Kentucky Journeyman Electrician Practice Test

20 questions in the style of the Kentucky journeyman exam (ICC (delivered by Pearson VUE)): NEC rules, code navigation and calculations. Pick an answer, check it, and read why — with the section to look up.

The real Kentucky exam: 80 questions in 4 h, open book, 2023 NEC. Full Kentucky exam guide →

Question 1 of 20Branch circuits & receptacles
PUT IT INTO PRACTICE

A 120 V individual branch circuit supplies one piece of fixed equipment that draws 18 A for 8 hours at a time, and no other load. What minimum standard-size overcurrent device does 210.20(A) require?

Given conditions

Overcurrent device not listed for 100 % operation

Select your answer
Report a problem with this question

Describe the content issue. Do not include private patient or workplace information.

Pick an answer and check it.

See all 20 questions with answers and explanations
  1. A 120 V individual branch circuit supplies one piece of fixed equipment that draws 18 A for 8 hours at a time, and no other load. What minimum standard-size overcurrent device does 210.20(A) require?

    • 15 A
    • 20 A
    • 25 A
    • 30 A

    Answer: 25 A

    Why: The equipment runs 3 hours or more, so it is a continuous load. 210.20(A) requires the overcurrent device to be at least the noncontinuous load plus 125 % of the continuous load: 18 A × 1.25 = 22.5 A. The next standard size in 240.6(A) is 25 A, which is permitted because this is an individual branch circuit (210.3). (NEC 210.20(A), 240.6(A), 210.3)

  2. A receptacle reads 120 V on a true-RMS meter. What is the peak voltage of the sine wave?

    • 84.9 V
    • 169.7 V
    • 240 V
    • 339.4 V

    Answer: 169.7 V

    Why: Meters read RMS, the effective value. For a sine wave, peak = RMS × 1.414 (√2). So 120 × 1.414 = 169.7 V. The wave swings from +169.7 V to −169.7 V sixty times a second.

  3. A 20 A duplex receptacle on a single yoke is installed in a device box and connected to 12 AWG copper conductors. What volume allowance must be added to the box fill for the receptacle?

    • 2.25 in.³
    • 4.00 in.³
    • 4.50 in.³
    • 9.00 in.³

    Answer: 4.50 in.³

    Why: 314.16(B)(4) gives each yoke or strap holding a device a double volume allowance, based on the largest conductor connected to that device. Table 314.16(B) lists 12 AWG at 2.25 in.³, so the receptacle takes 2 × 2.25 = 4.50 in.³. It is per yoke, not per receptacle face. (NEC 314.16(B)(4), Table 314.16(B))

  4. A one-family dwelling has a 125 A, 120/240 V, single-phase service supplying the entire dwelling load. Using 310.12 with copper THWN-2 conductors, 75 °C terminations, and no adjustment or correction factors, what is the minimum ungrounded service-entrance conductor size?

    • 3 AWG
    • 2 AWG
    • 1 AWG
    • 1/0 AWG

    Answer: 2 AWG

    Why: 310.12 lets the conductors of a 120/240 V single-phase dwelling service be sized at 83 % of the service rating: 125 × 0.83 = 103.75 A. In the 75 °C copper column of Table 310.16, 3 AWG is 100 A (too small) and 2 AWG is 115 A. So 2 AWG copper is the minimum. (NEC 310.12, Table 310.16)

  5. A 30 A branch circuit uses 10 AWG THHN copper. Neither the breaker nor the receptacle terminals carry any temperature marking. Which ampacity column of Table 310.16 limits this conductor?

    • The 60 °C column
    • The 75 °C column
    • The 90 °C column
    • Any column, if the load is noncontinuous

    Answer: The 60 °C column

    Why: For circuits rated 100 A or less, or conductors 14 through 1 AWG, 110.14(C)(1)(a) assumes 60 °C terminations unless the equipment is listed and marked for a higher rating. 10 AWG copper is 30 A in the 60 °C column, which happens to match this 30 A circuit. (NEC 110.14(C)(1)(a), Table 310.16)

  6. The supply frequency to a circuit rises from 50 Hz to 60 Hz. What happens to inductive reactance (XL) and capacitive reactance (XC)?

    • XL rises and XC rises
    • XL falls and XC rises
    • XL falls and XC falls
    • XL rises and XC falls

    Answer: XL rises and XC falls

    Why: XL = 2πfL, so it rises in step with frequency. XC = 1 ÷ (2πfC), so frequency is in the denominator and XC falls as frequency rises. Coils fight fast changes harder; capacitors pass them more easily.

  7. In which installation is the next-size-up allowance of 240.4(B) NOT permitted?

    • A multioutlet receptacle branch circuit for portable loads
    • A feeder with 140 A ampacity protected by a 150 A breaker
    • An individual branch circuit to one fixed appliance
    • A feeder with 475 A ampacity protected at 500 A

    Answer: A multioutlet receptacle branch circuit for portable loads

    Why: 240.4(B)(1) excludes branch circuits that supply more than one receptacle for cord-and-plug-connected portable loads. Any plug on that circuit could draw up to the breaker rating, so the breaker must not exceed the conductor ampacity. (NEC 240.4(B)(1))

  8. A balanced three-phase, 208 V load draws 150 A on each line. How many kVA does it draw?

    • 18.0 kVA
    • 31.2 kVA
    • 54.0 kVA
    • 93.6 kVA

    Answer: 54.0 kVA

    Why: Three-phase kVA = 1.732 × line volts × line amps ÷ 1,000 = 1.732 × 208 × 150 ÷ 1,000 = 54.04 kVA, which rounds to 54.0 kVA. The same answer comes from 3 × 120 V × 150 A per phase.

  9. A 480Y/277 V panelboard has exposed live parts on one side of the working space and a concrete block wall on the other. What minimum depth of working space does Table 110.26(A)(1) require?

    • 3 ft
    • 3½ ft
    • 4 ft
    • 5 ft

    Answer: 3½ ft

    Why: Enter the table with voltage to ground: 277 V falls in the 151–1000 V row. Concrete, brick and tile walls are considered grounded, so live parts across from a block wall is Condition 2. The minimum depth is 3½ ft (1.0 m). (NEC 110.26(A)(1), Table 110.26(A)(1))

  10. A 20 A multioutlet branch circuit supplies lighting outlets and fastened-in-place equipment. What is the maximum total rating of the fastened-in-place equipment, other than luminaires?

    • 7.5 A
    • 10 A
    • 12 A
    • 16 A

    Answer: 10 A

    Why: 210.23 limits the total rating of utilization equipment fastened in place, other than luminaires, to 50 % of the circuit rating when the circuit also supplies lighting or cord-and-plug equipment. 50 % of 20 A is 10 A. (NEC 210.23)

  11. A resistive water heater element rated 4,500 W at 240 V is connected to a 208 V circuit. If its resistance does not change, about how many watts does it produce?

    • 3,380 W
    • 3,900 W
    • 4,500 W
    • 5,192 W

    Answer: 3,380 W

    Why: The element's resistance is what stays fixed: R = 240² ÷ 4,500 = 12.8 Ω. At 208 V, P = 208² ÷ 12.8 = 43,264 ÷ 12.8 = 3,380 W, about 75 % of nameplate. Power follows the square of voltage, so a 13 % lower voltage costs about 25 % of the heat.

  12. In a purely capacitive AC circuit, how does the current relate to the voltage?

    • It lags the voltage by 90°
    • It is in phase with the voltage
    • It lags the voltage by 45°
    • It leads the voltage by 90°

    Answer: It leads the voltage by 90°

    Why: A capacitor's current is greatest when the voltage is changing fastest, a quarter-cycle before the voltage peaks. So current leads voltage by 90°. Memory aid: ELI the ICE man. In C, I comes before E.

  13. A loose splice on a branch circuit has 0.05 Ω of resistance and carries 40 A. How much power is turned into heat at the splice?

    • 2 W
    • 80 W
    • 800 W
    • 1,600 W

    Answer: 80 W

    Why: With amps and ohms given, use P = I² × R: 40² × 0.05 = 1,600 × 0.05 = 80 W. That is a small lamp's worth of heat buried in a box. Because heat rises with the square of current, a bad termination that is fine at light load can scorch at heavy load.

  14. You are pouring a 1-1/2 in. trade size sealing fitting in a Class I, Division 1 location. The fitting has no marking that calls for a different depth. What is the minimum thickness of sealing compound?

    • 5/8 in.
    • 3/4 in.
    • 1-1/2 in.
    • 2 in.

    Answer: 1-1/2 in.

    Why: The compound must be at least as thick as the trade size of the sealing fitting, and never less than 5/8 in. (501.15(C)(3)). For a 1-1/2 in. fitting that means at least 1-1/2 in. of compound. The 5/8 in. figure is only the floor for very small fittings. (NEC 501.15(C)(3))

  15. Under the 2023 NEC, a one-family dwelling has 1,800 ft² of living space (outside dimensions), a 400 ft² attached garage, and a 200 ft² open front porch. Using the standard method, what is the general lighting load before any demand factor?

    • 5,400 VA
    • 6,000 VA
    • 6,600 VA
    • 7,200 VA

    Answer: 5,400 VA

    Why: 220.41 assigns 3 VA per square foot to dwelling units, but 220.5(C) counts only floor area that is, or can become, living space, measured from outside dimensions. Garages, open porches, and unfinished space not adaptable for future use are left out. 1,800 ft² × 3 VA = 5,400 VA. (NEC 220.5(C), 220.41) Edition note: 2023 NEC numbering. In the 2026 NEC, load calculations moved from Article 220 to Article 120. In the 2020 NEC the 3 VA/ft² dwelling load was in 220.14(J) and floor area in 220.11.

  16. A resistive water heater element has a resistance of 16 Ω and is connected to 240 V. How much current does it draw?

    • 0.067 A
    • 7.5 A
    • 15 A
    • 3,840 A

    Answer: 15 A

    Why: Ohm's law: current equals voltage divided by resistance, I = E ÷ R. Here 240 V ÷ 16 Ω = 15 A. Think of it as push divided by opposition: more volts push more amps, more ohms hold them back.

  17. An office building has an emergency system for egress lighting required by the building code. After normal power fails, within what time must the emergency system supply power?

    • 10 seconds
    • 30 seconds
    • 60 seconds
    • 90 seconds

    Answer: 10 seconds

    Why: 700.12 requires emergency lighting and power to be available within the time needed for the application, but no more than 10 seconds. Emergency systems protect life during evacuation, so people cannot be left in the dark for long. Legally required standby gets 60 seconds; optional standby has no time limit. (NEC 700.12)

  18. A load draws 100 kVA at a power factor of 0.8. How much real power does it use?

    • 60 kW
    • 80 kW
    • 100 kW
    • 125 kW

    Answer: 80 kW

    Why: Power factor is the share of apparent power that does real work: kW = kVA × PF = 100 × 0.8 = 80 kW. The remaining side of the triangle is √(100² − 80²) = 60 kVAR of reactive power.

  19. A ceiling box with internal clamps and a luminaire stud has two 14/2 NM cables with ground entering it. The luminaire's two 18 AWG fixture wires and its grounding conductor come in from a domed canopy. What minimum box volume is required?

    • 12.00 in.³
    • 14.00 in.³
    • 16.00 in.³
    • 17.00 in.³

    Answer: 14.00 in.³

    Why: Four 14 AWG conductors take 8.00 in.³. Grounds, clamps and the stud each take one 2.00 in.³ allowance, adding 6.00. The fixture wires and the luminaire ground from a domed canopy may be left out (exception to 314.16(B)(1)). Total 14.00 in.³. (NEC 314.16(B)(1) Exception, 314.16(B)(3), Table 314.16(B))

  20. You are sizing the branch-circuit short-circuit and ground-fault protective device for a general-purpose three-phase squirrel-cage motor. Which current do you start from?

    • The nameplate full-load current
    • The locked-rotor current on the nameplate
    • The full-load current from Table 430.250
    • The service-factor current on the nameplate

    Answer: The full-load current from Table 430.250

    Why: 430.6(A)(1) sends you to the FLC tables for conductor ampacity, switch ratings and the short-circuit and ground-fault device. Table values are conservative and let the circuit be designed before the exact motor arrives. The nameplate value is used for separate overload protection. (NEC 430.6(A)(1), 430.6(A)(2), Table 430.250)

Original practice questions written for Ohmward on the 2023 NEC — not real exam items.