Required dwelling receptacle outlets and circuits

Dwelling receptacle layout per NEC 210.52: the 6-ft and 24-in. rules, required 20 A circuits in 210.11(C), service receptacles and lighting outlets.

STEP 1 · THE 6-FT RULE (SO 12 FT APART)

In kitchens, family rooms, dining and living rooms, bedrooms, dens and similar rooms, 210.52(A) requires that no point along the floor line of any wall space be more than 6 ft from a receptacle outlet. That puts receptacles at most 12 ft apart, and the first one within 6 ft of each doorway.