COURSE LESSON · 12 MIN · WIRING METHODS, BOXES & RACEWAYS

Conduit fill with Chapter 9 tables

Size conduit like the exam expects: Chapter 9 Table 1 fill limits, Table 4 and Table 5 areas, the Annex C shortcut, and the 60 % nipple rule.

STEP 1 · FILL IS A SHARE OF THE AREA

Chapter 9, Table 1 caps how much of a raceway's inside area the wires may take: one conductor 53 %, two conductors 31 %, three or more 40 %. Two wires get the lowest number because two round wires side by side can span the raceway and wedge during a pull.