FREE · NO SIGN-UP · NEC REFERENCES

Connecticut Journeyman Electrician Practice Test

20 questions in the style of the Connecticut journeyman exam (PSI): NEC rules, code navigation and calculations. Pick an answer, check it, and read why — with the section to look up.

The real Connecticut exam: 80 questions in 3 h 30 min, open book, 2020 or 2023 NEC. Full Connecticut exam guide →

Question 1 of 20Wiring methods, boxes & raceways
PUT IT INTO PRACTICE

A ceiling box with internal clamps and a luminaire stud has two 14/2 NM cables with ground entering it. The luminaire's two 18 AWG fixture wires and its grounding conductor come in from a domed canopy. What minimum box volume is required?

Given conditions

Copper conductors

Select your answer
Report a problem with this question

Describe the content issue. Do not include private patient or workplace information.

Pick an answer and check it.

See all 20 questions with answers and explanations
  1. A ceiling box with internal clamps and a luminaire stud has two 14/2 NM cables with ground entering it. The luminaire's two 18 AWG fixture wires and its grounding conductor come in from a domed canopy. What minimum box volume is required?

    • 12.00 in.³
    • 14.00 in.³
    • 16.00 in.³
    • 17.00 in.³

    Answer: 14.00 in.³

    Why: Four 14 AWG conductors take 8.00 in.³. Grounds, clamps and the stud each take one 2.00 in.³ allowance, adding 6.00. The fixture wires and the luminaire ground from a domed canopy may be left out (exception to 314.16(B)(1)). Total 14.00 in.³. (NEC 314.16(B)(1) Exception, 314.16(B)(3), Table 314.16(B))

  2. A 6 AWG THWN copper conductor (75 °C terminations, no correction or adjustment) supplies a single fixed 55 A noncontinuous load on an individual branch circuit. What is the largest breaker that may protect it?

    • 60 A
    • 70 A
    • 75 A
    • 80 A

    Answer: 70 A

    Why: 6 AWG copper at 75 °C is 65 A, which isn't a standard rating. 240.4(B) lets you use the next higher standard rating, 70 A, because the circuit doesn't supply multiple receptacles for portable loads and the rating is under 800 A. (NEC 240.4(B), 240.6(A), Table 310.16)

  3. Under the 2023 NEC optional method for a one-family dwelling (220.82), the first 10 kVA of the general load is taken at 100 %. At what percentage is the rest of the general load taken?

    • 25 %
    • 35 %
    • 40 %
    • 65 %

    Answer: 40 %

    Why: 220.82(B) takes the first 10 kVA of the general load at 100 % and everything above that at 40 %. Heating and air conditioning are not in that pile; they are added separately under 220.82(C). (NEC 220.82(B)) Edition note: 2023 NEC numbering. In the 2026 NEC, load calculations moved from Article 220 to Article 120.

  4. Under the 2023 NEC standard method, a 2,000 ft² one-family dwelling on a 120/240 V service has 2 small-appliance circuits, 1 laundry circuit, a 12 kW range, a 5 kW dryer, four fastened-in-place appliances totaling 8,100 VA, 10 kW of fixed electric heat, and a 6 kVA air conditioner. What is the calculated load in amperes?

    • 128 A
    • 130 A
    • 136 A
    • 145 A

    Answer: 145 A

    Why: General load: 6,000 + 3,000 + 1,500 = 10,500 VA, reduced by Table 220.45 to 3,000 + (7,500 × 0.35) = 5,625 VA. Add the range at 8,000 VA (Table 220.55, Column C), the dryer at 5,000 VA (220.54), the appliances at 8,100 × 0.75 = 6,075 VA (220.53), and the larger of heat or AC, 10,000 VA (220.51, 220.60). Total 34,700 VA ÷ 240 V = 144.58 A, which rounds to 145 A (220.5(B)). (NEC Table 220.45, 220.51, 220.53, 220.54, Table 220.55, 220.60, 220.5(B)) Edition note: 2023 NEC numbering. In the 2026 NEC, load calculations moved from Article 220 to Article 120. The dwelling demand tiers were Table 220.42 in the 2020 NEC and are Table 220.45 in 2023.

  5. A 2 hp, 115 V, single-phase motor drives a shop air compressor (not a hermetic refrigerant compressor). What minimum ampacity must its branch-circuit conductors have?

    • 15.0 A
    • 24.0 A
    • 27.6 A
    • 30.0 A

    Answer: 30.0 A

    Why: Single-phase motors use Table 430.248, which lists 24 A for 2 hp at 115 V. 430.22 requires 125 %: 24 × 1.25 = 30 A. (NEC Table 430.248, 430.22)

  6. Under 90.3, which chapters of the NEC apply generally to all electrical installations?

    • Chapters 1 through 7
    • Chapters 1 through 3
    • Chapters 1 through 9
    • Chapters 1 through 4

    Answer: Chapters 1 through 4

    Why: Section 90.3 says Chapters 1 through 4 apply generally. Chapters 5, 6 and 7 apply to special occupancies, special equipment and special conditions and may supplement or modify the general rules. Knowing this split tells you where to look first. (NEC 90.3)

  7. A 10 hp, 460 V, three-phase motor has a nameplate full-load current of 13 A and a service factor of 1.15. What is the maximum trip setting for a separate overload device, using the basic rule?

    • 16.25 A
    • 16.90 A
    • 17.50 A
    • 18.20 A

    Answer: 16.25 A

    Why: Overloads are sized from the nameplate current (430.6(A)(2)). With a service factor of 1.15 or more, 430.32(A)(1) allows up to 125 %: 13 × 1.25 = 16.25 A. (NEC 430.6(A)(2), 430.32(A)(1))

  8. On a 480 V, three-phase, four-wire wye system, what voltage should you measure from any phase conductor to the neutral?

    • 277 V
    • 339 V
    • 480 V
    • 831 V

    Answer: 277 V

    Why: In a wye, line voltage = phase voltage × 1.732, so phase voltage = 480 ÷ 1.732 = 277 V. That's why the system is called 480Y/277 V and why 277 V lighting runs phase to neutral.

  9. A loose splice on a branch circuit has 0.05 Ω of resistance and carries 40 A. How much power is turned into heat at the splice?

    • 2 W
    • 80 W
    • 800 W
    • 1,600 W

    Answer: 80 W

    Why: With amps and ohms given, use P = I² × R: 40² × 0.05 = 1,600 × 0.05 = 80 W. That is a small lamp's worth of heat buried in a box. Because heat rises with the square of current, a bad termination that is fine at light load can scorch at heavy load.

  10. A 480Y/277 V panelboard has exposed live parts on one side of the working space and a concrete block wall on the other. What minimum depth of working space does Table 110.26(A)(1) require?

    • 3 ft
    • 3½ ft
    • 4 ft
    • 5 ft

    Answer: 3½ ft

    Why: Enter the table with voltage to ground: 277 V falls in the 151–1000 V row. Concrete, brick and tile walls are considered grounded, so live parts across from a block wall is Condition 2. The minimum depth is 3½ ft (1.0 m). (NEC 110.26(A)(1), Table 110.26(A)(1))

  11. In a dwelling, which 120 V, 15 A receptacle requires GFCI protection under 210.8(A)?

    • A receptacle beside the bed in a bedroom
    • A receptacle in an upstairs hallway
    • A receptacle in the dining room
    • A receptacle in an unfinished basement

    Answer: A receptacle in an unfinished basement

    Why: Basements are on the 210.8(A) list of dwelling locations where 125 V through 250 V receptacles need GFCI protection. Bedrooms, hallways and dining rooms are not on the list, though they do need AFCI protection under 210.12. (NEC 210.8(A))

  12. Under the 2023 NEC standard method, what demand load is used for a single 14 kW household electric range in a one-family dwelling?

    • 8.0 kW
    • 8.8 kW
    • 10.5 kW
    • 14.0 kW

    Answer: 8.8 kW

    Why: Table 220.55 Column C gives 8 kW for one range rated not over 12 kW. Note 1 raises the Column C value by 5 % for each kW (or major fraction) above 12 kW. A 14 kW range is 2 kW over, so 8 kW × 1.10 = 8.8 kW. (NEC 220.55, Table 220.55) Edition note: 2023 NEC numbering. In the 2026 NEC, load calculations moved from Article 220 to Article 120.

  13. A 60 A circuit breaker protects 6 AWG copper feeder conductors to a subpanel in the same building. The conductors are not upsized. What minimum size copper equipment grounding conductor is required?

    • 12 AWG
    • 10 AWG
    • 8 AWG
    • 6 AWG

    Answer: 10 AWG

    Why: Table 250.122 sizes the EGC from the rating of the overcurrent device ahead of the circuit. The 60 A row calls for 10 AWG copper. The size of the circuit conductors doesn't set the EGC unless they were upsized (250.122(B)). (NEC 250.122(A), Table 250.122)

  14. A 75 kVA, three-phase transformer is rated 480 V delta primary, 208Y/120 V secondary. What is its full-load primary current?

    • 90.21 A
    • 156.25 A
    • 208.18 A
    • 270.63 A

    Answer: 90.21 A

    Why: Three-phase current is VA ÷ (1.732 × line volts). On the primary: 75,000 ÷ (1.732 × 480) = 75,000 ÷ 831.36 = 90.21 A.

  15. A single-phase transformer steps 7,200 V down to 240 V. The secondary load draws 90 A. Ignoring losses, how much current flows in the primary?

    • 1.5 A
    • 3.0 A
    • 90.0 A
    • 2,700.0 A

    Answer: 3.0 A

    Why: The turns ratio equals the voltage ratio: 7,200 ÷ 240 = 30. Current changes the opposite way to voltage, so the primary carries 90 ÷ 30 = 3 A. Check: 7,200 × 3 = 21,600 VA and 240 × 90 = 21,600 VA.

  16. A 250 kcmil THWN-2 copper feeder lands on switchboard lugs that carry no temperature marking. There are three current-carrying conductors at a 30 °C ambient. What ampacity may be used for this conductor?

    • 205 A
    • 215 A
    • 230 A
    • 255 A

    Answer: 255 A

    Why: For conductors larger than 1 AWG (or circuits over 100 A), 110.14(C)(1)(b) lets you use the 75 °C column even without a marking. 250 kcmil copper is 255 A at 75 °C in Table 310.16. The 90 °C value of 290 A is not usable at these terminations. (NEC 110.14(C)(1)(b), Table 310.16)

  17. A 10 hp, 460 V, three-phase induction motor has a nameplate full-load current of 13 A. What minimum ampacity must its branch-circuit conductors have?

    • 14.0 A
    • 16.1 A
    • 16.25 A
    • 17.5 A

    Answer: 17.5 A

    Why: Conductor sizing starts from the table full-load current, not the nameplate (430.6(A)(1)). Table 430.250 gives 14 A for 10 hp at 460 V, and 430.22 requires conductors rated at least 125 % of that: 14 × 1.25 = 17.5 A. (NEC 430.6(A)(1), Table 430.250, 430.22)

  18. A metal device box with internal cable clamps has two 14/2 NM cables with ground entering it. A single-pole switch is installed, and the two bare grounds are spliced with a pigtail to the switch. What minimum box volume is required?

    • 14.00 in.³
    • 16.00 in.³
    • 18.00 in.³
    • 20.00 in.³

    Answer: 16.00 in.³

    Why: Count by 314.16(B) at 2.00 in.³ for 14 AWG: four insulated conductors (8.00), one allowance for all grounds (2.00), one for the clamps (2.00), and two for the switch yoke (4.00). Total 16.00 in.³. The pigtail never leaves the box, so it counts zero. (NEC 314.16(B)(1), 314.16(B)(2), 314.16(B)(4), 314.16(B)(5), Table 314.16(B))

  19. An office building has an emergency system for egress lighting required by the building code. After normal power fails, within what time must the emergency system supply power?

    • 10 seconds
    • 30 seconds
    • 60 seconds
    • 90 seconds

    Answer: 10 seconds

    Why: 700.12 requires emergency lighting and power to be available within the time needed for the application, but no more than 10 seconds. Emergency systems protect life during evacuation, so people cannot be left in the dark for long. Legally required standby gets 60 seconds; optional standby has no time limit. (NEC 700.12)

  20. A 15 hp, three-phase induction motor is connected to a 208 V system and is rated 208 V. What minimum ampacity must its branch-circuit conductors have?

    • 52.50 A
    • 53.13 A
    • 57.75 A
    • 60.38 A

    Answer: 57.75 A

    Why: Use the 208 V column of Table 430.250, which lists 46.2 A for 15 hp. Branch-circuit conductors for one motor must be rated at least 125 % of that current (430.22): 46.2 × 1.25 = 57.75 A. (NEC Table 430.250, 430.22)

Original practice questions written for Ohmward on the 2023 NEC — not real exam items.