Indiana Journeyman Electrician Practice Test
20 questions in the style of the Indiana journeyman exam: NEC rules, code navigation and calculations. Pick an answer, check it, and read why — with the section to look up.
A one-family dwelling has a 125 A, 120/240 V, single-phase service supplying the entire dwelling load. Using 310.12 with copper THWN-2 conductors, 75 °C terminations, and no adjustment or correction factors, what is the minimum ungrounded service-entrance conductor size?
Given conditions
Copper conductors, 75 °C terminations
No ambient correction or bundling adjustment
Report a problem with this question
See all 20 questions with answers and explanations
A one-family dwelling has a 125 A, 120/240 V, single-phase service supplying the entire dwelling load. Using 310.12 with copper THWN-2 conductors, 75 °C terminations, and no adjustment or correction factors, what is the minimum ungrounded service-entrance conductor size?
- 3 AWG
- 2 AWG
- 1 AWG
- 1/0 AWG
Answer: 2 AWG
Why: 310.12 lets the conductors of a 120/240 V single-phase dwelling service be sized at 83 % of the service rating: 125 × 0.83 = 103.75 A. In the 75 °C copper column of Table 310.16, 3 AWG is 100 A (too small) and 2 AWG is 115 A. So 2 AWG copper is the minimum. (NEC 310.12, Table 310.16)
You are pouring a 1-1/2 in. trade size sealing fitting in a Class I, Division 1 location. The fitting has no marking that calls for a different depth. What is the minimum thickness of sealing compound?
- 5/8 in.
- 3/4 in.
- 1-1/2 in.
- 2 in.
Answer: 1-1/2 in.
Why: The compound must be at least as thick as the trade size of the sealing fitting, and never less than 5/8 in. (501.15(C)(3)). For a 1-1/2 in. fitting that means at least 1-1/2 in. of compound. The 5/8 in. figure is only the floor for very small fittings. (NEC 501.15(C)(3))
A 75 kVA, three-phase, 480 V to 208Y/120 V transformer is protected on the primary side only. What is the largest standard primary breaker permitted by Table 450.3(B) and its notes?
- 90 A
- 100 A
- 110 A
- 125 A
Answer: 125 A
Why: Primary current is 75,000 ÷ (1.732 × 480) = 90.21 A. Primary-only protection for 9 A or more is 125 %: 90.21 × 1.25 = 112.77 A. Table 450.3(B) Note 1 permits the next higher standard size, 125 A. (NEC 450.3(B), Table 450.3(B), 240.6(A))
A 20 A duplex receptacle on a single yoke is installed in a device box and connected to 12 AWG copper conductors. What volume allowance must be added to the box fill for the receptacle?
- 2.25 in.³
- 4.00 in.³
- 4.50 in.³
- 9.00 in.³
Answer: 4.50 in.³
Why: 314.16(B)(4) gives each yoke or strap holding a device a double volume allowance, based on the largest conductor connected to that device. Table 314.16(B) lists 12 AWG at 2.25 in.³, so the receptacle takes 2 × 2.25 = 4.50 in.³. It is per yoke, not per receptacle face. (NEC 314.16(B)(4), Table 314.16(B))
A textile mill has looms that throw off cotton lint and flyings, which collect on ledges and equipment. Under Article 500, how is this area classified?
- Class I, Group D
- Class II, Group G
- Class III
- Class II, Group E
Answer: Class III
Why: Class locations are sorted by what can burn. Class I is gases and vapors, Class II is combustible dust, and Class III is easily ignitible fibers and flyings such as cotton lint. Textile mills and cotton gins are the textbook Class III examples in 500.5(D). Class III has no material groups. (NEC 500.5(D))
A box with internal clamps contains two 12/2 NM cables spliced through for a 20 A circuit and one 14/2 NM cable feeding a 15 A duplex receptacle in the same box. All three cables have bare grounds. What minimum box volume is required?
- 21.50 in.³
- 22.00 in.³
- 23.50 in.³
- 24.00 in.³
Answer: 21.50 in.³
Why: Each conductor counts at its own size: 4 × 2.25 = 9.00 plus 2 × 2.00 = 4.00. Grounds take one allowance at the largest ground (12 AWG, 2.25) and clamps one at the largest conductor (12 AWG, 2.25). The receptacle is connected only to 14 AWG, so it takes 2 × 2.00 = 4.00 (314.16(B)(4)). Total 21.50 in.³. (NEC 314.16(B)(2), 314.16(B)(4), 314.16(B)(5), Table 314.16(B))
A general-purpose branch circuit uses 12 AWG THHN copper with 75 °C terminations. No correction or adjustment applies, and no special exception (such as a motor circuit) is involved. What is the largest overcurrent device permitted?
- 15 A
- 20 A
- 25 A
- 30 A
Answer: 20 A
Why: Table 310.16 lists 12 AWG copper at 25 A (75 °C) and 30 A (90 °C), but 240.4(D) caps the overcurrent protection of 12 AWG copper at 20 A. The small-conductor rule wins unless a specific section such as 240.4(G) permits otherwise. (NEC 240.4(D), Table 310.16)
A 120 V individual branch circuit supplies one piece of fixed equipment that draws 18 A for 8 hours at a time, and no other load. What minimum standard-size overcurrent device does 210.20(A) require?
- 15 A
- 20 A
- 25 A
- 30 A
Answer: 25 A
Why: The equipment runs 3 hours or more, so it is a continuous load. 210.20(A) requires the overcurrent device to be at least the noncontinuous load plus 125 % of the continuous load: 18 A × 1.25 = 22.5 A. The next standard size in 240.6(A) is 25 A, which is permitted because this is an individual branch circuit (210.3). (NEC 210.20(A), 240.6(A), 210.3)
A 20 A multioutlet branch circuit supplies lighting outlets and fastened-in-place equipment. What is the maximum total rating of the fastened-in-place equipment, other than luminaires?
- 7.5 A
- 10 A
- 12 A
- 16 A
Answer: 10 A
Why: 210.23 limits the total rating of utilization equipment fastened in place, other than luminaires, to 50 % of the circuit rating when the circuit also supplies lighting or cord-and-plug equipment. 50 % of 20 A is 10 A. (NEC 210.23)
Under the 2023 NEC standard method, a 2,000 ft² one-family dwelling on a 120/240 V service has 2 small-appliance circuits, 1 laundry circuit, a 12 kW range, a 5 kW dryer, four fastened-in-place appliances totaling 8,100 VA, 10 kW of fixed electric heat, and a 6 kVA air conditioner. What is the calculated load in amperes?
- 128 A
- 130 A
- 136 A
- 145 A
Answer: 145 A
Why: General load: 6,000 + 3,000 + 1,500 = 10,500 VA, reduced by Table 220.45 to 3,000 + (7,500 × 0.35) = 5,625 VA. Add the range at 8,000 VA (Table 220.55, Column C), the dryer at 5,000 VA (220.54), the appliances at 8,100 × 0.75 = 6,075 VA (220.53), and the larger of heat or AC, 10,000 VA (220.51, 220.60). Total 34,700 VA ÷ 240 V = 144.58 A, which rounds to 145 A (220.5(B)). (NEC Table 220.45, 220.51, 220.53, 220.54, Table 220.55, 220.60, 220.5(B)) Edition note: 2023 NEC numbering. In the 2026 NEC, load calculations moved from Article 220 to Article 120. The dwelling demand tiers were Table 220.42 in the 2020 NEC and are Table 220.45 in 2023.
A receptacle reads 120 V on a true-RMS meter. What is the peak voltage of the sine wave?
- 84.9 V
- 169.7 V
- 240 V
- 339.4 V
Answer: 169.7 V
Why: Meters read RMS, the effective value. For a sine wave, peak = RMS × 1.414 (√2). So 120 × 1.414 = 169.7 V. The wave swings from +169.7 V to −169.7 V sixty times a second.
An office building has an emergency system for egress lighting required by the building code. After normal power fails, within what time must the emergency system supply power?
- 10 seconds
- 30 seconds
- 60 seconds
- 90 seconds
Answer: 10 seconds
Why: 700.12 requires emergency lighting and power to be available within the time needed for the application, but no more than 10 seconds. Emergency systems protect life during evacuation, so people cannot be left in the dark for long. Legally required standby gets 60 seconds; optional standby has no time limit. (NEC 700.12)
A resistive water heater element rated 4,500 W at 240 V is connected to a 208 V circuit. If its resistance does not change, about how many watts does it produce?
- 3,380 W
- 3,900 W
- 4,500 W
- 5,192 W
Answer: 3,380 W
Why: The element's resistance is what stays fixed: R = 240² ÷ 4,500 = 12.8 Ω. At 208 V, P = 208² ÷ 12.8 = 43,264 ÷ 12.8 = 3,380 W, about 75 % of nameplate. Power follows the square of voltage, so a 13 % lower voltage costs about 25 % of the heat.
A 22 kW, 240 V, single-phase standby generator is rated at unity power factor. What minimum ampacity must the conductors from its output terminals to the first overcurrent device have?
- 60.9 A
- 91.7 A
- 105.4 A
- 114.6 A
Answer: 105.4 A
Why: Rated current is 22,000 ÷ 240 = 91.67 A. 445.13(A) requires these conductors to be rated at least 115 % of the nameplate current: 91.67 × 1.15 = 105.42 A, about 105.4 A. (NEC 445.13(A))
Five THHN conductors will be installed in a 60 ft run of EMT between two panelboards. What maximum percentage of the EMT's cross-sectional area may the conductors fill?
- 31 %
- 40 %
- 53 %
- 60 %
Answer: 40 %
Why: Chapter 9, Table 1 allows 40 % fill when a raceway holds more than two conductors. 53 % is for one conductor, 31 % for two, and 60 % only for nipples 24 in. or shorter. A 60 ft run is a full raceway, so 40 % applies. (NEC Chapter 9, Table 1)
Resistors of 10 Ω, 20 Ω and 30 Ω are connected in series across 120 V. What is the voltage across the 30 Ω resistor?
- 20 V
- 40 V
- 60 V
- 120 V
Answer: 60 V
Why: In series the resistances add: 10 + 20 + 30 = 60 Ω, and the same current flows through each: 120 ÷ 60 = 2 A. The drop across the 30 Ω resistor is 2 A × 30 Ω = 60 V. The biggest resistor takes the biggest share, and the drops (20 + 40 + 60) add back to 120 V.
In which installation is the next-size-up allowance of 240.4(B) NOT permitted?
- A multioutlet receptacle branch circuit for portable loads
- A feeder with 140 A ampacity protected by a 150 A breaker
- An individual branch circuit to one fixed appliance
- A feeder with 475 A ampacity protected at 500 A
Answer: A multioutlet receptacle branch circuit for portable loads
Why: 240.4(B)(1) excludes branch circuits that supply more than one receptacle for cord-and-plug-connected portable loads. Any plug on that circuit could draw up to the breaker rating, so the breaker must not exceed the conductor ampacity. (NEC 240.4(B)(1))
A loose splice on a branch circuit has 0.05 Ω of resistance and carries 40 A. How much power is turned into heat at the splice?
- 2 W
- 80 W
- 800 W
- 1,600 W
Answer: 80 W
Why: With amps and ohms given, use P = I² × R: 40² × 0.05 = 1,600 × 0.05 = 80 W. That is a small lamp's worth of heat buried in a box. Because heat rises with the square of current, a bad termination that is fine at light load can scorch at heavy load.
A 10 hp, 460 V, three-phase motor has a nameplate full-load current of 13 A and a service factor of 1.15. What is the maximum trip setting for a separate overload device, using the basic rule?
- 16.25 A
- 16.90 A
- 17.50 A
- 18.20 A
Answer: 16.25 A
Why: Overloads are sized from the nameplate current (430.6(A)(2)). With a service factor of 1.15 or more, 430.32(A)(1) allows up to 125 %: 13 × 1.25 = 16.25 A. (NEC 430.6(A)(2), 430.32(A)(1))
The supply frequency to a circuit rises from 50 Hz to 60 Hz. What happens to inductive reactance (XL) and capacitive reactance (XC)?
- XL rises and XC rises
- XL falls and XC rises
- XL falls and XC falls
- XL rises and XC falls
Answer: XL rises and XC falls
Why: XL = 2πfL, so it rises in step with frequency. XC = 1 ÷ (2πfC), so frequency is in the denominator and XC falls as frequency rises. Coils fight fast changes harder; capacitors pass them more easily.
Original practice questions written for Ohmward on the 2023 NEC — not real exam items.