COURSE LESSON · 12 MIN · WIRING METHODS, BOXES & RACEWAYS

Protect, bury and support wiring methods

NEC rules journeymen get tested on: nail plates (300.4), burial cover (300.5), NM and EMT support, 360° bend limit, free conductor length and pull boxes.

STEP 1 · KEEP CABLE AWAY FROM NAILS

300.4(A): a bored hole in a wood stud or joist must have its edge at least 1-1/4 in. from the nearest edge of the wood. Closer than that, or in a notch, cover it with a steel plate at least 1/16 in. thick. Under metal-corrugated roof decking, stay at least 1-1/2 in. below the deck (300.4(E)).