GUIDED LESSON · 12 MIN
Step 1 of 17Reading Table 310.16 and termination limits
Restoring your place…
The 90 °C trap
You pull 8 AWG THHN for a 55 A load because the 90 °C column says 55 A. The inspector writes it up. The wire was fine; the breaker lug is rated 75 °C, and the lug sets the limit.
Sources and content review
- NFPA 70, National Electrical Code (2023 edition) · Table 310.16; 110.14(C); 240.4(D) · checked 2026-11-27
Original instructional material written in our own words and checked against the sources above by two separate reviewers. NEC references are to NFPA 70-2023 unless stated. See our editorial policy.