COURSE LESSON · 12 MIN · LOAD CALCULATIONS & SERVICES

Services: conductors, clearances, disconnects

Size dwelling service conductors with the 310.12 83 % rule, set overhead clearances (230.9, 230.24, 230.26), and place and rate the service disconnect.

STEP 1 · 83 % FOR THE WHOLE HOUSE

310.12 lets you size the conductors of a 120/240 V single-phase dwelling service, or a feeder carrying the entire dwelling load, at 83 % of the service rating when rated 100 A through 400 A. Multiply the rating by 0.83, then pick the smallest conductor in the 75 °C column of Table 310.16 that meets it.

In this lesson

  • ⚡ Size the service conductors
  • ⚡ Raise the drop over the driveway
  • ⚡ Clear the street
  • ⚡ Where can the disconnect go?
  • ⚡ True or false: the 83 % rule
  • 🔒 Worked: 200 A service
  • 🔒 Overhead clearances from grade
  • 🔒 Roofs, windows, attachment
  • 🔒 Where the disconnect goes
  • 🔒 Find it fast in the code book
  • 🔒 83 % has limits
  • 🔒 5 practice questions with hints and NEC references