Montana Journeyman Electrician Practice Test
20 questions in the style of the Montana journeyman exam (PSI): NEC rules, code navigation and calculations. Pick an answer, check it, and read why — with the section to look up.
The real Montana exam: 60 questions in 3 h, open book, 2020 NEC. Full Montana exam guide →
Under the 2023 NEC standard method, a 2,400 ft² dwelling has the two required small-appliance circuits and one laundry circuit. What is the net general lighting, small-appliance and laundry demand after Table 220.45?
Report a problem with this question
See all 20 questions with answers and explanations
Under the 2023 NEC standard method, a 2,400 ft² dwelling has the two required small-appliance circuits and one laundry circuit. What is the net general lighting, small-appliance and laundry demand after Table 220.45?
- 4,095 VA
- 5,520 VA
- 6,045 VA
- 11,700 VA
Answer: 6,045 VA
Why: Start with 2,400 × 3 VA = 7,200 VA, then add 1,500 VA for each small-appliance and laundry circuit (220.52): 7,200 + 3,000 + 1,500 = 11,700 VA. Table 220.45 takes the first 3,000 VA at 100 % and the next portion, up to 120,000 VA, at 35 %: 3,000 + (8,700 × 0.35) = 6,045 VA. (NEC 220.41, 220.52(A), 220.52(B), Table 220.45) Edition note: 2023 NEC numbering. In the 2026 NEC, load calculations moved from Article 220 to Article 120. The dwelling demand tiers were Table 220.42 in the 2020 NEC and are Table 220.45 in 2023.
A 10 hp, 460 V, three-phase induction motor has a nameplate full-load current of 13 A. What minimum ampacity must its branch-circuit conductors have?
- 14.0 A
- 16.1 A
- 16.25 A
- 17.5 A
Answer: 17.5 A
Why: Conductor sizing starts from the table full-load current, not the nameplate (430.6(A)(1)). Table 430.250 gives 14 A for 10 hp at 460 V, and 430.22 requires conductors rated at least 125 % of that: 14 × 1.25 = 17.5 A. (NEC 430.6(A)(1), Table 430.250, 430.22)
A 15 hp, three-phase induction motor is connected to a 208 V system and is rated 208 V. What minimum ampacity must its branch-circuit conductors have?
- 52.50 A
- 53.13 A
- 57.75 A
- 60.38 A
Answer: 57.75 A
Why: Use the 208 V column of Table 430.250, which lists 46.2 A for 15 hp. Branch-circuit conductors for one motor must be rated at least 125 % of that current (430.22): 46.2 × 1.25 = 57.75 A. (NEC Table 430.250, 430.22)
Under the 2023 NEC standard method, what demand load is used for a single 14 kW household electric range in a one-family dwelling?
- 8.0 kW
- 8.8 kW
- 10.5 kW
- 14.0 kW
Answer: 8.8 kW
Why: Table 220.55 Column C gives 8 kW for one range rated not over 12 kW. Note 1 raises the Column C value by 5 % for each kW (or major fraction) above 12 kW. A 14 kW range is 2 kW over, so 8 kW × 1.10 = 8.8 kW. (NEC 220.55, Table 220.55) Edition note: 2023 NEC numbering. In the 2026 NEC, load calculations moved from Article 220 to Article 120.
Three 6 AWG THHN copper current-carrying conductors run through a boiler room with a 45 °C ambient. Using Table 310.15(B)(1)(1), what is the conductor's ampacity after ambient correction, before the termination check?
- 53.30 A
- 60.00 A
- 61.50 A
- 65.25 A
Answer: 65.25 A
Why: THHN is 90 °C, so start at 75 A (6 AWG copper, 90 °C column). The 41–45 °C row gives 0.87 in the 90 °C column: 75 × 0.87 = 65.25 A. The 110.14(C) termination check comes afterwards. (NEC Table 310.15(B)(1)(1), Table 310.16) Edition note: The 2023 NEC numbers the 30 °C-based correction table as Table 310.15(B)(1)(1); the 2020 edition called it Table 310.15(B)(1).
A box with internal clamps contains two 12/2 NM cables spliced through for a 20 A circuit and one 14/2 NM cable feeding a 15 A duplex receptacle in the same box. All three cables have bare grounds. What minimum box volume is required?
- 21.50 in.³
- 22.00 in.³
- 23.50 in.³
- 24.00 in.³
Answer: 21.50 in.³
Why: Each conductor counts at its own size: 4 × 2.25 = 9.00 plus 2 × 2.00 = 4.00. Grounds take one allowance at the largest ground (12 AWG, 2.25) and clamps one at the largest conductor (12 AWG, 2.25). The receptacle is connected only to 14 AWG, so it takes 2 × 2.00 = 4.00 (314.16(B)(4)). Total 21.50 in.³. (NEC 314.16(B)(2), 314.16(B)(4), 314.16(B)(5), Table 314.16(B))
A loose splice on a branch circuit has 0.05 Ω of resistance and carries 40 A. How much power is turned into heat at the splice?
- 2 W
- 80 W
- 800 W
- 1,600 W
Answer: 80 W
Why: With amps and ohms given, use P = I² × R: 40² × 0.05 = 1,600 × 0.05 = 80 W. That is a small lamp's worth of heat buried in a box. Because heat rises with the square of current, a bad termination that is fine at light load can scorch at heavy load.
Article 100 defines a continuous load as one where the maximum current is expected to continue for how long?
- 30 minutes or more
- 1 hour or more
- 2 hours or more
- 3 hours or more
Answer: 3 hours or more
Why: Article 100 defines a continuous load as a load where the maximum current is expected to continue for 3 hours or more. Store lighting, office lighting and EV charging are typical examples. (NEC Article 100 (Continuous Load))
Type NM cable is run along the side of a floor joist to a metal device box. Under the general rule of 334.30, what are the maximum distances for securing the cable?
- Within 12 in. of the box, then every 4-1/2 ft
- Within 12 in. of the box, then every 6 ft
- Within 18 in. of the box, then every 4-1/2 ft
- Within 3 ft of the box, then every 10 ft
Answer: Within 12 in. of the box, then every 4-1/2 ft
Why: 334.30 requires NM cable to be secured within 12 in. of every box, cabinet or fitting and at intervals not over 4-1/2 ft. The 12 in. rule keeps the cable from pulling out of the clamp; the 4-1/2 ft spacing keeps it tight to the framing. (NEC 334.30)
A metal device box with internal cable clamps has two 14/2 NM cables with ground entering it. A single-pole switch is installed, and the two bare grounds are spliced with a pigtail to the switch. What minimum box volume is required?
- 14.00 in.³
- 16.00 in.³
- 18.00 in.³
- 20.00 in.³
Answer: 16.00 in.³
Why: Count by 314.16(B) at 2.00 in.³ for 14 AWG: four insulated conductors (8.00), one allowance for all grounds (2.00), one for the clamps (2.00), and two for the switch yoke (4.00). Total 16.00 in.³. The pigtail never leaves the box, so it counts zero. (NEC 314.16(B)(1), 314.16(B)(2), 314.16(B)(4), 314.16(B)(5), Table 314.16(B))
Along an unbroken living room wall, what is the maximum distance from any point on the floor line to the nearest receptacle outlet?
- 4 ft
- 6 ft
- 10 ft
- 12 ft
Answer: 6 ft
Why: 210.52(A)(1) requires receptacles placed so that no point along the floor line of any wall space is more than 6 ft from a receptacle outlet. That allows receptacles up to 12 ft apart. (NEC 210.52(A)(1))
A feeder supplies 90 A of continuous lighting load and no other load. The breaker is not listed for 100 % operation. What is the minimum standard breaker rating?
- 90 A
- 110 A
- 125 A
- 150 A
Answer: 125 A
Why: 215.3 requires the feeder overcurrent device to be at least 125 % of the continuous load: 90 × 1.25 = 112.5 A. 112.5 A isn't a standard rating, so go up to the next standard size in 240.6(A), 125 A. (NEC 215.3, 240.6(A))
A textile mill has looms that throw off cotton lint and flyings, which collect on ledges and equipment. Under Article 500, how is this area classified?
- Class I, Group D
- Class II, Group G
- Class III
- Class II, Group E
Answer: Class III
Why: Class locations are sorted by what can burn. Class I is gases and vapors, Class II is combustible dust, and Class III is easily ignitible fibers and flyings such as cotton lint. Textile mills and cotton gins are the textbook Class III examples in 500.5(D). Class III has no material groups. (NEC 500.5(D))
A 200 A service is supplied by 3/0 AWG copper service-entrance conductors. What minimum size copper grounding electrode conductor is required to the metal underground water pipe electrode?
- 8 AWG
- 6 AWG
- 4 AWG
- 2 AWG
Answer: 4 AWG
Why: Table 250.66 sizes the GEC from the largest ungrounded service-entrance conductor. 3/0 copper falls in the "2/0 or 3/0" row, which calls for 4 AWG copper. The water pipe isn't a rod, plate, concrete-encased electrode, or ground ring, so none of the 250.66(A)–(C) limits apply. (NEC 250.66, Table 250.66)
A ceiling box with internal clamps and a luminaire stud has two 14/2 NM cables with ground entering it. The luminaire's two 18 AWG fixture wires and its grounding conductor come in from a domed canopy. What minimum box volume is required?
- 12.00 in.³
- 14.00 in.³
- 16.00 in.³
- 17.00 in.³
Answer: 14.00 in.³
Why: Four 14 AWG conductors take 8.00 in.³. Grounds, clamps and the stud each take one 2.00 in.³ allowance, adding 6.00. The fixture wires and the luminaire ground from a domed canopy may be left out (exception to 314.16(B)(1)). Total 14.00 in.³. (NEC 314.16(B)(1) Exception, 314.16(B)(3), Table 314.16(B))
Under the 2023 NEC optional method for a one-family dwelling (220.82), the first 10 kVA of the general load is taken at 100 %. At what percentage is the rest of the general load taken?
- 25 %
- 35 %
- 40 %
- 65 %
Answer: 40 %
Why: 220.82(B) takes the first 10 kVA of the general load at 100 % and everything above that at 40 %. Heating and air conditioning are not in that pile; they are added separately under 220.82(C). (NEC 220.82(B)) Edition note: 2023 NEC numbering. In the 2026 NEC, load calculations moved from Article 220 to Article 120.
An office building has an emergency system for egress lighting required by the building code. After normal power fails, within what time must the emergency system supply power?
- 10 seconds
- 30 seconds
- 60 seconds
- 90 seconds
Answer: 10 seconds
Why: 700.12 requires emergency lighting and power to be available within the time needed for the application, but no more than 10 seconds. Emergency systems protect life during evacuation, so people cannot be left in the dark for long. Legally required standby gets 60 seconds; optional standby has no time limit. (NEC 700.12)
A 22 kW, 240 V, single-phase standby generator is rated at unity power factor. What minimum ampacity must the conductors from its output terminals to the first overcurrent device have?
- 60.9 A
- 91.7 A
- 105.4 A
- 114.6 A
Answer: 105.4 A
Why: Rated current is 22,000 ÷ 240 = 91.67 A. 445.13(A) requires these conductors to be rated at least 115 % of the nameplate current: 91.67 × 1.15 = 105.42 A, about 105.4 A. (NEC 445.13(A))
A one-family dwelling has a 125 A, 120/240 V, single-phase service supplying the entire dwelling load. Using 310.12 with copper THWN-2 conductors, 75 °C terminations, and no adjustment or correction factors, what is the minimum ungrounded service-entrance conductor size?
- 3 AWG
- 2 AWG
- 1 AWG
- 1/0 AWG
Answer: 2 AWG
Why: 310.12 lets the conductors of a 120/240 V single-phase dwelling service be sized at 83 % of the service rating: 125 × 0.83 = 103.75 A. In the 75 °C copper column of Table 310.16, 3 AWG is 100 A (too small) and 2 AWG is 115 A. So 2 AWG copper is the minimum. (NEC 310.12, Table 310.16)
A resistive heater is moved from a 120 V circuit to a 240 V circuit. If its resistance stays the same, how does its power compare with before?
- One-quarter as much
- One-half as much
- Twice as much
- Four times as much
Answer: Four times as much
Why: With resistance fixed, P = E² ÷ R. Doubling E makes E² four times larger, so the heater makes four times the watts. Current doubles too (I = E ÷ R), and twice the volts times twice the amps is four times the power. That is why a 120 V heater on 240 V fails fast.
Original practice questions written for Ohmward on the 2023 NEC — not real exam items.