Michigan Journeyman Electrician Practice Test

20 questions in the style of the Michigan journeyman exam (PSI): NEC rules, code navigation and calculations. Pick an answer, check it, and read why — with the section to look up.

The real Michigan exam: 80 questions in 2 h 30 min, open book, 2023 NEC. Full Michigan exam guide →

Question 1 of 20Wiring methods, boxes & raceways
PUT IT INTO PRACTICE

A box with internal clamps contains two 12/2 NM cables spliced through for a 20 A circuit and one 14/2 NM cable feeding a 15 A duplex receptacle in the same box. All three cables have bare grounds. What minimum box volume is required?

Given conditions

Copper conductors

The 12 AWG circuit is spliced in the box and does not connect to the receptacle

Select your answer
Report a problem with this question

Describe the content issue. Do not include private patient or workplace information.

Pick an answer and check it.

See all 20 questions with answers and explanations
  1. A box with internal clamps contains two 12/2 NM cables spliced through for a 20 A circuit and one 14/2 NM cable feeding a 15 A duplex receptacle in the same box. All three cables have bare grounds. What minimum box volume is required?

    • 21.50 in.³
    • 22.00 in.³
    • 23.50 in.³
    • 24.00 in.³

    Answer: 21.50 in.³

    Why: Each conductor counts at its own size: 4 × 2.25 = 9.00 plus 2 × 2.00 = 4.00. Grounds take one allowance at the largest ground (12 AWG, 2.25) and clamps one at the largest conductor (12 AWG, 2.25). The receptacle is connected only to 14 AWG, so it takes 2 × 2.00 = 4.00 (314.16(B)(4)). Total 21.50 in.³. (NEC 314.16(B)(2), 314.16(B)(4), 314.16(B)(5), Table 314.16(B))

  2. You need the requirements for a rooftop solar photovoltaic system (Article 690). Which chapter of the NEC contains it?

    • Chapter 5
    • Chapter 6
    • Chapter 7
    • Chapter 8

    Answer: Chapter 6

    Why: Chapter 6 covers special equipment, including signs, elevators, EV charging, pools (680) and solar PV (690). The first digit of the article number is the chapter: 690 is in Chapter 6. (NEC Article 690, 90.3)

  3. In a purely capacitive AC circuit, how does the current relate to the voltage?

    • It lags the voltage by 90°
    • It is in phase with the voltage
    • It lags the voltage by 45°
    • It leads the voltage by 90°

    Answer: It leads the voltage by 90°

    Why: A capacitor's current is greatest when the voltage is changing fastest, a quarter-cycle before the voltage peaks. So current leads voltage by 90°. Memory aid: ELI the ICE man. In C, I comes before E.

  4. A 30 hp, 460 V, three-phase motor has a nameplate full-load current of 38 A. What minimum ampere rating must its disconnecting means have?

    • 34.8 A
    • 40.0 A
    • 43.7 A
    • 46.0 A

    Answer: 46.0 A

    Why: 430.110(A) requires the disconnect to be rated at least 115 % of the motor's full-load current, and 430.6(A)(1) says switch ratings come from the table. Table 430.250 gives 40 A: 40 × 1.15 = 46 A. (NEC 430.110(A), 430.6(A)(1), Table 430.250)

  5. Under the 2023 NEC, a one-family dwelling has 1,800 ft² of living space (outside dimensions), a 400 ft² attached garage, and a 200 ft² open front porch. Using the standard method, what is the general lighting load before any demand factor?

    • 5,400 VA
    • 6,000 VA
    • 6,600 VA
    • 7,200 VA

    Answer: 5,400 VA

    Why: 220.41 assigns 3 VA per square foot to dwelling units, but 220.5(C) counts only floor area that is, or can become, living space, measured from outside dimensions. Garages, open porches, and unfinished space not adaptable for future use are left out. 1,800 ft² × 3 VA = 5,400 VA. (NEC 220.5(C), 220.41) Edition note: 2023 NEC numbering. In the 2026 NEC, load calculations moved from Article 220 to Article 120. In the 2020 NEC the 3 VA/ft² dwelling load was in 220.14(J) and floor area in 220.11.

  6. A 25 ft feeder tap is taken from a feeder protected by a 300 A breaker. Under 240.21(B)(2), what is the minimum ampacity of the tap conductors?

    • 30 A
    • 100 A
    • 150 A
    • 300 A

    Answer: 100 A

    Why: 240.21(B)(2) requires a 25-ft tap to have an ampacity of at least one-third of the feeder overcurrent device rating: 300 ÷ 3 = 100 A. The tap must also end in a single breaker or set of fuses that limits the load to the tap's ampacity. (NEC 240.21(B)(2))

  7. A resistive heater is moved from a 120 V circuit to a 240 V circuit. If its resistance stays the same, how does its power compare with before?

    • One-quarter as much
    • One-half as much
    • Twice as much
    • Four times as much

    Answer: Four times as much

    Why: With resistance fixed, P = E² ÷ R. Doubling E makes E² four times larger, so the heater makes four times the watts. Current doubles too (I = E ÷ R), and twice the volts times twice the amps is four times the power. That is why a 120 V heater on 240 V fails fast.

  8. Resistors of 10 Ω, 20 Ω and 30 Ω are connected in series across 120 V. What is the voltage across the 30 Ω resistor?

    • 20 V
    • 40 V
    • 60 V
    • 120 V

    Answer: 60 V

    Why: In series the resistances add: 10 + 20 + 30 = 60 Ω, and the same current flows through each: 120 ÷ 60 = 2 A. The drop across the 30 Ω resistor is 2 A × 30 Ω = 60 V. The biggest resistor takes the biggest share, and the drops (20 + 40 + 60) add back to 120 V.

  9. A resistive water heater element has a resistance of 16 Ω and is connected to 240 V. How much current does it draw?

    • 0.067 A
    • 7.5 A
    • 15 A
    • 3,840 A

    Answer: 15 A

    Why: Ohm's law: current equals voltage divided by resistance, I = E ÷ R. Here 240 V ÷ 16 Ω = 15 A. Think of it as push divided by opposition: more volts push more amps, more ohms hold them back.

  10. A 25 kVA, single-phase transformer has a 480 V primary and a 240 V secondary. What is its full-load secondary current?

    • 52.08 A
    • 60.14 A
    • 104.17 A
    • 180.42 A

    Answer: 104.17 A

    Why: Single-phase current is VA ÷ volts, with no √3. On the 240 V side: 25,000 ÷ 240 = 104.17 A. The secondary current is twice the primary current because the voltage is half.

  11. You are pouring a 1-1/2 in. trade size sealing fitting in a Class I, Division 1 location. The fitting has no marking that calls for a different depth. What is the minimum thickness of sealing compound?

    • 5/8 in.
    • 3/4 in.
    • 1-1/2 in.
    • 2 in.

    Answer: 1-1/2 in.

    Why: The compound must be at least as thick as the trade size of the sealing fitting, and never less than 5/8 in. (501.15(C)(3)). For a 1-1/2 in. fitting that means at least 1-1/2 in. of compound. The 5/8 in. figure is only the floor for very small fittings. (NEC 501.15(C)(3))

  12. You are sizing the branch-circuit short-circuit and ground-fault protective device for a general-purpose three-phase squirrel-cage motor. Which current do you start from?

    • The nameplate full-load current
    • The locked-rotor current on the nameplate
    • The full-load current from Table 430.250
    • The service-factor current on the nameplate

    Answer: The full-load current from Table 430.250

    Why: 430.6(A)(1) sends you to the FLC tables for conductor ampacity, switch ratings and the short-circuit and ground-fault device. Table values are conservative and let the circuit be designed before the exact motor arrives. The nameplate value is used for separate overload protection. (NEC 430.6(A)(1), 430.6(A)(2), Table 430.250)

  13. A storage room holds gasoline in closed, sealed drums. Vapors could escape only if a drum ruptured or leaked by accident. No dispensing happens in the room. How is the room classified?

    • Class I, Division 1
    • Class I, Division 2
    • Class II, Division 2
    • Class II, Division 1

    Answer: Class I, Division 2

    Why: Gasoline vapor makes it Class I. The division depends on how often an ignitible mixture is expected. Liquids kept in closed containers that release vapor only through accidental rupture or breakdown fit Division 2 in 500.5(B)(2). Division 1 is for places where the mixture exists in normal operation, such as open dispensing. (NEC 500.5(B)(2))

  14. A 6 AWG THWN copper conductor (75 °C terminations, no correction or adjustment) supplies a single fixed 55 A noncontinuous load on an individual branch circuit. What is the largest breaker that may protect it?

    • 60 A
    • 70 A
    • 75 A
    • 80 A

    Answer: 70 A

    Why: 6 AWG copper at 75 °C is 65 A, which isn't a standard rating. 240.4(B) lets you use the next higher standard rating, 70 A, because the circuit doesn't supply multiple receptacles for portable loads and the rating is under 800 A. (NEC 240.4(B), 240.6(A), Table 310.16)

  15. A 4,500 W water heater element runs 3 hours a day for 30 days. Electricity costs $0.15 per kWh. What is the energy cost for the month?

    • $2.03
    • $20.25
    • $60.75
    • $60,750

    Answer: $60.75

    Why: Energy is power × time, billed in kilowatt-hours. Convert to kW first: 4,500 W = 4.5 kW. Energy = 4.5 kW × 3 h × 30 days = 405 kWh. Cost = 405 × $0.15 = $60.75.

  16. A 250 kcmil THWN-2 copper feeder lands on switchboard lugs that carry no temperature marking. There are three current-carrying conductors at a 30 °C ambient. What ampacity may be used for this conductor?

    • 205 A
    • 215 A
    • 230 A
    • 255 A

    Answer: 255 A

    Why: For conductors larger than 1 AWG (or circuits over 100 A), 110.14(C)(1)(b) lets you use the 75 °C column even without a marking. 250 kcmil copper is 255 A at 75 °C in Table 310.16. The 90 °C value of 290 A is not usable at these terminations. (NEC 110.14(C)(1)(b), Table 310.16)

  17. A 75 kVA, three-phase transformer is rated 480 V delta primary, 208Y/120 V secondary. What is its full-load primary current?

    • 90.21 A
    • 156.25 A
    • 208.18 A
    • 270.63 A

    Answer: 90.21 A

    Why: Three-phase current is VA ÷ (1.732 × line volts). On the primary: 75,000 ÷ (1.732 × 480) = 75,000 ÷ 831.36 = 90.21 A.

  18. In a dwelling, which 120 V, 15 A receptacle requires GFCI protection under 210.8(A)?

    • A receptacle beside the bed in a bedroom
    • A receptacle in an upstairs hallway
    • A receptacle in the dining room
    • A receptacle in an unfinished basement

    Answer: A receptacle in an unfinished basement

    Why: Basements are on the 210.8(A) list of dwelling locations where 125 V through 250 V receptacles need GFCI protection. Bedrooms, hallways and dining rooms are not on the list, though they do need AFCI protection under 210.12. (NEC 210.8(A))

  19. Under 90.3, which chapters of the NEC apply generally to all electrical installations?

    • Chapters 1 through 7
    • Chapters 1 through 3
    • Chapters 1 through 9
    • Chapters 1 through 4

    Answer: Chapters 1 through 4

    Why: Section 90.3 says Chapters 1 through 4 apply generally. Chapters 5, 6 and 7 apply to special occupancies, special equipment and special conditions and may supplement or modify the general rules. Knowing this split tells you where to look first. (NEC 90.3)

  20. A new in-ground pool is installed at a single-family home. At least one 125 V, 15 or 20 A general-purpose receptacle is required near the pool. Between what distances from the inside wall of the pool must it be located?

    • 5 ft and 10 ft
    • 5 ft and 20 ft
    • 6 ft and 10 ft
    • 6 ft and 20 ft

    Answer: 6 ft and 20 ft

    Why: 680.22(A)(1) requires at least one general-purpose receptacle at a dwelling pool so nobody runs an extension cord across the deck. It must sit no closer than 6 ft and no farther than 20 ft from the inside wall, and no higher than 6 ft 6 in. above the deck. It is also GFCI protected because it is within 20 ft. (NEC 680.22(A)(1))

Original practice questions written for Ohmward on the 2023 NEC — not real exam items.