FREE · NO SIGN-UP · NEC REFERENCES

Arizona Journeyman Electrician Practice Test

20 questions in the style of the Arizona journeyman exam: NEC rules, code navigation and calculations. Pick an answer, check it, and read why — with the section to look up.

Question 1 of 20Transformers & generators
PUT IT INTO PRACTICE

A 75 kVA, three-phase transformer is rated 480 V delta primary, 208Y/120 V secondary. What is its full-load primary current?

Given conditions

Currents rounded to two decimals; √3 taken as 1.732

Select your answer
Report a problem with this question

Describe the content issue. Do not include private patient or workplace information.

Pick an answer and check it.

See all 20 questions with answers and explanations
  1. A 75 kVA, three-phase transformer is rated 480 V delta primary, 208Y/120 V secondary. What is its full-load primary current?

    • 90.21 A
    • 156.25 A
    • 208.18 A
    • 270.63 A

    Answer: 90.21 A

    Why: Three-phase current is VA ÷ (1.732 × line volts). On the primary: 75,000 ÷ (1.732 × 480) = 75,000 ÷ 831.36 = 90.21 A.

  2. A 120 V branch circuit supplies a metal pole light in a parking lot. Which of these must not be counted on as the effective ground-fault current path for that circuit?

    • The earth, through a ground rod at the pole
    • An EMT raceway with listed set-screw fittings
    • A copper wire-type equipment grounding conductor
    • The metal armor of listed Type AC cable

    Answer: The earth, through a ground rod at the pole

    Why: 250.4(A)(5) says the earth is not to be considered an effective ground-fault current path. Soil resistance is far too high to let enough current flow to open the breaker. The fault path has to be an intentional, low-impedance metal path back to the source, such as EMT, a wire-type EGC, or AC cable armor, all of which 250.118 permits. (NEC 250.4(A)(5), 250.118)

  3. A 22 kW, 240 V, single-phase standby generator is rated at unity power factor. What minimum ampacity must the conductors from its output terminals to the first overcurrent device have?

    • 60.9 A
    • 91.7 A
    • 105.4 A
    • 114.6 A

    Answer: 105.4 A

    Why: Rated current is 22,000 ÷ 240 = 91.67 A. 445.13(A) requires these conductors to be rated at least 115 % of the nameplate current: 91.67 × 1.15 = 105.42 A, about 105.4 A. (NEC 445.13(A))

  4. A receptacle reads 120 V on a true-RMS meter. What is the peak voltage of the sine wave?

    • 84.9 V
    • 169.7 V
    • 240 V
    • 339.4 V

    Answer: 169.7 V

    Why: Meters read RMS, the effective value. For a sine wave, peak = RMS × 1.414 (√2). So 120 × 1.414 = 169.7 V. The wave swings from +169.7 V to −169.7 V sixty times a second.

  5. An exam question asks for the allowable ampacity of a 4 AWG copper THWN conductor in a raceway. Where will you find the answer most directly?

    • Table 250.66
    • Chapter 9, Table 8
    • Table 314.16(A)
    • Table 310.16

    Answer: Table 310.16

    Why: Allowable ampacities for insulated conductors in raceway, cable or earth are in Table 310.16, in Article 310, Conductors for General Wiring. Memorize this table's location; it is the most-used table on the exam. (NEC Table 310.16)

  6. A 20 A multioutlet branch circuit supplies lighting and receptacles. What is the maximum rating of one cord-and-plug-connected appliance that is not fastened in place?

    • 10 A
    • 12 A
    • 16 A
    • 20 A

    Answer: 16 A

    Why: 210.23 limits a single cord-and-plug-connected item not fastened in place to 80 % of the branch-circuit rating. 80 % of 20 A is 16 A. (NEC 210.23)

  7. Which receptacle ratings are permitted on a 40 A branch circuit with more than one receptacle?

    • 40 A only
    • 30 A or 40 A
    • 50 A only
    • 40 A or 50 A

    Answer: 40 A or 50 A

    Why: Table 210.21(B)(3) lists the receptacle ratings for each circuit size: 15 A → 15 A; 20 A → 15 or 20 A; 30 A → 30 A; 40 A → 40 or 50 A; 50 A → 50 A. A 40 A circuit takes 40 A or 50 A receptacles. (NEC Table 210.21(B)(3))

  8. A storage room holds gasoline in closed, sealed drums. Vapors could escape only if a drum ruptured or leaked by accident. No dispensing happens in the room. How is the room classified?

    • Class I, Division 1
    • Class I, Division 2
    • Class II, Division 2
    • Class II, Division 1

    Answer: Class I, Division 2

    Why: Gasoline vapor makes it Class I. The division depends on how often an ignitible mixture is expected. Liquids kept in closed containers that release vapor only through accidental rupture or breakdown fit Division 2 in 500.5(B)(2). Division 1 is for places where the mixture exists in normal operation, such as open dispensing. (NEC 500.5(B)(2))

  9. Resistors of 10 Ω, 20 Ω and 30 Ω are connected in series across 120 V. What is the voltage across the 30 Ω resistor?

    • 20 V
    • 40 V
    • 60 V
    • 120 V

    Answer: 60 V

    Why: In series the resistances add: 10 + 20 + 30 = 60 Ω, and the same current flows through each: 120 ÷ 60 = 2 A. The drop across the 30 Ω resistor is 2 A × 30 Ω = 60 V. The biggest resistor takes the biggest share, and the drops (20 + 40 + 60) add back to 120 V.

  10. Under the 2023 NEC standard method, a 2,400 ft² dwelling has the two required small-appliance circuits and one laundry circuit. What is the net general lighting, small-appliance and laundry demand after Table 220.45?

    • 4,095 VA
    • 5,520 VA
    • 6,045 VA
    • 11,700 VA

    Answer: 6,045 VA

    Why: Start with 2,400 × 3 VA = 7,200 VA, then add 1,500 VA for each small-appliance and laundry circuit (220.52): 7,200 + 3,000 + 1,500 = 11,700 VA. Table 220.45 takes the first 3,000 VA at 100 % and the next portion, up to 120,000 VA, at 35 %: 3,000 + (8,700 × 0.35) = 6,045 VA. (NEC 220.41, 220.52(A), 220.52(B), Table 220.45) Edition note: 2023 NEC numbering. In the 2026 NEC, load calculations moved from Article 220 to Article 120. The dwelling demand tiers were Table 220.42 in the 2020 NEC and are Table 220.45 in 2023.

  11. Three 6 AWG THHN copper current-carrying conductors run through a boiler room with a 45 °C ambient. Using Table 310.15(B)(1)(1), what is the conductor's ampacity after ambient correction, before the termination check?

    • 53.30 A
    • 60.00 A
    • 61.50 A
    • 65.25 A

    Answer: 65.25 A

    Why: THHN is 90 °C, so start at 75 A (6 AWG copper, 90 °C column). The 41–45 °C row gives 0.87 in the 90 °C column: 75 × 0.87 = 65.25 A. The 110.14(C) termination check comes afterwards. (NEC Table 310.15(B)(1)(1), Table 310.16) Edition note: The 2023 NEC numbers the 30 °C-based correction table as Table 310.15(B)(1)(1); the 2020 edition called it Table 310.15(B)(1).

  12. A 120 V, 2-wire branch circuit of 12 AWG copper runs 100 ft (one way) to a 16 A load. Using VD = 2KIL/CM with K = 12.9 and circular mils from Chapter 9, Table 8, what is the voltage drop?

    • 3.16 V
    • 3.98 V
    • 5.47 V
    • 6.32 V

    Answer: 6.32 V

    Why: 12 AWG is 6,530 cmil. VD = 2 × 12.9 × 16 × 100 ÷ 6,530 = 6.32 V, which is 5.3 % of 120 V, well above the recommended 3 %. The 2 accounts for current flowing out and back. (NEC Chapter 9, Table 8)

  13. On a 480 V, three-phase, four-wire wye system, what voltage should you measure from any phase conductor to the neutral?

    • 277 V
    • 339 V
    • 480 V
    • 831 V

    Answer: 277 V

    Why: In a wye, line voltage = phase voltage × 1.732, so phase voltage = 480 ÷ 1.732 = 277 V. That's why the system is called 480Y/277 V and why 277 V lighting runs phase to neutral.

  14. A 25 kVA, single-phase transformer has a 480 V primary and a 240 V secondary. What is its full-load secondary current?

    • 52.08 A
    • 60.14 A
    • 104.17 A
    • 180.42 A

    Answer: 104.17 A

    Why: Single-phase current is VA ÷ volts, with no √3. On the 240 V side: 25,000 ÷ 240 = 104.17 A. The secondary current is twice the primary current because the voltage is half.

  15. A 6 AWG THWN copper conductor (75 °C terminations, no correction or adjustment) supplies a single fixed 55 A noncontinuous load on an individual branch circuit. What is the largest breaker that may protect it?

    • 60 A
    • 70 A
    • 75 A
    • 80 A

    Answer: 70 A

    Why: 6 AWG copper at 75 °C is 65 A, which isn't a standard rating. 240.4(B) lets you use the next higher standard rating, 70 A, because the circuit doesn't supply multiple receptacles for portable loads and the rating is under 800 A. (NEC 240.4(B), 240.6(A), Table 310.16)

  16. A coil with 0.1 H of inductance is connected to a 60 Hz supply. What is its inductive reactance?

    • 6.0 Ω
    • 18.8 Ω
    • 37.7 Ω
    • 377 Ω

    Answer: 37.7 Ω

    Why: XL = 2πfL. At 60 Hz, 2πf = 2 × 3.1416 × 60 = 377. Then XL = 377 × 0.1 = 37.7 Ω. Inductive reactance grows with both frequency and inductance.

  17. A resistive water heater element rated 4,500 W at 240 V is connected to a 208 V circuit. If its resistance does not change, about how many watts does it produce?

    • 3,380 W
    • 3,900 W
    • 4,500 W
    • 5,192 W

    Answer: 3,380 W

    Why: The element's resistance is what stays fixed: R = 240² ÷ 4,500 = 12.8 Ω. At 208 V, P = 208² ÷ 12.8 = 43,264 ÷ 12.8 = 3,380 W, about 75 % of nameplate. Power follows the square of voltage, so a 13 % lower voltage costs about 25 % of the heat.

  18. A 480Y/277 V panelboard has exposed live parts on one side of the working space and a concrete block wall on the other. What minimum depth of working space does Table 110.26(A)(1) require?

    • 3 ft
    • 3½ ft
    • 4 ft
    • 5 ft

    Answer: 3½ ft

    Why: Enter the table with voltage to ground: 277 V falls in the 151–1000 V row. Concrete, brick and tile walls are considered grounded, so live parts across from a block wall is Condition 2. The minimum depth is 3½ ft (1.0 m). (NEC 110.26(A)(1), Table 110.26(A)(1))

  19. A 200 A service is supplied by 3/0 AWG copper service-entrance conductors. What minimum size copper grounding electrode conductor is required to the metal underground water pipe electrode?

    • 8 AWG
    • 6 AWG
    • 4 AWG
    • 2 AWG

    Answer: 4 AWG

    Why: Table 250.66 sizes the GEC from the largest ungrounded service-entrance conductor. 3/0 copper falls in the "2/0 or 3/0" row, which calls for 4 AWG copper. The water pipe isn't a rod, plate, concrete-encased electrode, or ground ring, so none of the 250.66(A)–(C) limits apply. (NEC 250.66, Table 250.66)

  20. A textile mill has looms that throw off cotton lint and flyings, which collect on ledges and equipment. Under Article 500, how is this area classified?

    • Class I, Group D
    • Class II, Group G
    • Class III
    • Class II, Group E

    Answer: Class III

    Why: Class locations are sorted by what can burn. Class I is gases and vapors, Class II is combustible dust, and Class III is easily ignitible fibers and flyings such as cotton lint. Textile mills and cotton gins are the textbook Class III examples in 500.5(D). Class III has no material groups. (NEC 500.5(D))

Original practice questions written for Ohmward on the 2023 NEC — not real exam items.