Massachusetts Journeyman Electrician Practice Test
20 questions in the style of the Massachusetts journeyman exam (PSI): NEC rules, code navigation and calculations. Pick an answer, check it, and read why — with the section to look up.
The real Massachusetts exam: 110 questions in 4 h, open book, 2026 NEC. Full Massachusetts exam guide →
Under the 2023 NEC standard method, a 2,400 ft² dwelling has the two required small-appliance circuits and one laundry circuit. What is the net general lighting, small-appliance and laundry demand after Table 220.45?
Report a problem with this question
See all 20 questions with answers and explanations
Under the 2023 NEC standard method, a 2,400 ft² dwelling has the two required small-appliance circuits and one laundry circuit. What is the net general lighting, small-appliance and laundry demand after Table 220.45?
- 4,095 VA
- 5,520 VA
- 6,045 VA
- 11,700 VA
Answer: 6,045 VA
Why: Start with 2,400 × 3 VA = 7,200 VA, then add 1,500 VA for each small-appliance and laundry circuit (220.52): 7,200 + 3,000 + 1,500 = 11,700 VA. Table 220.45 takes the first 3,000 VA at 100 % and the next portion, up to 120,000 VA, at 35 %: 3,000 + (8,700 × 0.35) = 6,045 VA. (NEC 220.41, 220.52(A), 220.52(B), Table 220.45) Edition note: 2023 NEC numbering. In the 2026 NEC, load calculations moved from Article 220 to Article 120. The dwelling demand tiers were Table 220.42 in the 2020 NEC and are Table 220.45 in 2023.
A 75 kVA, three-phase, 480 V to 208Y/120 V transformer is protected on the primary side only. What is the largest standard primary breaker permitted by Table 450.3(B) and its notes?
- 90 A
- 100 A
- 110 A
- 125 A
Answer: 125 A
Why: Primary current is 75,000 ÷ (1.732 × 480) = 90.21 A. Primary-only protection for 9 A or more is 125 %: 90.21 × 1.25 = 112.77 A. Table 450.3(B) Note 1 permits the next higher standard size, 125 A. (NEC 450.3(B), Table 450.3(B), 240.6(A))
A general-purpose branch circuit uses 12 AWG THHN copper with 75 °C terminations. No correction or adjustment applies, and no special exception (such as a motor circuit) is involved. What is the largest overcurrent device permitted?
- 15 A
- 20 A
- 25 A
- 30 A
Answer: 20 A
Why: Table 310.16 lists 12 AWG copper at 25 A (75 °C) and 30 A (90 °C), but 240.4(D) caps the overcurrent protection of 12 AWG copper at 20 A. The small-conductor rule wins unless a specific section such as 240.4(G) permits otherwise. (NEC 240.4(D), Table 310.16)
Three 6 AWG THHN copper current-carrying conductors run through a boiler room with a 45 °C ambient. Using Table 310.15(B)(1)(1), what is the conductor's ampacity after ambient correction, before the termination check?
- 53.30 A
- 60.00 A
- 61.50 A
- 65.25 A
Answer: 65.25 A
Why: THHN is 90 °C, so start at 75 A (6 AWG copper, 90 °C column). The 41–45 °C row gives 0.87 in the 90 °C column: 75 × 0.87 = 65.25 A. The 110.14(C) termination check comes afterwards. (NEC Table 310.15(B)(1)(1), Table 310.16) Edition note: The 2023 NEC numbers the 30 °C-based correction table as Table 310.15(B)(1)(1); the 2020 edition called it Table 310.15(B)(1).
A resistive water heater element has a resistance of 16 Ω and is connected to 240 V. How much current does it draw?
- 0.067 A
- 7.5 A
- 15 A
- 3,840 A
Answer: 15 A
Why: Ohm's law: current equals voltage divided by resistance, I = E ÷ R. Here 240 V ÷ 16 Ω = 15 A. Think of it as push divided by opposition: more volts push more amps, more ohms hold them back.
You are sizing the branch-circuit short-circuit and ground-fault protective device for a general-purpose three-phase squirrel-cage motor. Which current do you start from?
- The nameplate full-load current
- The locked-rotor current on the nameplate
- The full-load current from Table 430.250
- The service-factor current on the nameplate
Answer: The full-load current from Table 430.250
Why: 430.6(A)(1) sends you to the FLC tables for conductor ampacity, switch ratings and the short-circuit and ground-fault device. Table values are conservative and let the circuit be designed before the exact motor arrives. The nameplate value is used for separate overload protection. (NEC 430.6(A)(1), 430.6(A)(2), Table 430.250)
A receptacle reads 120 V on a true-RMS meter. What is the peak voltage of the sine wave?
- 84.9 V
- 169.7 V
- 240 V
- 339.4 V
Answer: 169.7 V
Why: Meters read RMS, the effective value. For a sine wave, peak = RMS × 1.414 (√2). So 120 × 1.414 = 169.7 V. The wave swings from +169.7 V to −169.7 V sixty times a second.
A 25 kVA, single-phase transformer has a 480 V primary and a 240 V secondary. What is its full-load secondary current?
- 52.08 A
- 60.14 A
- 104.17 A
- 180.42 A
Answer: 104.17 A
Why: Single-phase current is VA ÷ volts, with no √3. On the 240 V side: 25,000 ÷ 240 = 104.17 A. The secondary current is twice the primary current because the voltage is half.
A load draws 100 kVA at a power factor of 0.8. How much real power does it use?
- 60 kW
- 80 kW
- 100 kW
- 125 kW
Answer: 80 kW
Why: Power factor is the share of apparent power that does real work: kW = kVA × PF = 100 × 0.8 = 80 kW. The remaining side of the triangle is √(100² − 80²) = 60 kVAR of reactive power.
A textile mill has looms that throw off cotton lint and flyings, which collect on ledges and equipment. Under Article 500, how is this area classified?
- Class I, Group D
- Class II, Group G
- Class III
- Class II, Group E
Answer: Class III
Why: Class locations are sorted by what can burn. Class I is gases and vapors, Class II is combustible dust, and Class III is easily ignitible fibers and flyings such as cotton lint. Textile mills and cotton gins are the textbook Class III examples in 500.5(D). Class III has no material groups. (NEC 500.5(D))
A metal device box with internal cable clamps has two 14/2 NM cables with ground entering it. A single-pole switch is installed, and the two bare grounds are spliced with a pigtail to the switch. What minimum box volume is required?
- 14.00 in.³
- 16.00 in.³
- 18.00 in.³
- 20.00 in.³
Answer: 16.00 in.³
Why: Count by 314.16(B) at 2.00 in.³ for 14 AWG: four insulated conductors (8.00), one allowance for all grounds (2.00), one for the clamps (2.00), and two for the switch yoke (4.00). Total 16.00 in.³. The pigtail never leaves the box, so it counts zero. (NEC 314.16(B)(1), 314.16(B)(2), 314.16(B)(4), 314.16(B)(5), Table 314.16(B))
A 250 kcmil THWN-2 copper feeder lands on switchboard lugs that carry no temperature marking. There are three current-carrying conductors at a 30 °C ambient. What ampacity may be used for this conductor?
- 205 A
- 215 A
- 230 A
- 255 A
Answer: 255 A
Why: For conductors larger than 1 AWG (or circuits over 100 A), 110.14(C)(1)(b) lets you use the 75 °C column even without a marking. 250 kcmil copper is 255 A at 75 °C in Table 310.16. The 90 °C value of 290 A is not usable at these terminations. (NEC 110.14(C)(1)(b), Table 310.16)
A 10 hp, 460 V, three-phase motor has a nameplate full-load current of 13 A and a service factor of 1.15. What is the maximum trip setting for a separate overload device, using the basic rule?
- 16.25 A
- 16.90 A
- 17.50 A
- 18.20 A
Answer: 16.25 A
Why: Overloads are sized from the nameplate current (430.6(A)(2)). With a service factor of 1.15 or more, 430.32(A)(1) allows up to 125 %: 13 × 1.25 = 16.25 A. (NEC 430.6(A)(2), 430.32(A)(1))
You are pouring a 1-1/2 in. trade size sealing fitting in a Class I, Division 1 location. The fitting has no marking that calls for a different depth. What is the minimum thickness of sealing compound?
- 5/8 in.
- 3/4 in.
- 1-1/2 in.
- 2 in.
Answer: 1-1/2 in.
Why: The compound must be at least as thick as the trade size of the sealing fitting, and never less than 5/8 in. (501.15(C)(3)). For a 1-1/2 in. fitting that means at least 1-1/2 in. of compound. The 5/8 in. figure is only the floor for very small fittings. (NEC 501.15(C)(3))
A loose splice on a branch circuit has 0.05 Ω of resistance and carries 40 A. How much power is turned into heat at the splice?
- 2 W
- 80 W
- 800 W
- 1,600 W
Answer: 80 W
Why: With amps and ohms given, use P = I² × R: 40² × 0.05 = 1,600 × 0.05 = 80 W. That is a small lamp's worth of heat buried in a box. Because heat rises with the square of current, a bad termination that is fine at light load can scorch at heavy load.
A 120 V ungrounded conductor faults to a metal sign whose only connection to anything is a ground rod. The total path through the earth back to the utility's grounded conductor measures 25 Ω, and the circuit breaker is rated 20 A. Ignoring wire resistance, about how much fault current flows?
- 0.21 A
- 4.8 A
- 20 A
- 3,000 A
Answer: 4.8 A
Why: Ohm's law: I = E ÷ R = 120 V ÷ 25 Ω = 4.8 A. That's far below the breaker's 20 A rating, so the breaker never trips and the sign stays energized. This is exactly why 250.4(A)(5) says the earth can't be the effective ground-fault current path. (NEC 250.4(A)(5))
You're setting a feeder-supplied panelboard in the same building as the service. The feeder has two ungrounded conductors, a neutral, and an EGC. The panel ships with a green bonding screw for the neutral bar. What do you do with the screw?
- Install it so the neutral bar is bonded to the can
- Install it, but only if a ground rod is added here
- Install it, but only if the feeder lacks an EGC
- Leave it out and keep the neutral bar isolated
Answer: Leave it out and keep the neutral bar isolated
Why: Past the service disconnect, the grounded conductor may not be connected to equipment grounding (250.24(A)(5), 250.142(B)). The neutral bar stays isolated, and the EGCs land on a separate equipment grounding bar bonded to the enclosure (408.40). The only neutral-to-ground bond is the main bonding jumper at the service. (NEC 250.24(A)(5), 250.142(B), 408.40)
A branch circuit supplies 36 A of continuous load and 8 A of noncontinuous load. The breaker is not listed for 100 % operation. What is the minimum standard breaker rating?
- 40 A
- 45 A
- 50 A
- 60 A
Answer: 60 A
Why: 210.20(A): at least 125 % of the continuous load plus 100 % of the noncontinuous load. 36 × 1.25 = 45 A, plus 8 A = 53 A. The next standard rating at or above 53 A is 60 A. (NEC 210.20(A), 240.6(A))
Five THHN conductors will be installed in a 60 ft run of EMT between two panelboards. What maximum percentage of the EMT's cross-sectional area may the conductors fill?
- 31 %
- 40 %
- 53 %
- 60 %
Answer: 40 %
Why: Chapter 9, Table 1 allows 40 % fill when a raceway holds more than two conductors. 53 % is for one conductor, 31 % for two, and 60 % only for nipples 24 in. or shorter. A 60 ft run is a full raceway, so 40 % applies. (NEC Chapter 9, Table 1)
Resistors of 10 Ω, 20 Ω and 30 Ω are connected in series across 120 V. What is the voltage across the 30 Ω resistor?
- 20 V
- 40 V
- 60 V
- 120 V
Answer: 60 V
Why: In series the resistances add: 10 + 20 + 30 = 60 Ω, and the same current flows through each: 120 ÷ 60 = 2 A. The drop across the 30 Ω resistor is 2 A × 30 Ω = 60 V. The biggest resistor takes the biggest share, and the drops (20 + 40 + 60) add back to 120 V.
Original practice questions written for Ohmward on the 2023 NEC — not real exam items.