COURSE LESSON · 12 MIN · MOTORS & AIR CONDITIONING

Motor full-load current: tables, not nameplates

Size motor conductors from Table 430.248 and 430.250 full-load current, at 125 % for one motor and with the 430.24 rule for several.

STEP 1 · TWO CURRENTS, TWO JOBS

Every motor has two currents that matter. The table full-load current (Tables 430.248 and 430.250) sizes conductors, switches and the short-circuit and ground-fault device. The nameplate current sizes the overload. 430.6(A)(1) sets this split, and most motor questions test whether you picked the right one.