Question 1 of 20AC, power factor & three-phase
PUT IT INTO PRACTICE

In a purely capacitive AC circuit, how does the current relate to the voltage?

Select your answer
Report a problem with this question

Describe the content issue. Do not include private patient or workplace information.

Pick an answer and check it.

See all 20 questions with answers and explanations
  1. In a purely capacitive AC circuit, how does the current relate to the voltage?

    • It lags the voltage by 90°
    • It is in phase with the voltage
    • It lags the voltage by 45°
    • It leads the voltage by 90°

    Answer: It leads the voltage by 90°

    Why: A capacitor's current is greatest when the voltage is changing fastest, a quarter-cycle before the voltage peaks. So current leads voltage by 90°. Memory aid: ELI the ICE man. In C, I comes before E.

  2. A 30 hp, 460 V, three-phase motor has a nameplate full-load current of 38 A. What minimum ampere rating must its disconnecting means have?

    • 34.8 A
    • 40.0 A
    • 43.7 A
    • 46.0 A

    Answer: 46.0 A

    Why: 430.110(A) requires the disconnect to be rated at least 115 % of the motor's full-load current, and 430.6(A)(1) says switch ratings come from the table. Table 430.250 gives 40 A: 40 × 1.15 = 46 A. (NEC 430.110(A), 430.6(A)(1), Table 430.250)

  3. On a 480 V, three-phase, four-wire wye system, what voltage should you measure from any phase conductor to the neutral?

    • 277 V
    • 339 V
    • 480 V
    • 831 V

    Answer: 277 V

    Why: In a wye, line voltage = phase voltage × 1.732, so phase voltage = 480 ÷ 1.732 = 277 V. That's why the system is called 480Y/277 V and why 277 V lighting runs phase to neutral.

  4. Type NM cable is run along the side of a floor joist to a metal device box. Under the general rule of 334.30, what are the maximum distances for securing the cable?

    • Within 12 in. of the box, then every 4-1/2 ft
    • Within 12 in. of the box, then every 6 ft
    • Within 18 in. of the box, then every 4-1/2 ft
    • Within 3 ft of the box, then every 10 ft

    Answer: Within 12 in. of the box, then every 4-1/2 ft

    Why: 334.30 requires NM cable to be secured within 12 in. of every box, cabinet or fitting and at intervals not over 4-1/2 ft. The 12 in. rule keeps the cable from pulling out of the clamp; the 4-1/2 ft spacing keeps it tight to the framing. (NEC 334.30)

  5. A loose splice on a branch circuit has 0.05 Ω of resistance and carries 40 A. How much power is turned into heat at the splice?

    • 2 W
    • 80 W
    • 800 W
    • 1,600 W

    Answer: 80 W

    Why: With amps and ohms given, use P = I² × R: 40² × 0.05 = 1,600 × 0.05 = 80 W. That is a small lamp's worth of heat buried in a box. Because heat rises with the square of current, a bad termination that is fine at light load can scorch at heavy load.

  6. Along an unbroken living room wall, what is the maximum distance from any point on the floor line to the nearest receptacle outlet?

    • 4 ft
    • 6 ft
    • 10 ft
    • 12 ft

    Answer: 6 ft

    Why: 210.52(A)(1) requires receptacles placed so that no point along the floor line of any wall space is more than 6 ft from a receptacle outlet. That allows receptacles up to 12 ft apart. (NEC 210.52(A)(1))

  7. Article 100 defines a continuous load as one where the maximum current is expected to continue for how long?

    • 30 minutes or more
    • 1 hour or more
    • 2 hours or more
    • 3 hours or more

    Answer: 3 hours or more

    Why: Article 100 defines a continuous load as a load where the maximum current is expected to continue for 3 hours or more. Store lighting, office lighting and EV charging are typical examples. (NEC Article 100 (Continuous Load))

  8. Under the 2023 NEC, a one-family dwelling has 1,800 ft² of living space (outside dimensions), a 400 ft² attached garage, and a 200 ft² open front porch. Using the standard method, what is the general lighting load before any demand factor?

    • 5,400 VA
    • 6,000 VA
    • 6,600 VA
    • 7,200 VA

    Answer: 5,400 VA

    Why: 220.41 assigns 3 VA per square foot to dwelling units, but 220.5(C) counts only floor area that is, or can become, living space, measured from outside dimensions. Garages, open porches, and unfinished space not adaptable for future use are left out. 1,800 ft² × 3 VA = 5,400 VA. (NEC 220.5(C), 220.41) Edition note: 2023 NEC numbering. In the 2026 NEC, load calculations moved from Article 220 to Article 120. In the 2020 NEC the 3 VA/ft² dwelling load was in 220.14(J) and floor area in 220.11.

  9. You need the requirements for a rooftop solar photovoltaic system (Article 690). Which chapter of the NEC contains it?

    • Chapter 5
    • Chapter 6
    • Chapter 7
    • Chapter 8

    Answer: Chapter 6

    Why: Chapter 6 covers special equipment, including signs, elevators, EV charging, pools (680) and solar PV (690). The first digit of the article number is the chapter: 690 is in Chapter 6. (NEC Article 690, 90.3)

  10. A ceiling box with internal clamps and a luminaire stud has two 14/2 NM cables with ground entering it. The luminaire's two 18 AWG fixture wires and its grounding conductor come in from a domed canopy. What minimum box volume is required?

    • 12.00 in.³
    • 14.00 in.³
    • 16.00 in.³
    • 17.00 in.³

    Answer: 14.00 in.³

    Why: Four 14 AWG conductors take 8.00 in.³. Grounds, clamps and the stud each take one 2.00 in.³ allowance, adding 6.00. The fixture wires and the luminaire ground from a domed canopy may be left out (exception to 314.16(B)(1)). Total 14.00 in.³. (NEC 314.16(B)(1) Exception, 314.16(B)(3), Table 314.16(B))

  11. Under the 2023 NEC optional method for a one-family dwelling (220.82), the first 10 kVA of the general load is taken at 100 %. At what percentage is the rest of the general load taken?

    • 25 %
    • 35 %
    • 40 %
    • 65 %

    Answer: 40 %

    Why: 220.82(B) takes the first 10 kVA of the general load at 100 % and everything above that at 40 %. Heating and air conditioning are not in that pile; they are added separately under 220.82(C). (NEC 220.82(B)) Edition note: 2023 NEC numbering. In the 2026 NEC, load calculations moved from Article 220 to Article 120.

  12. A 60 A circuit breaker protects 6 AWG copper feeder conductors to a subpanel in the same building. The conductors are not upsized. What minimum size copper equipment grounding conductor is required?

    • 12 AWG
    • 10 AWG
    • 8 AWG
    • 6 AWG

    Answer: 10 AWG

    Why: Table 250.122 sizes the EGC from the rating of the overcurrent device ahead of the circuit. The 60 A row calls for 10 AWG copper. The size of the circuit conductors doesn't set the EGC unless they were upsized (250.122(B)). (NEC 250.122(A), Table 250.122)

  13. An inspector finds the neutral bonded to the enclosure in a feeder-supplied panelboard downstream of the service, in the same building. With that bond in place, where does part of the normal neutral current return to the service?

    • On the EGCs, raceways, and other bonded metal
    • Only into the earth through the ground rods
    • Nowhere, since a bond carries only fault current
    • Back through the ungrounded feeder conductors

    Answer: On the EGCs, raceways, and other bonded metal

    Why: The extra bond puts the feeder EGC, metal raceways, and any bonded piping in parallel with the neutral. Current divides among parallel paths, so part of the normal neutral current flows on metal that people touch. That's objectionable current under 250.6, and it's why 250.24(A)(5) and 250.142(B) prohibit the bond. (NEC 250.6(A), 250.24(A)(5), 250.142(B))

  14. A 480Y/277 V panelboard has exposed live parts on one side of the working space and a concrete block wall on the other. What minimum depth of working space does Table 110.26(A)(1) require?

    • 3 ft
    • 3½ ft
    • 4 ft
    • 5 ft

    Answer: 3½ ft

    Why: Enter the table with voltage to ground: 277 V falls in the 151–1000 V row. Concrete, brick and tile walls are considered grounded, so live parts across from a block wall is Condition 2. The minimum depth is 3½ ft (1.0 m). (NEC 110.26(A)(1), Table 110.26(A)(1))

  15. A 25 ft feeder tap is taken from a feeder protected by a 300 A breaker. Under 240.21(B)(2), what is the minimum ampacity of the tap conductors?

    • 30 A
    • 100 A
    • 150 A
    • 300 A

    Answer: 100 A

    Why: 240.21(B)(2) requires a 25-ft tap to have an ampacity of at least one-third of the feeder overcurrent device rating: 300 ÷ 3 = 100 A. The tap must also end in a single breaker or set of fuses that limits the load to the tap's ampacity. (NEC 240.21(B)(2))

  16. A metal device box with internal cable clamps has two 14/2 NM cables with ground entering it. A single-pole switch is installed, and the two bare grounds are spliced with a pigtail to the switch. What minimum box volume is required?

    • 14.00 in.³
    • 16.00 in.³
    • 18.00 in.³
    • 20.00 in.³

    Answer: 16.00 in.³

    Why: Count by 314.16(B) at 2.00 in.³ for 14 AWG: four insulated conductors (8.00), one allowance for all grounds (2.00), one for the clamps (2.00), and two for the switch yoke (4.00). Total 16.00 in.³. The pigtail never leaves the box, so it counts zero. (NEC 314.16(B)(1), 314.16(B)(2), 314.16(B)(4), 314.16(B)(5), Table 314.16(B))

  17. A resistive heater is moved from a 120 V circuit to a 240 V circuit. If its resistance stays the same, how does its power compare with before?

    • One-quarter as much
    • One-half as much
    • Twice as much
    • Four times as much

    Answer: Four times as much

    Why: With resistance fixed, P = E² ÷ R. Doubling E makes E² four times larger, so the heater makes four times the watts. Current doubles too (I = E ÷ R), and twice the volts times twice the amps is four times the power. That is why a 120 V heater on 240 V fails fast.

  18. Resistors of 10 Ω, 20 Ω and 30 Ω are connected in series across 120 V. What is the voltage across the 30 Ω resistor?

    • 20 V
    • 40 V
    • 60 V
    • 120 V

    Answer: 60 V

    Why: In series the resistances add: 10 + 20 + 30 = 60 Ω, and the same current flows through each: 120 ÷ 60 = 2 A. The drop across the 30 Ω resistor is 2 A × 30 Ω = 60 V. The biggest resistor takes the biggest share, and the drops (20 + 40 + 60) add back to 120 V.

  19. A 4,500 W water heater element runs 3 hours a day for 30 days. Electricity costs $0.15 per kWh. What is the energy cost for the month?

    • $2.03
    • $20.25
    • $60.75
    • $60,750

    Answer: $60.75

    Why: Energy is power × time, billed in kilowatt-hours. Convert to kW first: 4,500 W = 4.5 kW. Energy = 4.5 kW × 3 h × 30 days = 405 kWh. Cost = 405 × $0.15 = $60.75.

  20. Five THHN conductors will be installed in a 60 ft run of EMT between two panelboards. What maximum percentage of the EMT's cross-sectional area may the conductors fill?

    • 31 %
    • 40 %
    • 53 %
    • 60 %

    Answer: 40 %

    Why: Chapter 9, Table 1 allows 40 % fill when a raceway holds more than two conductors. 53 % is for one conductor, 31 % for two, and 60 % only for nipples 24 in. or shorter. A 60 ft run is a full raceway, so 40 % applies. (NEC Chapter 9, Table 1)

Original practice questions written for Ohmward on the 2023 NEC — not real exam items.