COURSE LESSON · 12 MIN · CONDUCTORS & AMPACITY

Ambient correction and bundling adjustment

Correct Table 310.16 ampacity for hot locations and adjust for more than three current-carrying conductors, starting from the 90 °C column.

STEP 1 · THE TABLE ASSUMES COOL AND ROOMY

Table 310.16 values assume a 30 °C ambient and no more than three current-carrying conductors. Change either and the conductor sheds heat less well, so its ampacity drops. Two multipliers fix it: ambient correction from Table 310.15(B)(1)(1) and adjustment from Table 310.15(C)(1).