These 20 questions practice what Prometric journeyman exams test: finding and applying NEC rules, and electrical calculations.

Question 1 of 20Transformers & generators
PUT IT INTO PRACTICE

A 22 kW, 240 V, single-phase standby generator is rated at unity power factor. What minimum ampacity must the conductors from its output terminals to the first overcurrent device have?

Given conditions

Unity power factor, so nameplate current = kW ÷ V

Rounded to 0.1 A

Select your answer
Report a problem with this question

Describe the content issue. Do not include private patient or workplace information.

Pick an answer and check it.

See all 20 questions with answers and explanations
  1. A 22 kW, 240 V, single-phase standby generator is rated at unity power factor. What minimum ampacity must the conductors from its output terminals to the first overcurrent device have?

    • 60.9 A
    • 91.7 A
    • 105.4 A
    • 114.6 A

    Answer: 105.4 A

    Why: Rated current is 22,000 ÷ 240 = 91.67 A. 445.13(A) requires these conductors to be rated at least 115 % of the nameplate current: 91.67 × 1.15 = 105.42 A, about 105.4 A. (NEC 445.13(A))

  2. A 200 A service is supplied by 3/0 AWG copper service-entrance conductors. What minimum size copper grounding electrode conductor is required to the metal underground water pipe electrode?

    • 8 AWG
    • 6 AWG
    • 4 AWG
    • 2 AWG

    Answer: 4 AWG

    Why: Table 250.66 sizes the GEC from the largest ungrounded service-entrance conductor. 3/0 copper falls in the "2/0 or 3/0" row, which calls for 4 AWG copper. The water pipe isn't a rod, plate, concrete-encased electrode, or ground ring, so none of the 250.66(A)–(C) limits apply. (NEC 250.66, Table 250.66)

  3. Under the 2023 NEC standard method, what demand load is used for a single 14 kW household electric range in a one-family dwelling?

    • 8.0 kW
    • 8.8 kW
    • 10.5 kW
    • 14.0 kW

    Answer: 8.8 kW

    Why: Table 220.55 Column C gives 8 kW for one range rated not over 12 kW. Note 1 raises the Column C value by 5 % for each kW (or major fraction) above 12 kW. A 14 kW range is 2 kW over, so 8 kW × 1.10 = 8.8 kW. (NEC 220.55, Table 220.55) Edition note: 2023 NEC numbering. In the 2026 NEC, load calculations moved from Article 220 to Article 120.

  4. Under the 2023 NEC standard method, a 2,400 ft² dwelling has the two required small-appliance circuits and one laundry circuit. What is the net general lighting, small-appliance and laundry demand after Table 220.45?

    • 4,095 VA
    • 5,520 VA
    • 6,045 VA
    • 11,700 VA

    Answer: 6,045 VA

    Why: Start with 2,400 × 3 VA = 7,200 VA, then add 1,500 VA for each small-appliance and laundry circuit (220.52): 7,200 + 3,000 + 1,500 = 11,700 VA. Table 220.45 takes the first 3,000 VA at 100 % and the next portion, up to 120,000 VA, at 35 %: 3,000 + (8,700 × 0.35) = 6,045 VA. (NEC 220.41, 220.52(A), 220.52(B), Table 220.45) Edition note: 2023 NEC numbering. In the 2026 NEC, load calculations moved from Article 220 to Article 120. The dwelling demand tiers were Table 220.42 in the 2020 NEC and are Table 220.45 in 2023.

  5. A 25 kVA, single-phase transformer has a 480 V primary and a 240 V secondary. What is its full-load secondary current?

    • 52.08 A
    • 60.14 A
    • 104.17 A
    • 180.42 A

    Answer: 104.17 A

    Why: Single-phase current is VA ÷ volts, with no √3. On the 240 V side: 25,000 ÷ 240 = 104.17 A. The secondary current is twice the primary current because the voltage is half.

  6. A 20 A duplex receptacle on a single yoke is installed in a device box and connected to 12 AWG copper conductors. What volume allowance must be added to the box fill for the receptacle?

    • 2.25 in.³
    • 4.00 in.³
    • 4.50 in.³
    • 9.00 in.³

    Answer: 4.50 in.³

    Why: 314.16(B)(4) gives each yoke or strap holding a device a double volume allowance, based on the largest conductor connected to that device. Table 314.16(B) lists 12 AWG at 2.25 in.³, so the receptacle takes 2 × 2.25 = 4.50 in.³. It is per yoke, not per receptacle face. (NEC 314.16(B)(4), Table 314.16(B))

  7. A one-family dwelling has a 125 A, 120/240 V, single-phase service supplying the entire dwelling load. Using 310.12 with copper THWN-2 conductors, 75 °C terminations, and no adjustment or correction factors, what is the minimum ungrounded service-entrance conductor size?

    • 3 AWG
    • 2 AWG
    • 1 AWG
    • 1/0 AWG

    Answer: 2 AWG

    Why: 310.12 lets the conductors of a 120/240 V single-phase dwelling service be sized at 83 % of the service rating: 125 × 0.83 = 103.75 A. In the 75 °C copper column of Table 310.16, 3 AWG is 100 A (too small) and 2 AWG is 115 A. So 2 AWG copper is the minimum. (NEC 310.12, Table 310.16)

  8. A 4,500 W water heater element runs 3 hours a day for 30 days. Electricity costs $0.15 per kWh. What is the energy cost for the month?

    • $2.03
    • $20.25
    • $60.75
    • $60,750

    Answer: $60.75

    Why: Energy is power × time, billed in kilowatt-hours. Convert to kW first: 4,500 W = 4.5 kW. Energy = 4.5 kW × 3 h × 30 days = 405 kWh. Cost = 405 × $0.15 = $60.75.

  9. You need the requirements for a rooftop solar photovoltaic system (Article 690). Which chapter of the NEC contains it?

    • Chapter 5
    • Chapter 6
    • Chapter 7
    • Chapter 8

    Answer: Chapter 6

    Why: Chapter 6 covers special equipment, including signs, elevators, EV charging, pools (680) and solar PV (690). The first digit of the article number is the chapter: 690 is in Chapter 6. (NEC Article 690, 90.3)

  10. Three 6 AWG THHN copper current-carrying conductors run through a boiler room with a 45 °C ambient. Using Table 310.15(B)(1)(1), what is the conductor's ampacity after ambient correction, before the termination check?

    • 53.30 A
    • 60.00 A
    • 61.50 A
    • 65.25 A

    Answer: 65.25 A

    Why: THHN is 90 °C, so start at 75 A (6 AWG copper, 90 °C column). The 41–45 °C row gives 0.87 in the 90 °C column: 75 × 0.87 = 65.25 A. The 110.14(C) termination check comes afterwards. (NEC Table 310.15(B)(1)(1), Table 310.16) Edition note: The 2023 NEC numbers the 30 °C-based correction table as Table 310.15(B)(1)(1); the 2020 edition called it Table 310.15(B)(1).

  11. A new in-ground pool is installed at a single-family home. At least one 125 V, 15 or 20 A general-purpose receptacle is required near the pool. Between what distances from the inside wall of the pool must it be located?

    • 5 ft and 10 ft
    • 5 ft and 20 ft
    • 6 ft and 10 ft
    • 6 ft and 20 ft

    Answer: 6 ft and 20 ft

    Why: 680.22(A)(1) requires at least one general-purpose receptacle at a dwelling pool so nobody runs an extension cord across the deck. It must sit no closer than 6 ft and no farther than 20 ft from the inside wall, and no higher than 6 ft 6 in. above the deck. It is also GFCI protected because it is within 20 ft. (NEC 680.22(A)(1))

  12. In which installation is the next-size-up allowance of 240.4(B) NOT permitted?

    • A multioutlet receptacle branch circuit for portable loads
    • A feeder with 140 A ampacity protected by a 150 A breaker
    • An individual branch circuit to one fixed appliance
    • A feeder with 475 A ampacity protected at 500 A

    Answer: A multioutlet receptacle branch circuit for portable loads

    Why: 240.4(B)(1) excludes branch circuits that supply more than one receptacle for cord-and-plug-connected portable loads. Any plug on that circuit could draw up to the breaker rating, so the breaker must not exceed the conductor ampacity. (NEC 240.4(B)(1))

  13. A 25 ft feeder tap is taken from a feeder protected by a 300 A breaker. Under 240.21(B)(2), what is the minimum ampacity of the tap conductors?

    • 30 A
    • 100 A
    • 150 A
    • 300 A

    Answer: 100 A

    Why: 240.21(B)(2) requires a 25-ft tap to have an ampacity of at least one-third of the feeder overcurrent device rating: 300 ÷ 3 = 100 A. The tap must also end in a single breaker or set of fuses that limits the load to the tap's ampacity. (NEC 240.21(B)(2))

  14. A 20 A multioutlet branch circuit supplies lighting outlets and fastened-in-place equipment. What is the maximum total rating of the fastened-in-place equipment, other than luminaires?

    • 7.5 A
    • 10 A
    • 12 A
    • 16 A

    Answer: 10 A

    Why: 210.23 limits the total rating of utilization equipment fastened in place, other than luminaires, to 50 % of the circuit rating when the circuit also supplies lighting or cord-and-plug equipment. 50 % of 20 A is 10 A. (NEC 210.23)

  15. A 30 hp, 460 V, three-phase motor has a nameplate full-load current of 38 A. What minimum ampere rating must its disconnecting means have?

    • 34.8 A
    • 40.0 A
    • 43.7 A
    • 46.0 A

    Answer: 46.0 A

    Why: 430.110(A) requires the disconnect to be rated at least 115 % of the motor's full-load current, and 430.6(A)(1) says switch ratings come from the table. Table 430.250 gives 40 A: 40 × 1.15 = 46 A. (NEC 430.110(A), 430.6(A)(1), Table 430.250)

  16. A resistive water heater element rated 4,500 W at 240 V is connected to a 208 V circuit. If its resistance does not change, about how many watts does it produce?

    • 3,380 W
    • 3,900 W
    • 4,500 W
    • 5,192 W

    Answer: 3,380 W

    Why: The element's resistance is what stays fixed: R = 240² ÷ 4,500 = 12.8 Ω. At 208 V, P = 208² ÷ 12.8 = 43,264 ÷ 12.8 = 3,380 W, about 75 % of nameplate. Power follows the square of voltage, so a 13 % lower voltage costs about 25 % of the heat.

  17. You are pouring a 1-1/2 in. trade size sealing fitting in a Class I, Division 1 location. The fitting has no marking that calls for a different depth. What is the minimum thickness of sealing compound?

    • 5/8 in.
    • 3/4 in.
    • 1-1/2 in.
    • 2 in.

    Answer: 1-1/2 in.

    Why: The compound must be at least as thick as the trade size of the sealing fitting, and never less than 5/8 in. (501.15(C)(3)). For a 1-1/2 in. fitting that means at least 1-1/2 in. of compound. The 5/8 in. figure is only the floor for very small fittings. (NEC 501.15(C)(3))

  18. A textile mill has looms that throw off cotton lint and flyings, which collect on ledges and equipment. Under Article 500, how is this area classified?

    • Class I, Group D
    • Class II, Group G
    • Class III
    • Class II, Group E

    Answer: Class III

    Why: Class locations are sorted by what can burn. Class I is gases and vapors, Class II is combustible dust, and Class III is easily ignitible fibers and flyings such as cotton lint. Textile mills and cotton gins are the textbook Class III examples in 500.5(D). Class III has no material groups. (NEC 500.5(D))

  19. A box with internal clamps contains two 12/2 NM cables spliced through for a 20 A circuit and one 14/2 NM cable feeding a 15 A duplex receptacle in the same box. All three cables have bare grounds. What minimum box volume is required?

    • 21.50 in.³
    • 22.00 in.³
    • 23.50 in.³
    • 24.00 in.³

    Answer: 21.50 in.³

    Why: Each conductor counts at its own size: 4 × 2.25 = 9.00 plus 2 × 2.00 = 4.00. Grounds take one allowance at the largest ground (12 AWG, 2.25) and clamps one at the largest conductor (12 AWG, 2.25). The receptacle is connected only to 14 AWG, so it takes 2 × 2.00 = 4.00 (314.16(B)(4)). Total 21.50 in.³. (NEC 314.16(B)(2), 314.16(B)(4), 314.16(B)(5), Table 314.16(B))

  20. A coil with 0.1 H of inductance is connected to a 60 Hz supply. What is its inductive reactance?

    • 6.0 Ω
    • 18.8 Ω
    • 37.7 Ω
    • 377 Ω

    Answer: 37.7 Ω

    Why: XL = 2πfL. At 60 Hz, 2πf = 2 × 3.1416 × 60 = 377. Then XL = 377 × 0.1 = 37.7 Ω. Inductive reactance grows with both frequency and inductance.