Kansas Journeyman Electrician Practice Test

20 questions in the style of the Kansas journeyman exam: NEC rules, code navigation and calculations. Pick an answer, check it, and read why — with the section to look up.

Question 1 of 20Special occupancies & equipment
PUT IT INTO PRACTICE

A single PV string uses modules with a short-circuit current (Isc) of 9.6 A. Using the 125 % method, what is the maximum circuit current for this string? (Round to two decimals.)

Given conditions

One string, no parallel strings

125 % (Isc) method, not a simulation method

Select your answer
Report a problem with this question

Describe the content issue. Do not include private patient or workplace information.

Pick an answer and check it.

See all 20 questions with answers and explanations
  1. A single PV string uses modules with a short-circuit current (Isc) of 9.6 A. Using the 125 % method, what is the maximum circuit current for this string? (Round to two decimals.)

    • 9.60 A
    • 11.04 A
    • 12.00 A
    • 15.00 A

    Answer: 12.00 A

    Why: 690.8(A)(1) sets the maximum current of a PV string at 125 % of the module Isc. The extra 25 % covers sunlight stronger than the standard test condition, such as cold, clear days with reflected light. 9.6 A × 1.25 = 12.00 A. A second 125 % is applied later, when you size conductors and overcurrent devices. (NEC 690.8(A)(1))

  2. You are sizing the branch-circuit short-circuit and ground-fault protective device for a general-purpose three-phase squirrel-cage motor. Which current do you start from?

    • The nameplate full-load current
    • The locked-rotor current on the nameplate
    • The full-load current from Table 430.250
    • The service-factor current on the nameplate

    Answer: The full-load current from Table 430.250

    Why: 430.6(A)(1) sends you to the FLC tables for conductor ampacity, switch ratings and the short-circuit and ground-fault device. Table values are conservative and let the circuit be designed before the exact motor arrives. The nameplate value is used for separate overload protection. (NEC 430.6(A)(1), 430.6(A)(2), Table 430.250)

  3. Under the 2023 NEC standard method, a 2,400 ft² dwelling has the two required small-appliance circuits and one laundry circuit. What is the net general lighting, small-appliance and laundry demand after Table 220.45?

    • 4,095 VA
    • 5,520 VA
    • 6,045 VA
    • 11,700 VA

    Answer: 6,045 VA

    Why: Start with 2,400 × 3 VA = 7,200 VA, then add 1,500 VA for each small-appliance and laundry circuit (220.52): 7,200 + 3,000 + 1,500 = 11,700 VA. Table 220.45 takes the first 3,000 VA at 100 % and the next portion, up to 120,000 VA, at 35 %: 3,000 + (8,700 × 0.35) = 6,045 VA. (NEC 220.41, 220.52(A), 220.52(B), Table 220.45) Edition note: 2023 NEC numbering. In the 2026 NEC, load calculations moved from Article 220 to Article 120. The dwelling demand tiers were Table 220.42 in the 2020 NEC and are Table 220.45 in 2023.

  4. A receptacle reads 120 V on a true-RMS meter. What is the peak voltage of the sine wave?

    • 84.9 V
    • 169.7 V
    • 240 V
    • 339.4 V

    Answer: 169.7 V

    Why: Meters read RMS, the effective value. For a sine wave, peak = RMS × 1.414 (√2). So 120 × 1.414 = 169.7 V. The wave swings from +169.7 V to −169.7 V sixty times a second.

  5. A 30 hp, 460 V, three-phase motor has a nameplate full-load current of 38 A. What minimum ampere rating must its disconnecting means have?

    • 34.8 A
    • 40.0 A
    • 43.7 A
    • 46.0 A

    Answer: 46.0 A

    Why: 430.110(A) requires the disconnect to be rated at least 115 % of the motor's full-load current, and 430.6(A)(1) says switch ratings come from the table. Table 430.250 gives 40 A: 40 × 1.15 = 46 A. (NEC 430.110(A), 430.6(A)(1), Table 430.250)

  6. A 25 kVA, single-phase transformer has a 480 V primary and a 240 V secondary. What is its full-load secondary current?

    • 52.08 A
    • 60.14 A
    • 104.17 A
    • 180.42 A

    Answer: 104.17 A

    Why: Single-phase current is VA ÷ volts, with no √3. On the 240 V side: 25,000 ÷ 240 = 104.17 A. The secondary current is twice the primary current because the voltage is half.

  7. A section says a wiring method 'shall be permitted' in a certain location. Under 90.5, what does that language mean?

    • The method is allowed but not required
    • The method is required in that location
    • The method needs special permission first
    • The text is explanatory and not enforceable

    Answer: The method is allowed but not required

    Why: Section 90.5 sorts code text into mandatory rules ('shall', 'shall not'), permissive rules ('shall be permitted', 'shall not be required') and explanatory material. A permissive rule allows an action without demanding it, so you may use the method but are not forced to. (NEC 90.5(A), 90.5(B))

  8. Three 6 AWG THHN copper current-carrying conductors run through a boiler room with a 45 °C ambient. Using Table 310.15(B)(1)(1), what is the conductor's ampacity after ambient correction, before the termination check?

    • 53.30 A
    • 60.00 A
    • 61.50 A
    • 65.25 A

    Answer: 65.25 A

    Why: THHN is 90 °C, so start at 75 A (6 AWG copper, 90 °C column). The 41–45 °C row gives 0.87 in the 90 °C column: 75 × 0.87 = 65.25 A. The 110.14(C) termination check comes afterwards. (NEC Table 310.15(B)(1)(1), Table 310.16) Edition note: The 2023 NEC numbers the 30 °C-based correction table as Table 310.15(B)(1)(1); the 2020 edition called it Table 310.15(B)(1).

  9. The general lighting in a retail store runs at full load from 8 a.m. to 10 p.m. every day. Under Article 100, how is this load classified?

    • Noncontinuous load
    • Intermittent duty
    • Periodic duty
    • Continuous load

    Answer: Continuous load

    Why: Article 100 defines a continuous load as one where maximum current is expected to continue for 3 hours or more. Store lighting that runs all day easily qualifies, so it gets the 125 % sizing rules for conductors and overcurrent devices. (NEC Article 100, Continuous Load)

  10. A general-purpose branch circuit uses 12 AWG THHN copper with 75 °C terminations. No correction or adjustment applies, and no special exception (such as a motor circuit) is involved. What is the largest overcurrent device permitted?

    • 15 A
    • 20 A
    • 25 A
    • 30 A

    Answer: 20 A

    Why: Table 310.16 lists 12 AWG copper at 25 A (75 °C) and 30 A (90 °C), but 240.4(D) caps the overcurrent protection of 12 AWG copper at 20 A. The small-conductor rule wins unless a specific section such as 240.4(G) permits otherwise. (NEC 240.4(D), Table 310.16)

  11. A loose splice on a branch circuit has 0.05 Ω of resistance and carries 40 A. How much power is turned into heat at the splice?

    • 2 W
    • 80 W
    • 800 W
    • 1,600 W

    Answer: 80 W

    Why: With amps and ohms given, use P = I² × R: 40² × 0.05 = 1,600 × 0.05 = 80 W. That is a small lamp's worth of heat buried in a box. Because heat rises with the square of current, a bad termination that is fine at light load can scorch at heavy load.

  12. A 120 V ungrounded conductor faults to a metal sign whose only connection to anything is a ground rod. The total path through the earth back to the utility's grounded conductor measures 25 Ω, and the circuit breaker is rated 20 A. Ignoring wire resistance, about how much fault current flows?

    • 0.21 A
    • 4.8 A
    • 20 A
    • 3,000 A

    Answer: 4.8 A

    Why: Ohm's law: I = E ÷ R = 120 V ÷ 25 Ω = 4.8 A. That's far below the breaker's 20 A rating, so the breaker never trips and the sign stays energized. This is exactly why 250.4(A)(5) says the earth can't be the effective ground-fault current path. (NEC 250.4(A)(5))

  13. A textile mill has looms that throw off cotton lint and flyings, which collect on ledges and equipment. Under Article 500, how is this area classified?

    • Class I, Group D
    • Class II, Group G
    • Class III
    • Class II, Group E

    Answer: Class III

    Why: Class locations are sorted by what can burn. Class I is gases and vapors, Class II is combustible dust, and Class III is easily ignitible fibers and flyings such as cotton lint. Textile mills and cotton gins are the textbook Class III examples in 500.5(D). Class III has no material groups. (NEC 500.5(D))

  14. You're setting a feeder-supplied panelboard in the same building as the service. The feeder has two ungrounded conductors, a neutral, and an EGC. The panel ships with a green bonding screw for the neutral bar. What do you do with the screw?

    • Install it so the neutral bar is bonded to the can
    • Install it, but only if a ground rod is added here
    • Install it, but only if the feeder lacks an EGC
    • Leave it out and keep the neutral bar isolated

    Answer: Leave it out and keep the neutral bar isolated

    Why: Past the service disconnect, the grounded conductor may not be connected to equipment grounding (250.24(A)(5), 250.142(B)). The neutral bar stays isolated, and the EGCs land on a separate equipment grounding bar bonded to the enclosure (408.40). The only neutral-to-ground bond is the main bonding jumper at the service. (NEC 250.24(A)(5), 250.142(B), 408.40)

  15. A branch circuit supplies 36 A of continuous load and 8 A of noncontinuous load. The breaker is not listed for 100 % operation. What is the minimum standard breaker rating?

    • 40 A
    • 45 A
    • 50 A
    • 60 A

    Answer: 60 A

    Why: 210.20(A): at least 125 % of the continuous load plus 100 % of the noncontinuous load. 36 × 1.25 = 45 A, plus 8 A = 53 A. The next standard rating at or above 53 A is 60 A. (NEC 210.20(A), 240.6(A))

  16. An office building has an emergency system for egress lighting required by the building code. After normal power fails, within what time must the emergency system supply power?

    • 10 seconds
    • 30 seconds
    • 60 seconds
    • 90 seconds

    Answer: 10 seconds

    Why: 700.12 requires emergency lighting and power to be available within the time needed for the application, but no more than 10 seconds. Emergency systems protect life during evacuation, so people cannot be left in the dark for long. Legally required standby gets 60 seconds; optional standby has no time limit. (NEC 700.12)

  17. You are pouring a 1-1/2 in. trade size sealing fitting in a Class I, Division 1 location. The fitting has no marking that calls for a different depth. What is the minimum thickness of sealing compound?

    • 5/8 in.
    • 3/4 in.
    • 1-1/2 in.
    • 2 in.

    Answer: 1-1/2 in.

    Why: The compound must be at least as thick as the trade size of the sealing fitting, and never less than 5/8 in. (501.15(C)(3)). For a 1-1/2 in. fitting that means at least 1-1/2 in. of compound. The 5/8 in. figure is only the floor for very small fittings. (NEC 501.15(C)(3))

  18. A 22 kW, 240 V, single-phase standby generator is rated at unity power factor. What minimum ampacity must the conductors from its output terminals to the first overcurrent device have?

    • 60.9 A
    • 91.7 A
    • 105.4 A
    • 114.6 A

    Answer: 105.4 A

    Why: Rated current is 22,000 ÷ 240 = 91.67 A. 445.13(A) requires these conductors to be rated at least 115 % of the nameplate current: 91.67 × 1.15 = 105.42 A, about 105.4 A. (NEC 445.13(A))

  19. In a dwelling, which 120 V, 15 A receptacle requires GFCI protection under 210.8(A)?

    • A receptacle beside the bed in a bedroom
    • A receptacle in an upstairs hallway
    • A receptacle in the dining room
    • A receptacle in an unfinished basement

    Answer: A receptacle in an unfinished basement

    Why: Basements are on the 210.8(A) list of dwelling locations where 125 V through 250 V receptacles need GFCI protection. Bedrooms, hallways and dining rooms are not on the list, though they do need AFCI protection under 210.12. (NEC 210.8(A))

  20. A 120 V individual branch circuit supplies one piece of fixed equipment that draws 18 A for 8 hours at a time, and no other load. What minimum standard-size overcurrent device does 210.20(A) require?

    • 15 A
    • 20 A
    • 25 A
    • 30 A

    Answer: 25 A

    Why: The equipment runs 3 hours or more, so it is a continuous load. 210.20(A) requires the overcurrent device to be at least the noncontinuous load plus 125 % of the continuous load: 18 A × 1.25 = 22.5 A. The next standard size in 240.6(A) is 25 A, which is permitted because this is an individual branch circuit (210.3). (NEC 210.20(A), 240.6(A), 210.3)

Original practice questions written for Ohmward on the 2023 NEC — not real exam items.