Iowa Journeyman Electrician Practice Test
20 questions in the style of the Iowa journeyman exam (PSI): NEC rules, code navigation and calculations. Pick an answer, check it, and read why — with the section to look up.
The real Iowa exam: 88 questions in 3 h 30 min, open book, 2023 NEC. Full Iowa exam guide →
An exam question asks for the allowable ampacity of a 4 AWG copper THWN conductor in a raceway. Where will you find the answer most directly?
Report a problem with this question
See all 20 questions with answers and explanations
An exam question asks for the allowable ampacity of a 4 AWG copper THWN conductor in a raceway. Where will you find the answer most directly?
- Table 250.66
- Chapter 9, Table 8
- Table 314.16(A)
- Table 310.16
Answer: Table 310.16
Why: Allowable ampacities for insulated conductors in raceway, cable or earth are in Table 310.16, in Article 310, Conductors for General Wiring. Memorize this table's location; it is the most-used table on the exam. (NEC Table 310.16)
On a 480 V, three-phase, four-wire wye system, what voltage should you measure from any phase conductor to the neutral?
- 277 V
- 339 V
- 480 V
- 831 V
Answer: 277 V
Why: In a wye, line voltage = phase voltage × 1.732, so phase voltage = 480 ÷ 1.732 = 277 V. That's why the system is called 480Y/277 V and why 277 V lighting runs phase to neutral.
In a dwelling, which 120 V, 15 A receptacle requires GFCI protection under 210.8(A)?
- A receptacle beside the bed in a bedroom
- A receptacle in an upstairs hallway
- A receptacle in the dining room
- A receptacle in an unfinished basement
Answer: A receptacle in an unfinished basement
Why: Basements are on the 210.8(A) list of dwelling locations where 125 V through 250 V receptacles need GFCI protection. Bedrooms, hallways and dining rooms are not on the list, though they do need AFCI protection under 210.12. (NEC 210.8(A))
Under the 2023 NEC standard method, a 2,000 ft² one-family dwelling on a 120/240 V service has 2 small-appliance circuits, 1 laundry circuit, a 12 kW range, a 5 kW dryer, four fastened-in-place appliances totaling 8,100 VA, 10 kW of fixed electric heat, and a 6 kVA air conditioner. What is the calculated load in amperes?
- 128 A
- 130 A
- 136 A
- 145 A
Answer: 145 A
Why: General load: 6,000 + 3,000 + 1,500 = 10,500 VA, reduced by Table 220.45 to 3,000 + (7,500 × 0.35) = 5,625 VA. Add the range at 8,000 VA (Table 220.55, Column C), the dryer at 5,000 VA (220.54), the appliances at 8,100 × 0.75 = 6,075 VA (220.53), and the larger of heat or AC, 10,000 VA (220.51, 220.60). Total 34,700 VA ÷ 240 V = 144.58 A, which rounds to 145 A (220.5(B)). (NEC Table 220.45, 220.51, 220.53, 220.54, Table 220.55, 220.60, 220.5(B)) Edition note: 2023 NEC numbering. In the 2026 NEC, load calculations moved from Article 220 to Article 120. The dwelling demand tiers were Table 220.42 in the 2020 NEC and are Table 220.45 in 2023.
Type NM cable is run along the side of a floor joist to a metal device box. Under the general rule of 334.30, what are the maximum distances for securing the cable?
- Within 12 in. of the box, then every 4-1/2 ft
- Within 12 in. of the box, then every 6 ft
- Within 18 in. of the box, then every 4-1/2 ft
- Within 3 ft of the box, then every 10 ft
Answer: Within 12 in. of the box, then every 4-1/2 ft
Why: 334.30 requires NM cable to be secured within 12 in. of every box, cabinet or fitting and at intervals not over 4-1/2 ft. The 12 in. rule keeps the cable from pulling out of the clamp; the 4-1/2 ft spacing keeps it tight to the framing. (NEC 334.30)
A 120 V, 2-wire branch circuit of 12 AWG copper runs 100 ft (one way) to a 16 A load. Using VD = 2KIL/CM with K = 12.9 and circular mils from Chapter 9, Table 8, what is the voltage drop?
- 3.16 V
- 3.98 V
- 5.47 V
- 6.32 V
Answer: 6.32 V
Why: 12 AWG is 6,530 cmil. VD = 2 × 12.9 × 16 × 100 ÷ 6,530 = 6.32 V, which is 5.3 % of 120 V, well above the recommended 3 %. The 2 accounts for current flowing out and back. (NEC Chapter 9, Table 8)
An office building has an emergency system for egress lighting required by the building code. After normal power fails, within what time must the emergency system supply power?
- 10 seconds
- 30 seconds
- 60 seconds
- 90 seconds
Answer: 10 seconds
Why: 700.12 requires emergency lighting and power to be available within the time needed for the application, but no more than 10 seconds. Emergency systems protect life during evacuation, so people cannot be left in the dark for long. Legally required standby gets 60 seconds; optional standby has no time limit. (NEC 700.12)
A 25 kVA, single-phase transformer has a 480 V primary and a 240 V secondary. What is its full-load secondary current?
- 52.08 A
- 60.14 A
- 104.17 A
- 180.42 A
Answer: 104.17 A
Why: Single-phase current is VA ÷ volts, with no √3. On the 240 V side: 25,000 ÷ 240 = 104.17 A. The secondary current is twice the primary current because the voltage is half.
Article 100 defines a continuous load as one where the maximum current is expected to continue for how long?
- 30 minutes or more
- 1 hour or more
- 2 hours or more
- 3 hours or more
Answer: 3 hours or more
Why: Article 100 defines a continuous load as a load where the maximum current is expected to continue for 3 hours or more. Store lighting, office lighting and EV charging are typical examples. (NEC Article 100 (Continuous Load))
Along an unbroken living room wall, what is the maximum distance from any point on the floor line to the nearest receptacle outlet?
- 4 ft
- 6 ft
- 10 ft
- 12 ft
Answer: 6 ft
Why: 210.52(A)(1) requires receptacles placed so that no point along the floor line of any wall space is more than 6 ft from a receptacle outlet. That allows receptacles up to 12 ft apart. (NEC 210.52(A)(1))
Five THHN conductors will be installed in a 60 ft run of EMT between two panelboards. What maximum percentage of the EMT's cross-sectional area may the conductors fill?
- 31 %
- 40 %
- 53 %
- 60 %
Answer: 40 %
Why: Chapter 9, Table 1 allows 40 % fill when a raceway holds more than two conductors. 53 % is for one conductor, 31 % for two, and 60 % only for nipples 24 in. or shorter. A 60 ft run is a full raceway, so 40 % applies. (NEC Chapter 9, Table 1)
A 20 A duplex receptacle on a single yoke is installed in a device box and connected to 12 AWG copper conductors. What volume allowance must be added to the box fill for the receptacle?
- 2.25 in.³
- 4.00 in.³
- 4.50 in.³
- 9.00 in.³
Answer: 4.50 in.³
Why: 314.16(B)(4) gives each yoke or strap holding a device a double volume allowance, based on the largest conductor connected to that device. Table 314.16(B) lists 12 AWG at 2.25 in.³, so the receptacle takes 2 × 2.25 = 4.50 in.³. It is per yoke, not per receptacle face. (NEC 314.16(B)(4), Table 314.16(B))
A 250 kcmil THWN-2 copper feeder lands on switchboard lugs that carry no temperature marking. There are three current-carrying conductors at a 30 °C ambient. What ampacity may be used for this conductor?
- 205 A
- 215 A
- 230 A
- 255 A
Answer: 255 A
Why: For conductors larger than 1 AWG (or circuits over 100 A), 110.14(C)(1)(b) lets you use the 75 °C column even without a marking. 250 kcmil copper is 255 A at 75 °C in Table 310.16. The 90 °C value of 290 A is not usable at these terminations. (NEC 110.14(C)(1)(b), Table 310.16)
A 22 kW, 240 V, single-phase standby generator is rated at unity power factor. What minimum ampacity must the conductors from its output terminals to the first overcurrent device have?
- 60.9 A
- 91.7 A
- 105.4 A
- 114.6 A
Answer: 105.4 A
Why: Rated current is 22,000 ÷ 240 = 91.67 A. 445.13(A) requires these conductors to be rated at least 115 % of the nameplate current: 91.67 × 1.15 = 105.42 A, about 105.4 A. (NEC 445.13(A))
A 480Y/277 V panelboard has exposed live parts on one side of the working space and a concrete block wall on the other. What minimum depth of working space does Table 110.26(A)(1) require?
- 3 ft
- 3½ ft
- 4 ft
- 5 ft
Answer: 3½ ft
Why: Enter the table with voltage to ground: 277 V falls in the 151–1000 V row. Concrete, brick and tile walls are considered grounded, so live parts across from a block wall is Condition 2. The minimum depth is 3½ ft (1.0 m). (NEC 110.26(A)(1), Table 110.26(A)(1))
A 75 kVA, three-phase transformer is rated 480 V delta primary, 208Y/120 V secondary. What is its full-load primary current?
- 90.21 A
- 156.25 A
- 208.18 A
- 270.63 A
Answer: 90.21 A
Why: Three-phase current is VA ÷ (1.732 × line volts). On the primary: 75,000 ÷ (1.732 × 480) = 75,000 ÷ 831.36 = 90.21 A.
A 10 hp, 460 V, three-phase induction motor has a nameplate full-load current of 13 A. What minimum ampacity must its branch-circuit conductors have?
- 14.0 A
- 16.1 A
- 16.25 A
- 17.5 A
Answer: 17.5 A
Why: Conductor sizing starts from the table full-load current, not the nameplate (430.6(A)(1)). Table 430.250 gives 14 A for 10 hp at 460 V, and 430.22 requires conductors rated at least 125 % of that: 14 × 1.25 = 17.5 A. (NEC 430.6(A)(1), Table 430.250, 430.22)
You need the requirements for a rooftop solar photovoltaic system (Article 690). Which chapter of the NEC contains it?
- Chapter 5
- Chapter 6
- Chapter 7
- Chapter 8
Answer: Chapter 6
Why: Chapter 6 covers special equipment, including signs, elevators, EV charging, pools (680) and solar PV (690). The first digit of the article number is the chapter: 690 is in Chapter 6. (NEC Article 690, 90.3)
A 15 hp, three-phase induction motor is connected to a 208 V system and is rated 208 V. What minimum ampacity must its branch-circuit conductors have?
- 52.50 A
- 53.13 A
- 57.75 A
- 60.38 A
Answer: 57.75 A
Why: Use the 208 V column of Table 430.250, which lists 46.2 A for 15 hp. Branch-circuit conductors for one motor must be rated at least 125 % of that current (430.22): 46.2 × 1.25 = 57.75 A. (NEC Table 430.250, 430.22)
A 20 A multioutlet branch circuit supplies lighting and receptacles. What is the maximum rating of one cord-and-plug-connected appliance that is not fastened in place?
- 10 A
- 12 A
- 16 A
- 20 A
Answer: 16 A
Why: 210.23 limits a single cord-and-plug-connected item not fastened in place to 80 % of the branch-circuit rating. 80 % of 20 A is 16 A. (NEC 210.23)
Original practice questions written for Ohmward on the 2023 NEC — not real exam items.