New Mexico Journeyman Electrician Practice Test
20 questions in the style of the New Mexico journeyman exam (PSI): NEC rules, code navigation and calculations. Pick an answer, check it, and read why — with the section to look up.
The real New Mexico exam: 100 questions in 6 h 25 min, 2020 NEC. Full New Mexico exam guide →
A 20 A multioutlet branch circuit supplies lighting and receptacles. What is the maximum rating of one cord-and-plug-connected appliance that is not fastened in place?
Report a problem with this question
See all 20 questions with answers and explanations
A 20 A multioutlet branch circuit supplies lighting and receptacles. What is the maximum rating of one cord-and-plug-connected appliance that is not fastened in place?
- 10 A
- 12 A
- 16 A
- 20 A
Answer: 16 A
Why: 210.23 limits a single cord-and-plug-connected item not fastened in place to 80 % of the branch-circuit rating. 80 % of 20 A is 16 A. (NEC 210.23)
Which receptacle ratings are permitted on a 40 A branch circuit with more than one receptacle?
- 40 A only
- 30 A or 40 A
- 50 A only
- 40 A or 50 A
Answer: 40 A or 50 A
Why: Table 210.21(B)(3) lists the receptacle ratings for each circuit size: 15 A → 15 A; 20 A → 15 or 20 A; 30 A → 30 A; 40 A → 40 or 50 A; 50 A → 50 A. A 40 A circuit takes 40 A or 50 A receptacles. (NEC Table 210.21(B)(3))
A 30 A branch circuit uses 10 AWG THHN copper. Neither the breaker nor the receptacle terminals carry any temperature marking. Which ampacity column of Table 310.16 limits this conductor?
- The 60 °C column
- The 75 °C column
- The 90 °C column
- Any column, if the load is noncontinuous
Answer: The 60 °C column
Why: For circuits rated 100 A or less, or conductors 14 through 1 AWG, 110.14(C)(1)(a) assumes 60 °C terminations unless the equipment is listed and marked for a higher rating. 10 AWG copper is 30 A in the 60 °C column, which happens to match this 30 A circuit. (NEC 110.14(C)(1)(a), Table 310.16)
A 60 A circuit breaker protects 6 AWG copper feeder conductors to a subpanel in the same building. The conductors are not upsized. What minimum size copper equipment grounding conductor is required?
- 12 AWG
- 10 AWG
- 8 AWG
- 6 AWG
Answer: 10 AWG
Why: Table 250.122 sizes the EGC from the rating of the overcurrent device ahead of the circuit. The 60 A row calls for 10 AWG copper. The size of the circuit conductors doesn't set the EGC unless they were upsized (250.122(B)). (NEC 250.122(A), Table 250.122)
A 120 V ungrounded conductor faults to a metal sign whose only connection to anything is a ground rod. The total path through the earth back to the utility's grounded conductor measures 25 Ω, and the circuit breaker is rated 20 A. Ignoring wire resistance, about how much fault current flows?
- 0.21 A
- 4.8 A
- 20 A
- 3,000 A
Answer: 4.8 A
Why: Ohm's law: I = E ÷ R = 120 V ÷ 25 Ω = 4.8 A. That's far below the breaker's 20 A rating, so the breaker never trips and the sign stays energized. This is exactly why 250.4(A)(5) says the earth can't be the effective ground-fault current path. (NEC 250.4(A)(5))
You're setting a feeder-supplied panelboard in the same building as the service. The feeder has two ungrounded conductors, a neutral, and an EGC. The panel ships with a green bonding screw for the neutral bar. What do you do with the screw?
- Install it so the neutral bar is bonded to the can
- Install it, but only if a ground rod is added here
- Install it, but only if the feeder lacks an EGC
- Leave it out and keep the neutral bar isolated
Answer: Leave it out and keep the neutral bar isolated
Why: Past the service disconnect, the grounded conductor may not be connected to equipment grounding (250.24(A)(5), 250.142(B)). The neutral bar stays isolated, and the EGCs land on a separate equipment grounding bar bonded to the enclosure (408.40). The only neutral-to-ground bond is the main bonding jumper at the service. (NEC 250.24(A)(5), 250.142(B), 408.40)
A branch circuit supplies 36 A of continuous load and 8 A of noncontinuous load. The breaker is not listed for 100 % operation. What is the minimum standard breaker rating?
- 40 A
- 45 A
- 50 A
- 60 A
Answer: 60 A
Why: 210.20(A): at least 125 % of the continuous load plus 100 % of the noncontinuous load. 36 × 1.25 = 45 A, plus 8 A = 53 A. The next standard rating at or above 53 A is 60 A. (NEC 210.20(A), 240.6(A))
A resistive water heater element rated 4,500 W at 240 V is connected to a 208 V circuit. If its resistance does not change, about how many watts does it produce?
- 3,380 W
- 3,900 W
- 4,500 W
- 5,192 W
Answer: 3,380 W
Why: The element's resistance is what stays fixed: R = 240² ÷ 4,500 = 12.8 Ω. At 208 V, P = 208² ÷ 12.8 = 43,264 ÷ 12.8 = 3,380 W, about 75 % of nameplate. Power follows the square of voltage, so a 13 % lower voltage costs about 25 % of the heat.
A balanced three-phase, 208 V load draws 150 A on each line. How many kVA does it draw?
- 18.0 kVA
- 31.2 kVA
- 54.0 kVA
- 93.6 kVA
Answer: 54.0 kVA
Why: Three-phase kVA = 1.732 × line volts × line amps ÷ 1,000 = 1.732 × 208 × 150 ÷ 1,000 = 54.04 kVA, which rounds to 54.0 kVA. The same answer comes from 3 × 120 V × 150 A per phase.
The general lighting in a retail store runs at full load from 8 a.m. to 10 p.m. every day. Under Article 100, how is this load classified?
- Noncontinuous load
- Intermittent duty
- Periodic duty
- Continuous load
Answer: Continuous load
Why: Article 100 defines a continuous load as one where maximum current is expected to continue for 3 hours or more. Store lighting that runs all day easily qualifies, so it gets the 125 % sizing rules for conductors and overcurrent devices. (NEC Article 100, Continuous Load)
A 480Y/277 V panelboard has exposed live parts on one side of the working space and a concrete block wall on the other. What minimum depth of working space does Table 110.26(A)(1) require?
- 3 ft
- 3½ ft
- 4 ft
- 5 ft
Answer: 3½ ft
Why: Enter the table with voltage to ground: 277 V falls in the 151–1000 V row. Concrete, brick and tile walls are considered grounded, so live parts across from a block wall is Condition 2. The minimum depth is 3½ ft (1.0 m). (NEC 110.26(A)(1), Table 110.26(A)(1))
An office building has an emergency system for egress lighting required by the building code. After normal power fails, within what time must the emergency system supply power?
- 10 seconds
- 30 seconds
- 60 seconds
- 90 seconds
Answer: 10 seconds
Why: 700.12 requires emergency lighting and power to be available within the time needed for the application, but no more than 10 seconds. Emergency systems protect life during evacuation, so people cannot be left in the dark for long. Legally required standby gets 60 seconds; optional standby has no time limit. (NEC 700.12)
Under 90.3, which chapters of the NEC apply generally to all electrical installations?
- Chapters 1 through 7
- Chapters 1 through 3
- Chapters 1 through 9
- Chapters 1 through 4
Answer: Chapters 1 through 4
Why: Section 90.3 says Chapters 1 through 4 apply generally. Chapters 5, 6 and 7 apply to special occupancies, special equipment and special conditions and may supplement or modify the general rules. Knowing this split tells you where to look first. (NEC 90.3)
A 22 kW, 240 V, single-phase standby generator is rated at unity power factor. What minimum ampacity must the conductors from its output terminals to the first overcurrent device have?
- 60.9 A
- 91.7 A
- 105.4 A
- 114.6 A
Answer: 105.4 A
Why: Rated current is 22,000 ÷ 240 = 91.67 A. 445.13(A) requires these conductors to be rated at least 115 % of the nameplate current: 91.67 × 1.15 = 105.42 A, about 105.4 A. (NEC 445.13(A))
A loose splice on a branch circuit has 0.05 Ω of resistance and carries 40 A. How much power is turned into heat at the splice?
- 2 W
- 80 W
- 800 W
- 1,600 W
Answer: 80 W
Why: With amps and ohms given, use P = I² × R: 40² × 0.05 = 1,600 × 0.05 = 80 W. That is a small lamp's worth of heat buried in a box. Because heat rises with the square of current, a bad termination that is fine at light load can scorch at heavy load.
A single PV string uses modules with a short-circuit current (Isc) of 9.6 A. Using the 125 % method, what is the maximum circuit current for this string? (Round to two decimals.)
- 9.60 A
- 11.04 A
- 12.00 A
- 15.00 A
Answer: 12.00 A
Why: 690.8(A)(1) sets the maximum current of a PV string at 125 % of the module Isc. The extra 25 % covers sunlight stronger than the standard test condition, such as cold, clear days with reflected light. 9.6 A × 1.25 = 12.00 A. A second 125 % is applied later, when you size conductors and overcurrent devices. (NEC 690.8(A)(1))
Resistors of 10 Ω, 20 Ω and 30 Ω are connected in series across 120 V. What is the voltage across the 30 Ω resistor?
- 20 V
- 40 V
- 60 V
- 120 V
Answer: 60 V
Why: In series the resistances add: 10 + 20 + 30 = 60 Ω, and the same current flows through each: 120 ÷ 60 = 2 A. The drop across the 30 Ω resistor is 2 A × 30 Ω = 60 V. The biggest resistor takes the biggest share, and the drops (20 + 40 + 60) add back to 120 V.
An inspector finds the neutral bonded to the enclosure in a feeder-supplied panelboard downstream of the service, in the same building. With that bond in place, where does part of the normal neutral current return to the service?
- On the EGCs, raceways, and other bonded metal
- Only into the earth through the ground rods
- Nowhere, since a bond carries only fault current
- Back through the ungrounded feeder conductors
Answer: On the EGCs, raceways, and other bonded metal
Why: The extra bond puts the feeder EGC, metal raceways, and any bonded piping in parallel with the neutral. Current divides among parallel paths, so part of the normal neutral current flows on metal that people touch. That's objectionable current under 250.6, and it's why 250.24(A)(5) and 250.142(B) prohibit the bond. (NEC 250.6(A), 250.24(A)(5), 250.142(B))
A section says a wiring method 'shall be permitted' in a certain location. Under 90.5, what does that language mean?
- The method is allowed but not required
- The method is required in that location
- The method needs special permission first
- The text is explanatory and not enforceable
Answer: The method is allowed but not required
Why: Section 90.5 sorts code text into mandatory rules ('shall', 'shall not'), permissive rules ('shall be permitted', 'shall not be required') and explanatory material. A permissive rule allows an action without demanding it, so you may use the method but are not forced to. (NEC 90.5(A), 90.5(B))
A load draws 100 kVA at a power factor of 0.8. How much real power does it use?
- 60 kW
- 80 kW
- 100 kW
- 125 kW
Answer: 80 kW
Why: Power factor is the share of apparent power that does real work: kW = kVA × PF = 100 × 0.8 = 80 kW. The remaining side of the triangle is √(100² − 80²) = 60 kVAR of reactive power.
Original practice questions written for Ohmward on the 2023 NEC — not real exam items.