GUIDED LESSON · 12 MIN

Reading Table 310.16 and termination limits

Step 1 of 17
Restoring your place…
THE IDEA

The 90 °C trap

You pull 8 AWG THHN for a 55 A load because the 90 °C column says 55 A. The inspector writes it up. The wire was fine; the breaker lug is rated 75 °C, and the lug sets the limit.

Sources and content review

Original instructional material written in our own words and checked against the sources above by two separate reviewers. NEC references are to NFPA 70-2023 unless stated. See our editorial policy.