ | 8 kW ÷ 10 kVA = 0.8 |
| Voltage drop (1φ) | VD = 2 × K × I × L ÷ CM (K = 12.9 Cu, 21.2 Al) | 2 × 12.9 × 20 × 100 ÷ 6,530 = 7.9 V |
| Voltage drop (3φ) | VD = 1.732 × K × I × L ÷ CM | |
| Minimum CM for a drop | CM = 2 × K × I × L ÷ VD (1φ) | |
| Transformer current | I = kVA × 1,000 ÷ E (1φ) · ÷ (E × 1.732) (3φ) | 25 kVA at 240 V → 104 A |
| Turns ratio | E_P ÷ E_S = N_P ÷ N_S = I_S ÷ I_P | 480 → 120 V is 4 : 1 |
| Continuous load | OCPD and conductors ≥ 125 % of continuous load (210.19, 210.20, 215.2, 215.3) | 16 A continuous → 20 A |
| Motor conductors | 125 % of Table 430.248 / 430.250 FLC (430.22) | 28 A FLC → 35 A |
| Motor overloads | 125 % (SF ≥ 1.15 or temp rise ≤ 40 °C) else 115 % of nameplate FLA (430.32) | |
| Motor short-circuit | Table 430.52(C)(1): ITB 250 %, TD fuse 175 %, non-TD fuse 300 % | 28 A × 250 % = 70 A |
| Ampacity adjustment | Table value × temp. correction × bundling adjustment (310.15(B), (C)(1)) | 75 A × 0.91 × 0.8 = 54.6 A |
| Box fill | Σ allowances × Table 314.16(B) volume (14 AWG 2.0, 12 AWG 2.25, 10 AWG 2.5 in³) | 9 × 2.25 = 20.25 in³ |
| Conduit fill | Σ conductor areas ≤ 40 % of raceway area (3+ conductors), Chapter 9 | |
| Dwelling general lighting | 3 VA/ft² + 1,500 VA per small-appliance and laundry circuit; first 3,000 VA at 100 %, rest to 120,000 VA at 35 % (220.41, Table 220.45) | 2,000 ft² → 5,625 VA |
| Efficiency | Efficiency = output ÷ input · 1 hp = 746 W | 10 hp output, 90 % → 8,289 W in |
| Energy cost | kWh = kW × hours · cost = kWh × rate | 4.5 kW × 3 h × $0.15 = $2.03 |
Section references are to the 2023 NEC. Always use the table values from the code edition your exam uses.