In which installation is the next-size-up allowance of 240.4(B) NOT permitted?
Report a problem with this question
See all 20 questions with answers and explanations
In which installation is the next-size-up allowance of 240.4(B) NOT permitted?
- A multioutlet receptacle branch circuit for portable loads
- A feeder with 140 A ampacity protected by a 150 A breaker
- An individual branch circuit to one fixed appliance
- A feeder with 475 A ampacity protected at 500 A
Answer: A multioutlet receptacle branch circuit for portable loads
Why: 240.4(B)(1) excludes branch circuits that supply more than one receptacle for cord-and-plug-connected portable loads. Any plug on that circuit could draw up to the breaker rating, so the breaker must not exceed the conductor ampacity. (NEC 240.4(B)(1))
A receptacle reads 120 V on a true-RMS meter. What is the peak voltage of the sine wave?
- 84.9 V
- 169.7 V
- 240 V
- 339.4 V
Answer: 169.7 V
Why: Meters read RMS, the effective value. For a sine wave, peak = RMS × 1.414 (√2). So 120 × 1.414 = 169.7 V. The wave swings from +169.7 V to −169.7 V sixty times a second.
A 200 A service is supplied by 3/0 AWG copper service-entrance conductors. What minimum size copper grounding electrode conductor is required to the metal underground water pipe electrode?
- 8 AWG
- 6 AWG
- 4 AWG
- 2 AWG
Answer: 4 AWG
Why: Table 250.66 sizes the GEC from the largest ungrounded service-entrance conductor. 3/0 copper falls in the "2/0 or 3/0" row, which calls for 4 AWG copper. The water pipe isn't a rod, plate, concrete-encased electrode, or ground ring, so none of the 250.66(A)–(C) limits apply. (NEC 250.66, Table 250.66)
A 10 hp, 460 V, three-phase motor has a nameplate full-load current of 13 A and a service factor of 1.15. What is the maximum trip setting for a separate overload device, using the basic rule?
- 16.25 A
- 16.90 A
- 17.50 A
- 18.20 A
Answer: 16.25 A
Why: Overloads are sized from the nameplate current (430.6(A)(2)). With a service factor of 1.15 or more, 430.32(A)(1) allows up to 125 %: 13 × 1.25 = 16.25 A. (NEC 430.6(A)(2), 430.32(A)(1))
A feeder supplies 90 A of continuous lighting load and no other load. The breaker is not listed for 100 % operation. What is the minimum standard breaker rating?
- 90 A
- 110 A
- 125 A
- 150 A
Answer: 125 A
Why: 215.3 requires the feeder overcurrent device to be at least 125 % of the continuous load: 90 × 1.25 = 112.5 A. 112.5 A isn't a standard rating, so go up to the next standard size in 240.6(A), 125 A. (NEC 215.3, 240.6(A))
You are pouring a 1-1/2 in. trade size sealing fitting in a Class I, Division 1 location. The fitting has no marking that calls for a different depth. What is the minimum thickness of sealing compound?
- 5/8 in.
- 3/4 in.
- 1-1/2 in.
- 2 in.
Answer: 1-1/2 in.
Why: The compound must be at least as thick as the trade size of the sealing fitting, and never less than 5/8 in. (501.15(C)(3)). For a 1-1/2 in. fitting that means at least 1-1/2 in. of compound. The 5/8 in. figure is only the floor for very small fittings. (NEC 501.15(C)(3))
A 120 V branch circuit supplies a metal pole light in a parking lot. Which of these must not be counted on as the effective ground-fault current path for that circuit?
- The earth, through a ground rod at the pole
- An EMT raceway with listed set-screw fittings
- A copper wire-type equipment grounding conductor
- The metal armor of listed Type AC cable
Answer: The earth, through a ground rod at the pole
Why: 250.4(A)(5) says the earth is not to be considered an effective ground-fault current path. Soil resistance is far too high to let enough current flow to open the breaker. The fault path has to be an intentional, low-impedance metal path back to the source, such as EMT, a wire-type EGC, or AC cable armor, all of which 250.118 permits. (NEC 250.4(A)(5), 250.118)
A 30 A branch circuit uses 10 AWG THHN copper. Neither the breaker nor the receptacle terminals carry any temperature marking. Which ampacity column of Table 310.16 limits this conductor?
- The 60 °C column
- The 75 °C column
- The 90 °C column
- Any column, if the load is noncontinuous
Answer: The 60 °C column
Why: For circuits rated 100 A or less, or conductors 14 through 1 AWG, 110.14(C)(1)(a) assumes 60 °C terminations unless the equipment is listed and marked for a higher rating. 10 AWG copper is 30 A in the 60 °C column, which happens to match this 30 A circuit. (NEC 110.14(C)(1)(a), Table 310.16)
Along an unbroken living room wall, what is the maximum distance from any point on the floor line to the nearest receptacle outlet?
- 4 ft
- 6 ft
- 10 ft
- 12 ft
Answer: 6 ft
Why: 210.52(A)(1) requires receptacles placed so that no point along the floor line of any wall space is more than 6 ft from a receptacle outlet. That allows receptacles up to 12 ft apart. (NEC 210.52(A)(1))
The supply frequency to a circuit rises from 50 Hz to 60 Hz. What happens to inductive reactance (XL) and capacitive reactance (XC)?
- XL rises and XC rises
- XL falls and XC rises
- XL falls and XC falls
- XL rises and XC falls
Answer: XL rises and XC falls
Why: XL = 2πfL, so it rises in step with frequency. XC = 1 ÷ (2πfC), so frequency is in the denominator and XC falls as frequency rises. Coils fight fast changes harder; capacitors pass them more easily.
A 30 hp, 460 V, three-phase motor has a nameplate full-load current of 38 A. What minimum ampere rating must its disconnecting means have?
- 34.8 A
- 40.0 A
- 43.7 A
- 46.0 A
Answer: 46.0 A
Why: 430.110(A) requires the disconnect to be rated at least 115 % of the motor's full-load current, and 430.6(A)(1) says switch ratings come from the table. Table 430.250 gives 40 A: 40 × 1.15 = 46 A. (NEC 430.110(A), 430.6(A)(1), Table 430.250)
A one-family dwelling has a 125 A, 120/240 V, single-phase service supplying the entire dwelling load. Using 310.12 with copper THWN-2 conductors, 75 °C terminations, and no adjustment or correction factors, what is the minimum ungrounded service-entrance conductor size?
- 3 AWG
- 2 AWG
- 1 AWG
- 1/0 AWG
Answer: 2 AWG
Why: 310.12 lets the conductors of a 120/240 V single-phase dwelling service be sized at 83 % of the service rating: 125 × 0.83 = 103.75 A. In the 75 °C copper column of Table 310.16, 3 AWG is 100 A (too small) and 2 AWG is 115 A. So 2 AWG copper is the minimum. (NEC 310.12, Table 310.16)
Under the 2023 NEC standard method, a 2,000 ft² one-family dwelling on a 120/240 V service has 2 small-appliance circuits, 1 laundry circuit, a 12 kW range, a 5 kW dryer, four fastened-in-place appliances totaling 8,100 VA, 10 kW of fixed electric heat, and a 6 kVA air conditioner. What is the calculated load in amperes?
- 128 A
- 130 A
- 136 A
- 145 A
Answer: 145 A
Why: General load: 6,000 + 3,000 + 1,500 = 10,500 VA, reduced by Table 220.45 to 3,000 + (7,500 × 0.35) = 5,625 VA. Add the range at 8,000 VA (Table 220.55, Column C), the dryer at 5,000 VA (220.54), the appliances at 8,100 × 0.75 = 6,075 VA (220.53), and the larger of heat or AC, 10,000 VA (220.51, 220.60). Total 34,700 VA ÷ 240 V = 144.58 A, which rounds to 145 A (220.5(B)). (NEC Table 220.45, 220.51, 220.53, 220.54, Table 220.55, 220.60, 220.5(B)) Edition note: 2023 NEC numbering. In the 2026 NEC, load calculations moved from Article 220 to Article 120. The dwelling demand tiers were Table 220.42 in the 2020 NEC and are Table 220.45 in 2023.
A balanced three-phase, 208 V load draws 150 A on each line. How many kVA does it draw?
- 18.0 kVA
- 31.2 kVA
- 54.0 kVA
- 93.6 kVA
Answer: 54.0 kVA
Why: Three-phase kVA = 1.732 × line volts × line amps ÷ 1,000 = 1.732 × 208 × 150 ÷ 1,000 = 54.04 kVA, which rounds to 54.0 kVA. The same answer comes from 3 × 120 V × 150 A per phase.
A 120 V, 2-wire branch circuit of 12 AWG copper runs 100 ft (one way) to a 16 A load. Using VD = 2KIL/CM with K = 12.9 and circular mils from Chapter 9, Table 8, what is the voltage drop?
- 3.16 V
- 3.98 V
- 5.47 V
- 6.32 V
Answer: 6.32 V
Why: 12 AWG is 6,530 cmil. VD = 2 × 12.9 × 16 × 100 ÷ 6,530 = 6.32 V, which is 5.3 % of 120 V, well above the recommended 3 %. The 2 accounts for current flowing out and back. (NEC Chapter 9, Table 8)
In a purely capacitive AC circuit, how does the current relate to the voltage?
- It lags the voltage by 90°
- It is in phase with the voltage
- It lags the voltage by 45°
- It leads the voltage by 90°
Answer: It leads the voltage by 90°
Why: A capacitor's current is greatest when the voltage is changing fastest, a quarter-cycle before the voltage peaks. So current leads voltage by 90°. Memory aid: ELI the ICE man. In C, I comes before E.
A 72 A noncontinuous load is supplied by three THHN copper conductors in EMT at a 30 °C ambient. The breaker and the load terminals are listed and marked for 75 °C. What is the minimum conductor size?
- 6 AWG
- 4 AWG
- 3 AWG
- 2 AWG
Answer: 4 AWG
Why: THHN is a 90 °C conductor, but the 75 °C terminals limit the ampacity you may use (110.14(C)(1)(a)). In the 75 °C copper column of Table 310.16, 6 AWG is 65 A (too small) and 4 AWG is 85 A, so 4 AWG is the smallest that carries 72 A. (NEC 110.14(C)(1)(a), Table 310.16)
A 25 kVA, single-phase transformer has a 480 V primary and a 240 V secondary. What is its full-load secondary current?
- 52.08 A
- 60.14 A
- 104.17 A
- 180.42 A
Answer: 104.17 A
Why: Single-phase current is VA ÷ volts, with no √3. On the 240 V side: 25,000 ÷ 240 = 104.17 A. The secondary current is twice the primary current because the voltage is half.
Under the 2023 NEC, a one-family dwelling has 1,800 ft² of living space (outside dimensions), a 400 ft² attached garage, and a 200 ft² open front porch. Using the standard method, what is the general lighting load before any demand factor?
- 5,400 VA
- 6,000 VA
- 6,600 VA
- 7,200 VA
Answer: 5,400 VA
Why: 220.41 assigns 3 VA per square foot to dwelling units, but 220.5(C) counts only floor area that is, or can become, living space, measured from outside dimensions. Garages, open porches, and unfinished space not adaptable for future use are left out. 1,800 ft² × 3 VA = 5,400 VA. (NEC 220.5(C), 220.41) Edition note: 2023 NEC numbering. In the 2026 NEC, load calculations moved from Article 220 to Article 120. In the 2020 NEC the 3 VA/ft² dwelling load was in 220.14(J) and floor area in 220.11.
A resistive heater is moved from a 120 V circuit to a 240 V circuit. If its resistance stays the same, how does its power compare with before?
- One-quarter as much
- One-half as much
- Twice as much
- Four times as much
Answer: Four times as much
Why: With resistance fixed, P = E² ÷ R. Doubling E makes E² four times larger, so the heater makes four times the watts. Current doubles too (I = E ÷ R), and twice the volts times twice the amps is four times the power. That is why a 120 V heater on 240 V fails fast.