You are sizing the branch-circuit short-circuit and ground-fault protective device for a general-purpose three-phase squirrel-cage motor. Which current do you start from?
Report a problem with this question
See all 20 questions with answers and explanations
You are sizing the branch-circuit short-circuit and ground-fault protective device for a general-purpose three-phase squirrel-cage motor. Which current do you start from?
- The nameplate full-load current
- The locked-rotor current on the nameplate
- The full-load current from Table 430.250
- The service-factor current on the nameplate
Answer: The full-load current from Table 430.250
Why: 430.6(A)(1) sends you to the FLC tables for conductor ampacity, switch ratings and the short-circuit and ground-fault device. Table values are conservative and let the circuit be designed before the exact motor arrives. The nameplate value is used for separate overload protection. (NEC 430.6(A)(1), 430.6(A)(2), Table 430.250)
A 75 kVA, three-phase transformer is rated 480 V delta primary, 208Y/120 V secondary. What is its full-load primary current?
- 90.21 A
- 156.25 A
- 208.18 A
- 270.63 A
Answer: 90.21 A
Why: Three-phase current is VA ÷ (1.732 × line volts). On the primary: 75,000 ÷ (1.732 × 480) = 75,000 ÷ 831.36 = 90.21 A.
A 20 A multioutlet branch circuit supplies lighting outlets and fastened-in-place equipment. What is the maximum total rating of the fastened-in-place equipment, other than luminaires?
- 7.5 A
- 10 A
- 12 A
- 16 A
Answer: 10 A
Why: 210.23 limits the total rating of utilization equipment fastened in place, other than luminaires, to 50 % of the circuit rating when the circuit also supplies lighting or cord-and-plug equipment. 50 % of 20 A is 10 A. (NEC 210.23)
A resistive heater is moved from a 120 V circuit to a 240 V circuit. If its resistance stays the same, how does its power compare with before?
- One-quarter as much
- One-half as much
- Twice as much
- Four times as much
Answer: Four times as much
Why: With resistance fixed, P = E² ÷ R. Doubling E makes E² four times larger, so the heater makes four times the watts. Current doubles too (I = E ÷ R), and twice the volts times twice the amps is four times the power. That is why a 120 V heater on 240 V fails fast.
In a dwelling, which 120 V, 15 A receptacle requires GFCI protection under 210.8(A)?
- A receptacle beside the bed in a bedroom
- A receptacle in an upstairs hallway
- A receptacle in the dining room
- A receptacle in an unfinished basement
Answer: A receptacle in an unfinished basement
Why: Basements are on the 210.8(A) list of dwelling locations where 125 V through 250 V receptacles need GFCI protection. Bedrooms, hallways and dining rooms are not on the list, though they do need AFCI protection under 210.12. (NEC 210.8(A))
You need the requirements for a rooftop solar photovoltaic system (Article 690). Which chapter of the NEC contains it?
- Chapter 5
- Chapter 6
- Chapter 7
- Chapter 8
Answer: Chapter 6
Why: Chapter 6 covers special equipment, including signs, elevators, EV charging, pools (680) and solar PV (690). The first digit of the article number is the chapter: 690 is in Chapter 6. (NEC Article 690, 90.3)
A 120 V branch circuit supplies a metal pole light in a parking lot. Which of these must not be counted on as the effective ground-fault current path for that circuit?
- The earth, through a ground rod at the pole
- An EMT raceway with listed set-screw fittings
- A copper wire-type equipment grounding conductor
- The metal armor of listed Type AC cable
Answer: The earth, through a ground rod at the pole
Why: 250.4(A)(5) says the earth is not to be considered an effective ground-fault current path. Soil resistance is far too high to let enough current flow to open the breaker. The fault path has to be an intentional, low-impedance metal path back to the source, such as EMT, a wire-type EGC, or AC cable armor, all of which 250.118 permits. (NEC 250.4(A)(5), 250.118)
A 120 V ungrounded conductor faults to a metal sign whose only connection to anything is a ground rod. The total path through the earth back to the utility's grounded conductor measures 25 Ω, and the circuit breaker is rated 20 A. Ignoring wire resistance, about how much fault current flows?
- 0.21 A
- 4.8 A
- 20 A
- 3,000 A
Answer: 4.8 A
Why: Ohm's law: I = E ÷ R = 120 V ÷ 25 Ω = 4.8 A. That's far below the breaker's 20 A rating, so the breaker never trips and the sign stays energized. This is exactly why 250.4(A)(5) says the earth can't be the effective ground-fault current path. (NEC 250.4(A)(5))
You're setting a feeder-supplied panelboard in the same building as the service. The feeder has two ungrounded conductors, a neutral, and an EGC. The panel ships with a green bonding screw for the neutral bar. What do you do with the screw?
- Install it so the neutral bar is bonded to the can
- Install it, but only if a ground rod is added here
- Install it, but only if the feeder lacks an EGC
- Leave it out and keep the neutral bar isolated
Answer: Leave it out and keep the neutral bar isolated
Why: Past the service disconnect, the grounded conductor may not be connected to equipment grounding (250.24(A)(5), 250.142(B)). The neutral bar stays isolated, and the EGCs land on a separate equipment grounding bar bonded to the enclosure (408.40). The only neutral-to-ground bond is the main bonding jumper at the service. (NEC 250.24(A)(5), 250.142(B), 408.40)
A branch circuit supplies 36 A of continuous load and 8 A of noncontinuous load. The breaker is not listed for 100 % operation. What is the minimum standard breaker rating?
- 40 A
- 45 A
- 50 A
- 60 A
Answer: 60 A
Why: 210.20(A): at least 125 % of the continuous load plus 100 % of the noncontinuous load. 36 × 1.25 = 45 A, plus 8 A = 53 A. The next standard rating at or above 53 A is 60 A. (NEC 210.20(A), 240.6(A))
A 25 ft feeder tap is taken from a feeder protected by a 300 A breaker. Under 240.21(B)(2), what is the minimum ampacity of the tap conductors?
- 30 A
- 100 A
- 150 A
- 300 A
Answer: 100 A
Why: 240.21(B)(2) requires a 25-ft tap to have an ampacity of at least one-third of the feeder overcurrent device rating: 300 ÷ 3 = 100 A. The tap must also end in a single breaker or set of fuses that limits the load to the tap's ampacity. (NEC 240.21(B)(2))
A 30 A branch circuit uses 10 AWG THHN copper. Neither the breaker nor the receptacle terminals carry any temperature marking. Which ampacity column of Table 310.16 limits this conductor?
- The 60 °C column
- The 75 °C column
- The 90 °C column
- Any column, if the load is noncontinuous
Answer: The 60 °C column
Why: For circuits rated 100 A or less, or conductors 14 through 1 AWG, 110.14(C)(1)(a) assumes 60 °C terminations unless the equipment is listed and marked for a higher rating. 10 AWG copper is 30 A in the 60 °C column, which happens to match this 30 A circuit. (NEC 110.14(C)(1)(a), Table 310.16)
Article 100 defines a continuous load as one where the maximum current is expected to continue for how long?
- 30 minutes or more
- 1 hour or more
- 2 hours or more
- 3 hours or more
Answer: 3 hours or more
Why: Article 100 defines a continuous load as a load where the maximum current is expected to continue for 3 hours or more. Store lighting, office lighting and EV charging are typical examples. (NEC Article 100 (Continuous Load))
A 250 kcmil THWN-2 copper feeder lands on switchboard lugs that carry no temperature marking. There are three current-carrying conductors at a 30 °C ambient. What ampacity may be used for this conductor?
- 205 A
- 215 A
- 230 A
- 255 A
Answer: 255 A
Why: For conductors larger than 1 AWG (or circuits over 100 A), 110.14(C)(1)(b) lets you use the 75 °C column even without a marking. 250 kcmil copper is 255 A at 75 °C in Table 310.16. The 90 °C value of 290 A is not usable at these terminations. (NEC 110.14(C)(1)(b), Table 310.16)
A balanced three-phase, 208 V load draws 150 A on each line. How many kVA does it draw?
- 18.0 kVA
- 31.2 kVA
- 54.0 kVA
- 93.6 kVA
Answer: 54.0 kVA
Why: Three-phase kVA = 1.732 × line volts × line amps ÷ 1,000 = 1.732 × 208 × 150 ÷ 1,000 = 54.04 kVA, which rounds to 54.0 kVA. The same answer comes from 3 × 120 V × 150 A per phase.
A ceiling box with internal clamps and a luminaire stud has two 14/2 NM cables with ground entering it. The luminaire's two 18 AWG fixture wires and its grounding conductor come in from a domed canopy. What minimum box volume is required?
- 12.00 in.³
- 14.00 in.³
- 16.00 in.³
- 17.00 in.³
Answer: 14.00 in.³
Why: Four 14 AWG conductors take 8.00 in.³. Grounds, clamps and the stud each take one 2.00 in.³ allowance, adding 6.00. The fixture wires and the luminaire ground from a domed canopy may be left out (exception to 314.16(B)(1)). Total 14.00 in.³. (NEC 314.16(B)(1) Exception, 314.16(B)(3), Table 314.16(B))
Under the 2023 NEC optional method for a one-family dwelling (220.82), the first 10 kVA of the general load is taken at 100 %. At what percentage is the rest of the general load taken?
- 25 %
- 35 %
- 40 %
- 65 %
Answer: 40 %
Why: 220.82(B) takes the first 10 kVA of the general load at 100 % and everything above that at 40 %. Heating and air conditioning are not in that pile; they are added separately under 220.82(C). (NEC 220.82(B)) Edition note: 2023 NEC numbering. In the 2026 NEC, load calculations moved from Article 220 to Article 120.
The general lighting in a retail store runs at full load from 8 a.m. to 10 p.m. every day. Under Article 100, how is this load classified?
- Noncontinuous load
- Intermittent duty
- Periodic duty
- Continuous load
Answer: Continuous load
Why: Article 100 defines a continuous load as one where maximum current is expected to continue for 3 hours or more. Store lighting that runs all day easily qualifies, so it gets the 125 % sizing rules for conductors and overcurrent devices. (NEC Article 100, Continuous Load)
A 20 A multioutlet branch circuit supplies lighting and receptacles. What is the maximum rating of one cord-and-plug-connected appliance that is not fastened in place?
- 10 A
- 12 A
- 16 A
- 20 A
Answer: 16 A
Why: 210.23 limits a single cord-and-plug-connected item not fastened in place to 80 % of the branch-circuit rating. 80 % of 20 A is 16 A. (NEC 210.23)
Which receptacle ratings are permitted on a 40 A branch circuit with more than one receptacle?
- 40 A only
- 30 A or 40 A
- 50 A only
- 40 A or 50 A
Answer: 40 A or 50 A
Why: Table 210.21(B)(3) lists the receptacle ratings for each circuit size: 15 A → 15 A; 20 A → 15 or 20 A; 30 A → 30 A; 40 A → 40 or 50 A; 50 A → 50 A. A 40 A circuit takes 40 A or 50 A receptacles. (NEC Table 210.21(B)(3))
Original practice questions written for Ohmward on the 2023 NEC — not real exam items.