Pearson VUE Journeyman Electrician Practice Test
Pearson VUE gives the journeyman electrician exam in 5 states we track. These 20 questions practice what Pearson VUE journeyman exams test: finding and applying NEC rules, and electrical calculations.
In a purely capacitive AC circuit, how does the current relate to the voltage?
Report a problem with this question
See all 20 questions with answers and explanations
In a purely capacitive AC circuit, how does the current relate to the voltage?
- It lags the voltage by 90°
- It is in phase with the voltage
- It lags the voltage by 45°
- It leads the voltage by 90°
Answer: It leads the voltage by 90°
Why: A capacitor's current is greatest when the voltage is changing fastest, a quarter-cycle before the voltage peaks. So current leads voltage by 90°. Memory aid: ELI the ICE man. In C, I comes before E.
You need the requirements for a rooftop solar photovoltaic system (Article 690). Which chapter of the NEC contains it?
- Chapter 5
- Chapter 6
- Chapter 7
- Chapter 8
Answer: Chapter 6
Why: Chapter 6 covers special equipment, including signs, elevators, EV charging, pools (680) and solar PV (690). The first digit of the article number is the chapter: 690 is in Chapter 6. (NEC Article 690, 90.3)
A 20 A multioutlet branch circuit supplies lighting outlets and fastened-in-place equipment. What is the maximum total rating of the fastened-in-place equipment, other than luminaires?
- 7.5 A
- 10 A
- 12 A
- 16 A
Answer: 10 A
Why: 210.23 limits the total rating of utilization equipment fastened in place, other than luminaires, to 50 % of the circuit rating when the circuit also supplies lighting or cord-and-plug equipment. 50 % of 20 A is 10 A. (NEC 210.23)
Under the 2023 NEC, a one-family dwelling has 1,800 ft² of living space (outside dimensions), a 400 ft² attached garage, and a 200 ft² open front porch. Using the standard method, what is the general lighting load before any demand factor?
- 5,400 VA
- 6,000 VA
- 6,600 VA
- 7,200 VA
Answer: 5,400 VA
Why: 220.41 assigns 3 VA per square foot to dwelling units, but 220.5(C) counts only floor area that is, or can become, living space, measured from outside dimensions. Garages, open porches, and unfinished space not adaptable for future use are left out. 1,800 ft² × 3 VA = 5,400 VA. (NEC 220.5(C), 220.41) Edition note: 2023 NEC numbering. In the 2026 NEC, load calculations moved from Article 220 to Article 120. In the 2020 NEC the 3 VA/ft² dwelling load was in 220.14(J) and floor area in 220.11.
A 200 A service is supplied by 3/0 AWG copper service-entrance conductors. What minimum size copper grounding electrode conductor is required to the metal underground water pipe electrode?
- 8 AWG
- 6 AWG
- 4 AWG
- 2 AWG
Answer: 4 AWG
Why: Table 250.66 sizes the GEC from the largest ungrounded service-entrance conductor. 3/0 copper falls in the "2/0 or 3/0" row, which calls for 4 AWG copper. The water pipe isn't a rod, plate, concrete-encased electrode, or ground ring, so none of the 250.66(A)–(C) limits apply. (NEC 250.66, Table 250.66)
A 250 kcmil THWN-2 copper feeder lands on switchboard lugs that carry no temperature marking. There are three current-carrying conductors at a 30 °C ambient. What ampacity may be used for this conductor?
- 205 A
- 215 A
- 230 A
- 255 A
Answer: 255 A
Why: For conductors larger than 1 AWG (or circuits over 100 A), 110.14(C)(1)(b) lets you use the 75 °C column even without a marking. 250 kcmil copper is 255 A at 75 °C in Table 310.16. The 90 °C value of 290 A is not usable at these terminations. (NEC 110.14(C)(1)(b), Table 310.16)
A box with internal clamps contains two 12/2 NM cables spliced through for a 20 A circuit and one 14/2 NM cable feeding a 15 A duplex receptacle in the same box. All three cables have bare grounds. What minimum box volume is required?
- 21.50 in.³
- 22.00 in.³
- 23.50 in.³
- 24.00 in.³
Answer: 21.50 in.³
Why: Each conductor counts at its own size: 4 × 2.25 = 9.00 plus 2 × 2.00 = 4.00. Grounds take one allowance at the largest ground (12 AWG, 2.25) and clamps one at the largest conductor (12 AWG, 2.25). The receptacle is connected only to 14 AWG, so it takes 2 × 2.00 = 4.00 (314.16(B)(4)). Total 21.50 in.³. (NEC 314.16(B)(2), 314.16(B)(4), 314.16(B)(5), Table 314.16(B))
A textile mill has looms that throw off cotton lint and flyings, which collect on ledges and equipment. Under Article 500, how is this area classified?
- Class I, Group D
- Class II, Group G
- Class III
- Class II, Group E
Answer: Class III
Why: Class locations are sorted by what can burn. Class I is gases and vapors, Class II is combustible dust, and Class III is easily ignitible fibers and flyings such as cotton lint. Textile mills and cotton gins are the textbook Class III examples in 500.5(D). Class III has no material groups. (NEC 500.5(D))
A 25 ft feeder tap is taken from a feeder protected by a 300 A breaker. Under 240.21(B)(2), what is the minimum ampacity of the tap conductors?
- 30 A
- 100 A
- 150 A
- 300 A
Answer: 100 A
Why: 240.21(B)(2) requires a 25-ft tap to have an ampacity of at least one-third of the feeder overcurrent device rating: 300 ÷ 3 = 100 A. The tap must also end in a single breaker or set of fuses that limits the load to the tap's ampacity. (NEC 240.21(B)(2))
The general lighting in a retail store runs at full load from 8 a.m. to 10 p.m. every day. Under Article 100, how is this load classified?
- Noncontinuous load
- Intermittent duty
- Periodic duty
- Continuous load
Answer: Continuous load
Why: Article 100 defines a continuous load as one where maximum current is expected to continue for 3 hours or more. Store lighting that runs all day easily qualifies, so it gets the 125 % sizing rules for conductors and overcurrent devices. (NEC Article 100, Continuous Load)
A resistive heater is moved from a 120 V circuit to a 240 V circuit. If its resistance stays the same, how does its power compare with before?
- One-quarter as much
- One-half as much
- Twice as much
- Four times as much
Answer: Four times as much
Why: With resistance fixed, P = E² ÷ R. Doubling E makes E² four times larger, so the heater makes four times the watts. Current doubles too (I = E ÷ R), and twice the volts times twice the amps is four times the power. That is why a 120 V heater on 240 V fails fast.
A 20 A multioutlet branch circuit supplies lighting and receptacles. What is the maximum rating of one cord-and-plug-connected appliance that is not fastened in place?
- 10 A
- 12 A
- 16 A
- 20 A
Answer: 16 A
Why: 210.23 limits a single cord-and-plug-connected item not fastened in place to 80 % of the branch-circuit rating. 80 % of 20 A is 16 A. (NEC 210.23)
Which receptacle ratings are permitted on a 40 A branch circuit with more than one receptacle?
- 40 A only
- 30 A or 40 A
- 50 A only
- 40 A or 50 A
Answer: 40 A or 50 A
Why: Table 210.21(B)(3) lists the receptacle ratings for each circuit size: 15 A → 15 A; 20 A → 15 or 20 A; 30 A → 30 A; 40 A → 40 or 50 A; 50 A → 50 A. A 40 A circuit takes 40 A or 50 A receptacles. (NEC Table 210.21(B)(3))
On a 480 V, three-phase, four-wire wye system, what voltage should you measure from any phase conductor to the neutral?
- 277 V
- 339 V
- 480 V
- 831 V
Answer: 277 V
Why: In a wye, line voltage = phase voltage × 1.732, so phase voltage = 480 ÷ 1.732 = 277 V. That's why the system is called 480Y/277 V and why 277 V lighting runs phase to neutral.
A 2 hp, 115 V, single-phase motor drives a shop air compressor (not a hermetic refrigerant compressor). What minimum ampacity must its branch-circuit conductors have?
- 15.0 A
- 24.0 A
- 27.6 A
- 30.0 A
Answer: 30.0 A
Why: Single-phase motors use Table 430.248, which lists 24 A for 2 hp at 115 V. 430.22 requires 125 %: 24 × 1.25 = 30 A. (NEC Table 430.248, 430.22)
A 30 hp, 460 V, three-phase motor has a nameplate full-load current of 38 A. What minimum ampere rating must its disconnecting means have?
- 34.8 A
- 40.0 A
- 43.7 A
- 46.0 A
Answer: 46.0 A
Why: 430.110(A) requires the disconnect to be rated at least 115 % of the motor's full-load current, and 430.6(A)(1) says switch ratings come from the table. Table 430.250 gives 40 A: 40 × 1.15 = 46 A. (NEC 430.110(A), 430.6(A)(1), Table 430.250)
A storage room holds gasoline in closed, sealed drums. Vapors could escape only if a drum ruptured or leaked by accident. No dispensing happens in the room. How is the room classified?
- Class I, Division 1
- Class I, Division 2
- Class II, Division 2
- Class II, Division 1
Answer: Class I, Division 2
Why: Gasoline vapor makes it Class I. The division depends on how often an ignitible mixture is expected. Liquids kept in closed containers that release vapor only through accidental rupture or breakdown fit Division 2 in 500.5(B)(2). Division 1 is for places where the mixture exists in normal operation, such as open dispensing. (NEC 500.5(B)(2))
A 4,500 W water heater element runs 3 hours a day for 30 days. Electricity costs $0.15 per kWh. What is the energy cost for the month?
- $2.03
- $20.25
- $60.75
- $60,750
Answer: $60.75
Why: Energy is power × time, billed in kilowatt-hours. Convert to kW first: 4,500 W = 4.5 kW. Energy = 4.5 kW × 3 h × 30 days = 405 kWh. Cost = 405 × $0.15 = $60.75.
A 60 A circuit breaker protects 6 AWG copper feeder conductors to a subpanel in the same building. The conductors are not upsized. What minimum size copper equipment grounding conductor is required?
- 12 AWG
- 10 AWG
- 8 AWG
- 6 AWG
Answer: 10 AWG
Why: Table 250.122 sizes the EGC from the rating of the overcurrent device ahead of the circuit. The 60 A row calls for 10 AWG copper. The size of the circuit conductors doesn't set the EGC unless they were upsized (250.122(B)). (NEC 250.122(A), Table 250.122)
A new in-ground pool is installed at a single-family home. At least one 125 V, 15 or 20 A general-purpose receptacle is required near the pool. Between what distances from the inside wall of the pool must it be located?
- 5 ft and 10 ft
- 5 ft and 20 ft
- 6 ft and 10 ft
- 6 ft and 20 ft
Answer: 6 ft and 20 ft
Why: 680.22(A)(1) requires at least one general-purpose receptacle at a dwelling pool so nobody runs an extension cord across the deck. It must sit no closer than 6 ft and no farther than 20 ft from the inside wall, and no higher than 6 ft 6 in. above the deck. It is also GFCI protected because it is within 20 ft. (NEC 680.22(A)(1))
Pearson VUE journeyman exam format by state
| State | Questions | Time | Open book | NEC |
|---|---|---|---|---|
| California | 100 | 4 h 30 min | Yes | 2023 |
| Kentucky | 80 | 4 h | Yes | 2023 |
| South Dakota | 80 | 4 h | Yes | 2023 |
| Wisconsin | 100 | 4 h | Yes | 2023 |
| Wyoming | 80 | 4 h | Yes | — |
Original practice questions written for Ohmward. Not affiliated with Pearson VUE.