Question 1 of 20Motors & air conditioning
PUT IT INTO PRACTICE

A 30 hp, 460 V, three-phase motor has a nameplate full-load current of 38 A. What minimum ampere rating must its disconnecting means have?

Select your answer
Report a problem with this question

Describe the content issue. Do not include private patient or workplace information.

Pick an answer and check it.

See all 20 questions with answers and explanations
  1. A 30 hp, 460 V, three-phase motor has a nameplate full-load current of 38 A. What minimum ampere rating must its disconnecting means have?

    • 34.8 A
    • 40.0 A
    • 43.7 A
    • 46.0 A

    Answer: 46.0 A

    Why: 430.110(A) requires the disconnect to be rated at least 115 % of the motor's full-load current, and 430.6(A)(1) says switch ratings come from the table. Table 430.250 gives 40 A: 40 × 1.15 = 46 A. (NEC 430.110(A), 430.6(A)(1), Table 430.250)

  2. An office building has an emergency system for egress lighting required by the building code. After normal power fails, within what time must the emergency system supply power?

    • 10 seconds
    • 30 seconds
    • 60 seconds
    • 90 seconds

    Answer: 10 seconds

    Why: 700.12 requires emergency lighting and power to be available within the time needed for the application, but no more than 10 seconds. Emergency systems protect life during evacuation, so people cannot be left in the dark for long. Legally required standby gets 60 seconds; optional standby has no time limit. (NEC 700.12)

  3. A ceiling box with internal clamps and a luminaire stud has two 14/2 NM cables with ground entering it. The luminaire's two 18 AWG fixture wires and its grounding conductor come in from a domed canopy. What minimum box volume is required?

    • 12.00 in.³
    • 14.00 in.³
    • 16.00 in.³
    • 17.00 in.³

    Answer: 14.00 in.³

    Why: Four 14 AWG conductors take 8.00 in.³. Grounds, clamps and the stud each take one 2.00 in.³ allowance, adding 6.00. The fixture wires and the luminaire ground from a domed canopy may be left out (exception to 314.16(B)(1)). Total 14.00 in.³. (NEC 314.16(B)(1) Exception, 314.16(B)(3), Table 314.16(B))

  4. Under the 2023 NEC optional method for a one-family dwelling (220.82), the first 10 kVA of the general load is taken at 100 %. At what percentage is the rest of the general load taken?

    • 25 %
    • 35 %
    • 40 %
    • 65 %

    Answer: 40 %

    Why: 220.82(B) takes the first 10 kVA of the general load at 100 % and everything above that at 40 %. Heating and air conditioning are not in that pile; they are added separately under 220.82(C). (NEC 220.82(B)) Edition note: 2023 NEC numbering. In the 2026 NEC, load calculations moved from Article 220 to Article 120.

  5. Under the 2023 NEC standard method, a 2,000 ft² one-family dwelling on a 120/240 V service has 2 small-appliance circuits, 1 laundry circuit, a 12 kW range, a 5 kW dryer, four fastened-in-place appliances totaling 8,100 VA, 10 kW of fixed electric heat, and a 6 kVA air conditioner. What is the calculated load in amperes?

    • 128 A
    • 130 A
    • 136 A
    • 145 A

    Answer: 145 A

    Why: General load: 6,000 + 3,000 + 1,500 = 10,500 VA, reduced by Table 220.45 to 3,000 + (7,500 × 0.35) = 5,625 VA. Add the range at 8,000 VA (Table 220.55, Column C), the dryer at 5,000 VA (220.54), the appliances at 8,100 × 0.75 = 6,075 VA (220.53), and the larger of heat or AC, 10,000 VA (220.51, 220.60). Total 34,700 VA ÷ 240 V = 144.58 A, which rounds to 145 A (220.5(B)). (NEC Table 220.45, 220.51, 220.53, 220.54, Table 220.55, 220.60, 220.5(B)) Edition note: 2023 NEC numbering. In the 2026 NEC, load calculations moved from Article 220 to Article 120. The dwelling demand tiers were Table 220.42 in the 2020 NEC and are Table 220.45 in 2023.

  6. A 22 kW, 240 V, single-phase standby generator is rated at unity power factor. What minimum ampacity must the conductors from its output terminals to the first overcurrent device have?

    • 60.9 A
    • 91.7 A
    • 105.4 A
    • 114.6 A

    Answer: 105.4 A

    Why: Rated current is 22,000 ÷ 240 = 91.67 A. 445.13(A) requires these conductors to be rated at least 115 % of the nameplate current: 91.67 × 1.15 = 105.42 A, about 105.4 A. (NEC 445.13(A))

  7. A metal device box with internal cable clamps has two 14/2 NM cables with ground entering it. A single-pole switch is installed, and the two bare grounds are spliced with a pigtail to the switch. What minimum box volume is required?

    • 14.00 in.³
    • 16.00 in.³
    • 18.00 in.³
    • 20.00 in.³

    Answer: 16.00 in.³

    Why: Count by 314.16(B) at 2.00 in.³ for 14 AWG: four insulated conductors (8.00), one allowance for all grounds (2.00), one for the clamps (2.00), and two for the switch yoke (4.00). Total 16.00 in.³. The pigtail never leaves the box, so it counts zero. (NEC 314.16(B)(1), 314.16(B)(2), 314.16(B)(4), 314.16(B)(5), Table 314.16(B))

  8. A 6 AWG THWN copper conductor (75 °C terminations, no correction or adjustment) supplies a single fixed 55 A noncontinuous load on an individual branch circuit. What is the largest breaker that may protect it?

    • 60 A
    • 70 A
    • 75 A
    • 80 A

    Answer: 70 A

    Why: 6 AWG copper at 75 °C is 65 A, which isn't a standard rating. 240.4(B) lets you use the next higher standard rating, 70 A, because the circuit doesn't supply multiple receptacles for portable loads and the rating is under 800 A. (NEC 240.4(B), 240.6(A), Table 310.16)

  9. A load draws 100 kVA at a power factor of 0.8. How much real power does it use?

    • 60 kW
    • 80 kW
    • 100 kW
    • 125 kW

    Answer: 80 kW

    Why: Power factor is the share of apparent power that does real work: kW = kVA × PF = 100 × 0.8 = 80 kW. The remaining side of the triangle is √(100² − 80²) = 60 kVAR of reactive power.

  10. A 10 hp, 460 V, three-phase induction motor has a nameplate full-load current of 13 A. What minimum ampacity must its branch-circuit conductors have?

    • 14.0 A
    • 16.1 A
    • 16.25 A
    • 17.5 A

    Answer: 17.5 A

    Why: Conductor sizing starts from the table full-load current, not the nameplate (430.6(A)(1)). Table 430.250 gives 14 A for 10 hp at 460 V, and 430.22 requires conductors rated at least 125 % of that: 14 × 1.25 = 17.5 A. (NEC 430.6(A)(1), Table 430.250, 430.22)

  11. A 15 hp, three-phase induction motor is connected to a 208 V system and is rated 208 V. What minimum ampacity must its branch-circuit conductors have?

    • 52.50 A
    • 53.13 A
    • 57.75 A
    • 60.38 A

    Answer: 57.75 A

    Why: Use the 208 V column of Table 430.250, which lists 46.2 A for 15 hp. Branch-circuit conductors for one motor must be rated at least 125 % of that current (430.22): 46.2 × 1.25 = 57.75 A. (NEC Table 430.250, 430.22)

  12. A 120 V individual branch circuit supplies one piece of fixed equipment that draws 18 A for 8 hours at a time, and no other load. What minimum standard-size overcurrent device does 210.20(A) require?

    • 15 A
    • 20 A
    • 25 A
    • 30 A

    Answer: 25 A

    Why: The equipment runs 3 hours or more, so it is a continuous load. 210.20(A) requires the overcurrent device to be at least the noncontinuous load plus 125 % of the continuous load: 18 A × 1.25 = 22.5 A. The next standard size in 240.6(A) is 25 A, which is permitted because this is an individual branch circuit (210.3). (NEC 210.20(A), 240.6(A), 210.3)

  13. A single PV string uses modules with a short-circuit current (Isc) of 9.6 A. Using the 125 % method, what is the maximum circuit current for this string? (Round to two decimals.)

    • 9.60 A
    • 11.04 A
    • 12.00 A
    • 15.00 A

    Answer: 12.00 A

    Why: 690.8(A)(1) sets the maximum current of a PV string at 125 % of the module Isc. The extra 25 % covers sunlight stronger than the standard test condition, such as cold, clear days with reflected light. 9.6 A × 1.25 = 12.00 A. A second 125 % is applied later, when you size conductors and overcurrent devices. (NEC 690.8(A)(1))

  14. A 30 A branch circuit uses 10 AWG THHN copper. Neither the breaker nor the receptacle terminals carry any temperature marking. Which ampacity column of Table 310.16 limits this conductor?

    • The 60 °C column
    • The 75 °C column
    • The 90 °C column
    • Any column, if the load is noncontinuous

    Answer: The 60 °C column

    Why: For circuits rated 100 A or less, or conductors 14 through 1 AWG, 110.14(C)(1)(a) assumes 60 °C terminations unless the equipment is listed and marked for a higher rating. 10 AWG copper is 30 A in the 60 °C column, which happens to match this 30 A circuit. (NEC 110.14(C)(1)(a), Table 310.16)

  15. A coil with 0.1 H of inductance is connected to a 60 Hz supply. What is its inductive reactance?

    • 6.0 Ω
    • 18.8 Ω
    • 37.7 Ω
    • 377 Ω

    Answer: 37.7 Ω

    Why: XL = 2πfL. At 60 Hz, 2πf = 2 × 3.1416 × 60 = 377. Then XL = 377 × 0.1 = 37.7 Ω. Inductive reactance grows with both frequency and inductance.

  16. Under the 2023 NEC standard method, what demand load is used for a single 14 kW household electric range in a one-family dwelling?

    • 8.0 kW
    • 8.8 kW
    • 10.5 kW
    • 14.0 kW

    Answer: 8.8 kW

    Why: Table 220.55 Column C gives 8 kW for one range rated not over 12 kW. Note 1 raises the Column C value by 5 % for each kW (or major fraction) above 12 kW. A 14 kW range is 2 kW over, so 8 kW × 1.10 = 8.8 kW. (NEC 220.55, Table 220.55) Edition note: 2023 NEC numbering. In the 2026 NEC, load calculations moved from Article 220 to Article 120.

  17. A section says a wiring method 'shall be permitted' in a certain location. Under 90.5, what does that language mean?

    • The method is allowed but not required
    • The method is required in that location
    • The method needs special permission first
    • The text is explanatory and not enforceable

    Answer: The method is allowed but not required

    Why: Section 90.5 sorts code text into mandatory rules ('shall', 'shall not'), permissive rules ('shall be permitted', 'shall not be required') and explanatory material. A permissive rule allows an action without demanding it, so you may use the method but are not forced to. (NEC 90.5(A), 90.5(B))

  18. In which installation is the next-size-up allowance of 240.4(B) NOT permitted?

    • A multioutlet receptacle branch circuit for portable loads
    • A feeder with 140 A ampacity protected by a 150 A breaker
    • An individual branch circuit to one fixed appliance
    • A feeder with 475 A ampacity protected at 500 A

    Answer: A multioutlet receptacle branch circuit for portable loads

    Why: 240.4(B)(1) excludes branch circuits that supply more than one receptacle for cord-and-plug-connected portable loads. Any plug on that circuit could draw up to the breaker rating, so the breaker must not exceed the conductor ampacity. (NEC 240.4(B)(1))

  19. A general-purpose branch circuit uses 12 AWG THHN copper with 75 °C terminations. No correction or adjustment applies, and no special exception (such as a motor circuit) is involved. What is the largest overcurrent device permitted?

    • 15 A
    • 20 A
    • 25 A
    • 30 A

    Answer: 20 A

    Why: Table 310.16 lists 12 AWG copper at 25 A (75 °C) and 30 A (90 °C), but 240.4(D) caps the overcurrent protection of 12 AWG copper at 20 A. The small-conductor rule wins unless a specific section such as 240.4(G) permits otherwise. (NEC 240.4(D), Table 310.16)

  20. A single-phase transformer steps 7,200 V down to 240 V. The secondary load draws 90 A. Ignoring losses, how much current flows in the primary?

    • 1.5 A
    • 3.0 A
    • 90.0 A
    • 2,700.0 A

    Answer: 3.0 A

    Why: The turns ratio equals the voltage ratio: 7,200 ÷ 240 = 30. Current changes the opposite way to voltage, so the primary carries 90 ÷ 30 = 3 A. Check: 7,200 × 3 = 21,600 VA and 240 × 90 = 21,600 VA.