New Jersey Journeyman Electrician Practice Test
20 questions in the style of the New Jersey journeyman exam: NEC rules, code navigation and calculations. Pick an answer, check it, and read why — with the section to look up.
A load draws 100 kVA at a power factor of 0.8. How much real power does it use?
Report a problem with this question
See all 20 questions with answers and explanations
A load draws 100 kVA at a power factor of 0.8. How much real power does it use?
- 60 kW
- 80 kW
- 100 kW
- 125 kW
Answer: 80 kW
Why: Power factor is the share of apparent power that does real work: kW = kVA × PF = 100 × 0.8 = 80 kW. The remaining side of the triangle is √(100² − 80²) = 60 kVAR of reactive power.
In a dwelling, which 120 V, 15 A receptacle requires GFCI protection under 210.8(A)?
- A receptacle beside the bed in a bedroom
- A receptacle in an upstairs hallway
- A receptacle in the dining room
- A receptacle in an unfinished basement
Answer: A receptacle in an unfinished basement
Why: Basements are on the 210.8(A) list of dwelling locations where 125 V through 250 V receptacles need GFCI protection. Bedrooms, hallways and dining rooms are not on the list, though they do need AFCI protection under 210.12. (NEC 210.8(A))
Resistors of 10 Ω, 20 Ω and 30 Ω are connected in series across 120 V. What is the voltage across the 30 Ω resistor?
- 20 V
- 40 V
- 60 V
- 120 V
Answer: 60 V
Why: In series the resistances add: 10 + 20 + 30 = 60 Ω, and the same current flows through each: 120 ÷ 60 = 2 A. The drop across the 30 Ω resistor is 2 A × 30 Ω = 60 V. The biggest resistor takes the biggest share, and the drops (20 + 40 + 60) add back to 120 V.
A 250 kcmil THWN-2 copper feeder lands on switchboard lugs that carry no temperature marking. There are three current-carrying conductors at a 30 °C ambient. What ampacity may be used for this conductor?
- 205 A
- 215 A
- 230 A
- 255 A
Answer: 255 A
Why: For conductors larger than 1 AWG (or circuits over 100 A), 110.14(C)(1)(b) lets you use the 75 °C column even without a marking. 250 kcmil copper is 255 A at 75 °C in Table 310.16. The 90 °C value of 290 A is not usable at these terminations. (NEC 110.14(C)(1)(b), Table 310.16)
A resistive water heater element rated 4,500 W at 240 V is connected to a 208 V circuit. If its resistance does not change, about how many watts does it produce?
- 3,380 W
- 3,900 W
- 4,500 W
- 5,192 W
Answer: 3,380 W
Why: The element's resistance is what stays fixed: R = 240² ÷ 4,500 = 12.8 Ω. At 208 V, P = 208² ÷ 12.8 = 43,264 ÷ 12.8 = 3,380 W, about 75 % of nameplate. Power follows the square of voltage, so a 13 % lower voltage costs about 25 % of the heat.
On a 480 V, three-phase, four-wire wye system, what voltage should you measure from any phase conductor to the neutral?
- 277 V
- 339 V
- 480 V
- 831 V
Answer: 277 V
Why: In a wye, line voltage = phase voltage × 1.732, so phase voltage = 480 ÷ 1.732 = 277 V. That's why the system is called 480Y/277 V and why 277 V lighting runs phase to neutral.
A 6 AWG THWN copper conductor (75 °C terminations, no correction or adjustment) supplies a single fixed 55 A noncontinuous load on an individual branch circuit. What is the largest breaker that may protect it?
- 60 A
- 70 A
- 75 A
- 80 A
Answer: 70 A
Why: 6 AWG copper at 75 °C is 65 A, which isn't a standard rating. 240.4(B) lets you use the next higher standard rating, 70 A, because the circuit doesn't supply multiple receptacles for portable loads and the rating is under 800 A. (NEC 240.4(B), 240.6(A), Table 310.16)
A 10 hp, 460 V, three-phase motor has a nameplate full-load current of 13 A and a service factor of 1.15. What is the maximum trip setting for a separate overload device, using the basic rule?
- 16.25 A
- 16.90 A
- 17.50 A
- 18.20 A
Answer: 16.25 A
Why: Overloads are sized from the nameplate current (430.6(A)(2)). With a service factor of 1.15 or more, 430.32(A)(1) allows up to 125 %: 13 × 1.25 = 16.25 A. (NEC 430.6(A)(2), 430.32(A)(1))
A 20 A multioutlet branch circuit supplies lighting and receptacles. What is the maximum rating of one cord-and-plug-connected appliance that is not fastened in place?
- 10 A
- 12 A
- 16 A
- 20 A
Answer: 16 A
Why: 210.23 limits a single cord-and-plug-connected item not fastened in place to 80 % of the branch-circuit rating. 80 % of 20 A is 16 A. (NEC 210.23)
Which receptacle ratings are permitted on a 40 A branch circuit with more than one receptacle?
- 40 A only
- 30 A or 40 A
- 50 A only
- 40 A or 50 A
Answer: 40 A or 50 A
Why: Table 210.21(B)(3) lists the receptacle ratings for each circuit size: 15 A → 15 A; 20 A → 15 or 20 A; 30 A → 30 A; 40 A → 40 or 50 A; 50 A → 50 A. A 40 A circuit takes 40 A or 50 A receptacles. (NEC Table 210.21(B)(3))
Article 100 defines a continuous load as one where the maximum current is expected to continue for how long?
- 30 minutes or more
- 1 hour or more
- 2 hours or more
- 3 hours or more
Answer: 3 hours or more
Why: Article 100 defines a continuous load as a load where the maximum current is expected to continue for 3 hours or more. Store lighting, office lighting and EV charging are typical examples. (NEC Article 100 (Continuous Load))
A 120 V branch circuit supplies a metal pole light in a parking lot. Which of these must not be counted on as the effective ground-fault current path for that circuit?
- The earth, through a ground rod at the pole
- An EMT raceway with listed set-screw fittings
- A copper wire-type equipment grounding conductor
- The metal armor of listed Type AC cable
Answer: The earth, through a ground rod at the pole
Why: 250.4(A)(5) says the earth is not to be considered an effective ground-fault current path. Soil resistance is far too high to let enough current flow to open the breaker. The fault path has to be an intentional, low-impedance metal path back to the source, such as EMT, a wire-type EGC, or AC cable armor, all of which 250.118 permits. (NEC 250.4(A)(5), 250.118)
A metal device box with internal cable clamps has two 14/2 NM cables with ground entering it. A single-pole switch is installed, and the two bare grounds are spliced with a pigtail to the switch. What minimum box volume is required?
- 14.00 in.³
- 16.00 in.³
- 18.00 in.³
- 20.00 in.³
Answer: 16.00 in.³
Why: Count by 314.16(B) at 2.00 in.³ for 14 AWG: four insulated conductors (8.00), one allowance for all grounds (2.00), one for the clamps (2.00), and two for the switch yoke (4.00). Total 16.00 in.³. The pigtail never leaves the box, so it counts zero. (NEC 314.16(B)(1), 314.16(B)(2), 314.16(B)(4), 314.16(B)(5), Table 314.16(B))
A 25 kVA, single-phase transformer has a 480 V primary and a 240 V secondary. What is its full-load secondary current?
- 52.08 A
- 60.14 A
- 104.17 A
- 180.42 A
Answer: 104.17 A
Why: Single-phase current is VA ÷ volts, with no √3. On the 240 V side: 25,000 ÷ 240 = 104.17 A. The secondary current is twice the primary current because the voltage is half.
A 72 A noncontinuous load is supplied by three THHN copper conductors in EMT at a 30 °C ambient. The breaker and the load terminals are listed and marked for 75 °C. What is the minimum conductor size?
- 6 AWG
- 4 AWG
- 3 AWG
- 2 AWG
Answer: 4 AWG
Why: THHN is a 90 °C conductor, but the 75 °C terminals limit the ampacity you may use (110.14(C)(1)(a)). In the 75 °C copper column of Table 310.16, 6 AWG is 65 A (too small) and 4 AWG is 85 A, so 4 AWG is the smallest that carries 72 A. (NEC 110.14(C)(1)(a), Table 310.16)
A 75 kVA, three-phase, 480 V to 208Y/120 V transformer is protected on the primary side only. What is the largest standard primary breaker permitted by Table 450.3(B) and its notes?
- 90 A
- 100 A
- 110 A
- 125 A
Answer: 125 A
Why: Primary current is 75,000 ÷ (1.732 × 480) = 90.21 A. Primary-only protection for 9 A or more is 125 %: 90.21 × 1.25 = 112.77 A. Table 450.3(B) Note 1 permits the next higher standard size, 125 A. (NEC 450.3(B), Table 450.3(B), 240.6(A))
The supply frequency to a circuit rises from 50 Hz to 60 Hz. What happens to inductive reactance (XL) and capacitive reactance (XC)?
- XL rises and XC rises
- XL falls and XC rises
- XL falls and XC falls
- XL rises and XC falls
Answer: XL rises and XC falls
Why: XL = 2πfL, so it rises in step with frequency. XC = 1 ÷ (2πfC), so frequency is in the denominator and XC falls as frequency rises. Coils fight fast changes harder; capacitors pass them more easily.
You are pouring a 1-1/2 in. trade size sealing fitting in a Class I, Division 1 location. The fitting has no marking that calls for a different depth. What is the minimum thickness of sealing compound?
- 5/8 in.
- 3/4 in.
- 1-1/2 in.
- 2 in.
Answer: 1-1/2 in.
Why: The compound must be at least as thick as the trade size of the sealing fitting, and never less than 5/8 in. (501.15(C)(3)). For a 1-1/2 in. fitting that means at least 1-1/2 in. of compound. The 5/8 in. figure is only the floor for very small fittings. (NEC 501.15(C)(3))
A 30 A branch circuit uses 10 AWG THHN copper. Neither the breaker nor the receptacle terminals carry any temperature marking. Which ampacity column of Table 310.16 limits this conductor?
- The 60 °C column
- The 75 °C column
- The 90 °C column
- Any column, if the load is noncontinuous
Answer: The 60 °C column
Why: For circuits rated 100 A or less, or conductors 14 through 1 AWG, 110.14(C)(1)(a) assumes 60 °C terminations unless the equipment is listed and marked for a higher rating. 10 AWG copper is 30 A in the 60 °C column, which happens to match this 30 A circuit. (NEC 110.14(C)(1)(a), Table 310.16)
Under the 2023 NEC standard method, what demand load is used for a single 14 kW household electric range in a one-family dwelling?
- 8.0 kW
- 8.8 kW
- 10.5 kW
- 14.0 kW
Answer: 8.8 kW
Why: Table 220.55 Column C gives 8 kW for one range rated not over 12 kW. Note 1 raises the Column C value by 5 % for each kW (or major fraction) above 12 kW. A 14 kW range is 2 kW over, so 8 kW × 1.10 = 8.8 kW. (NEC 220.55, Table 220.55) Edition note: 2023 NEC numbering. In the 2026 NEC, load calculations moved from Article 220 to Article 120.
Original practice questions written for Ohmward on the 2023 NEC — not real exam items.