Florida Journeyman Electrician Practice Test
20 questions in the style of the Florida journeyman exam: NEC rules, code navigation and calculations. Pick an answer, check it, and read why — with the section to look up.
A section says a wiring method 'shall be permitted' in a certain location. Under 90.5, what does that language mean?
Report a problem with this question
See all 20 questions with answers and explanations
A section says a wiring method 'shall be permitted' in a certain location. Under 90.5, what does that language mean?
- The method is allowed but not required
- The method is required in that location
- The method needs special permission first
- The text is explanatory and not enforceable
Answer: The method is allowed but not required
Why: Section 90.5 sorts code text into mandatory rules ('shall', 'shall not'), permissive rules ('shall be permitted', 'shall not be required') and explanatory material. A permissive rule allows an action without demanding it, so you may use the method but are not forced to. (NEC 90.5(A), 90.5(B))
A load draws 100 kVA at a power factor of 0.8. How much real power does it use?
- 60 kW
- 80 kW
- 100 kW
- 125 kW
Answer: 80 kW
Why: Power factor is the share of apparent power that does real work: kW = kVA × PF = 100 × 0.8 = 80 kW. The remaining side of the triangle is √(100² − 80²) = 60 kVAR of reactive power.
A box with internal clamps contains two 12/2 NM cables spliced through for a 20 A circuit and one 14/2 NM cable feeding a 15 A duplex receptacle in the same box. All three cables have bare grounds. What minimum box volume is required?
- 21.50 in.³
- 22.00 in.³
- 23.50 in.³
- 24.00 in.³
Answer: 21.50 in.³
Why: Each conductor counts at its own size: 4 × 2.25 = 9.00 plus 2 × 2.00 = 4.00. Grounds take one allowance at the largest ground (12 AWG, 2.25) and clamps one at the largest conductor (12 AWG, 2.25). The receptacle is connected only to 14 AWG, so it takes 2 × 2.00 = 4.00 (314.16(B)(4)). Total 21.50 in.³. (NEC 314.16(B)(2), 314.16(B)(4), 314.16(B)(5), Table 314.16(B))
Under the 2023 NEC standard method, what demand load is used for a single 14 kW household electric range in a one-family dwelling?
- 8.0 kW
- 8.8 kW
- 10.5 kW
- 14.0 kW
Answer: 8.8 kW
Why: Table 220.55 Column C gives 8 kW for one range rated not over 12 kW. Note 1 raises the Column C value by 5 % for each kW (or major fraction) above 12 kW. A 14 kW range is 2 kW over, so 8 kW × 1.10 = 8.8 kW. (NEC 220.55, Table 220.55) Edition note: 2023 NEC numbering. In the 2026 NEC, load calculations moved from Article 220 to Article 120.
A 30 A branch circuit uses 10 AWG THHN copper. Neither the breaker nor the receptacle terminals carry any temperature marking. Which ampacity column of Table 310.16 limits this conductor?
- The 60 °C column
- The 75 °C column
- The 90 °C column
- Any column, if the load is noncontinuous
Answer: The 60 °C column
Why: For circuits rated 100 A or less, or conductors 14 through 1 AWG, 110.14(C)(1)(a) assumes 60 °C terminations unless the equipment is listed and marked for a higher rating. 10 AWG copper is 30 A in the 60 °C column, which happens to match this 30 A circuit. (NEC 110.14(C)(1)(a), Table 310.16)
A single-phase transformer steps 7,200 V down to 240 V. The secondary load draws 90 A. Ignoring losses, how much current flows in the primary?
- 1.5 A
- 3.0 A
- 90.0 A
- 2,700.0 A
Answer: 3.0 A
Why: The turns ratio equals the voltage ratio: 7,200 ÷ 240 = 30. Current changes the opposite way to voltage, so the primary carries 90 ÷ 30 = 3 A. Check: 7,200 × 3 = 21,600 VA and 240 × 90 = 21,600 VA.
A general-purpose branch circuit uses 12 AWG THHN copper with 75 °C terminations. No correction or adjustment applies, and no special exception (such as a motor circuit) is involved. What is the largest overcurrent device permitted?
- 15 A
- 20 A
- 25 A
- 30 A
Answer: 20 A
Why: Table 310.16 lists 12 AWG copper at 25 A (75 °C) and 30 A (90 °C), but 240.4(D) caps the overcurrent protection of 12 AWG copper at 20 A. The small-conductor rule wins unless a specific section such as 240.4(G) permits otherwise. (NEC 240.4(D), Table 310.16)
A balanced three-phase, 208 V load draws 150 A on each line. How many kVA does it draw?
- 18.0 kVA
- 31.2 kVA
- 54.0 kVA
- 93.6 kVA
Answer: 54.0 kVA
Why: Three-phase kVA = 1.732 × line volts × line amps ÷ 1,000 = 1.732 × 208 × 150 ÷ 1,000 = 54.04 kVA, which rounds to 54.0 kVA. The same answer comes from 3 × 120 V × 150 A per phase.
A 75 kVA, three-phase, 480 V to 208Y/120 V transformer is protected on the primary side only. What is the largest standard primary breaker permitted by Table 450.3(B) and its notes?
- 90 A
- 100 A
- 110 A
- 125 A
Answer: 125 A
Why: Primary current is 75,000 ÷ (1.732 × 480) = 90.21 A. Primary-only protection for 9 A or more is 125 %: 90.21 × 1.25 = 112.77 A. Table 450.3(B) Note 1 permits the next higher standard size, 125 A. (NEC 450.3(B), Table 450.3(B), 240.6(A))
A 72 A noncontinuous load is supplied by three THHN copper conductors in EMT at a 30 °C ambient. The breaker and the load terminals are listed and marked for 75 °C. What is the minimum conductor size?
- 6 AWG
- 4 AWG
- 3 AWG
- 2 AWG
Answer: 4 AWG
Why: THHN is a 90 °C conductor, but the 75 °C terminals limit the ampacity you may use (110.14(C)(1)(a)). In the 75 °C copper column of Table 310.16, 6 AWG is 65 A (too small) and 4 AWG is 85 A, so 4 AWG is the smallest that carries 72 A. (NEC 110.14(C)(1)(a), Table 310.16)
A feeder supplies 90 A of continuous lighting load and no other load. The breaker is not listed for 100 % operation. What is the minimum standard breaker rating?
- 90 A
- 110 A
- 125 A
- 150 A
Answer: 125 A
Why: 215.3 requires the feeder overcurrent device to be at least 125 % of the continuous load: 90 × 1.25 = 112.5 A. 112.5 A isn't a standard rating, so go up to the next standard size in 240.6(A), 125 A. (NEC 215.3, 240.6(A))
An inspector finds the neutral bonded to the enclosure in a feeder-supplied panelboard downstream of the service, in the same building. With that bond in place, where does part of the normal neutral current return to the service?
- On the EGCs, raceways, and other bonded metal
- Only into the earth through the ground rods
- Nowhere, since a bond carries only fault current
- Back through the ungrounded feeder conductors
Answer: On the EGCs, raceways, and other bonded metal
Why: The extra bond puts the feeder EGC, metal raceways, and any bonded piping in parallel with the neutral. Current divides among parallel paths, so part of the normal neutral current flows on metal that people touch. That's objectionable current under 250.6, and it's why 250.24(A)(5) and 250.142(B) prohibit the bond. (NEC 250.6(A), 250.24(A)(5), 250.142(B))
A 120 V individual branch circuit supplies one piece of fixed equipment that draws 18 A for 8 hours at a time, and no other load. What minimum standard-size overcurrent device does 210.20(A) require?
- 15 A
- 20 A
- 25 A
- 30 A
Answer: 25 A
Why: The equipment runs 3 hours or more, so it is a continuous load. 210.20(A) requires the overcurrent device to be at least the noncontinuous load plus 125 % of the continuous load: 18 A × 1.25 = 22.5 A. The next standard size in 240.6(A) is 25 A, which is permitted because this is an individual branch circuit (210.3). (NEC 210.20(A), 240.6(A), 210.3)
A 60 A circuit breaker protects 6 AWG copper feeder conductors to a subpanel in the same building. The conductors are not upsized. What minimum size copper equipment grounding conductor is required?
- 12 AWG
- 10 AWG
- 8 AWG
- 6 AWG
Answer: 10 AWG
Why: Table 250.122 sizes the EGC from the rating of the overcurrent device ahead of the circuit. The 60 A row calls for 10 AWG copper. The size of the circuit conductors doesn't set the EGC unless they were upsized (250.122(B)). (NEC 250.122(A), Table 250.122)
A one-family dwelling has a 125 A, 120/240 V, single-phase service supplying the entire dwelling load. Using 310.12 with copper THWN-2 conductors, 75 °C terminations, and no adjustment or correction factors, what is the minimum ungrounded service-entrance conductor size?
- 3 AWG
- 2 AWG
- 1 AWG
- 1/0 AWG
Answer: 2 AWG
Why: 310.12 lets the conductors of a 120/240 V single-phase dwelling service be sized at 83 % of the service rating: 125 × 0.83 = 103.75 A. In the 75 °C copper column of Table 310.16, 3 AWG is 100 A (too small) and 2 AWG is 115 A. So 2 AWG copper is the minimum. (NEC 310.12, Table 310.16)
A resistive water heater element has a resistance of 16 Ω and is connected to 240 V. How much current does it draw?
- 0.067 A
- 7.5 A
- 15 A
- 3,840 A
Answer: 15 A
Why: Ohm's law: current equals voltage divided by resistance, I = E ÷ R. Here 240 V ÷ 16 Ω = 15 A. Think of it as push divided by opposition: more volts push more amps, more ohms hold them back.
A 10 hp, 460 V, three-phase motor has a nameplate full-load current of 13 A and a service factor of 1.15. What is the maximum trip setting for a separate overload device, using the basic rule?
- 16.25 A
- 16.90 A
- 17.50 A
- 18.20 A
Answer: 16.25 A
Why: Overloads are sized from the nameplate current (430.6(A)(2)). With a service factor of 1.15 or more, 430.32(A)(1) allows up to 125 %: 13 × 1.25 = 16.25 A. (NEC 430.6(A)(2), 430.32(A)(1))
The supply frequency to a circuit rises from 50 Hz to 60 Hz. What happens to inductive reactance (XL) and capacitive reactance (XC)?
- XL rises and XC rises
- XL falls and XC rises
- XL falls and XC falls
- XL rises and XC falls
Answer: XL rises and XC falls
Why: XL = 2πfL, so it rises in step with frequency. XC = 1 ÷ (2πfC), so frequency is in the denominator and XC falls as frequency rises. Coils fight fast changes harder; capacitors pass them more easily.
In which installation is the next-size-up allowance of 240.4(B) NOT permitted?
- A multioutlet receptacle branch circuit for portable loads
- A feeder with 140 A ampacity protected by a 150 A breaker
- An individual branch circuit to one fixed appliance
- A feeder with 475 A ampacity protected at 500 A
Answer: A multioutlet receptacle branch circuit for portable loads
Why: 240.4(B)(1) excludes branch circuits that supply more than one receptacle for cord-and-plug-connected portable loads. Any plug on that circuit could draw up to the breaker rating, so the breaker must not exceed the conductor ampacity. (NEC 240.4(B)(1))
You are sizing the branch-circuit short-circuit and ground-fault protective device for a general-purpose three-phase squirrel-cage motor. Which current do you start from?
- The nameplate full-load current
- The locked-rotor current on the nameplate
- The full-load current from Table 430.250
- The service-factor current on the nameplate
Answer: The full-load current from Table 430.250
Why: 430.6(A)(1) sends you to the FLC tables for conductor ampacity, switch ratings and the short-circuit and ground-fault device. Table values are conservative and let the circuit be designed before the exact motor arrives. The nameplate value is used for separate overload protection. (NEC 430.6(A)(1), 430.6(A)(2), Table 430.250)
Original practice questions written for Ohmward on the 2023 NEC — not real exam items.