North Dakota Journeyman Electrician Practice Test
20 questions in the style of the North Dakota journeyman exam (State-run (NDSEB)): NEC rules, code navigation and calculations. Pick an answer, check it, and read why — with the section to look up.
A 75 kVA, three-phase transformer is rated 480 V delta primary, 208Y/120 V secondary. What is its full-load primary current?
Given conditions
Currents rounded to two decimals; √3 taken as 1.732
Report a problem with this question
See all 20 questions with answers and explanations
A 75 kVA, three-phase transformer is rated 480 V delta primary, 208Y/120 V secondary. What is its full-load primary current?
- 90.21 A
- 156.25 A
- 208.18 A
- 270.63 A
Answer: 90.21 A
Why: Three-phase current is VA ÷ (1.732 × line volts). On the primary: 75,000 ÷ (1.732 × 480) = 75,000 ÷ 831.36 = 90.21 A.
An exam question asks for the allowable ampacity of a 4 AWG copper THWN conductor in a raceway. Where will you find the answer most directly?
- Table 250.66
- Chapter 9, Table 8
- Table 314.16(A)
- Table 310.16
Answer: Table 310.16
Why: Allowable ampacities for insulated conductors in raceway, cable or earth are in Table 310.16, in Article 310, Conductors for General Wiring. Memorize this table's location; it is the most-used table on the exam. (NEC Table 310.16)
A 75 kVA, three-phase, 480 V to 208Y/120 V transformer is protected on the primary side only. What is the largest standard primary breaker permitted by Table 450.3(B) and its notes?
- 90 A
- 100 A
- 110 A
- 125 A
Answer: 125 A
Why: Primary current is 75,000 ÷ (1.732 × 480) = 90.21 A. Primary-only protection for 9 A or more is 125 %: 90.21 × 1.25 = 112.77 A. Table 450.3(B) Note 1 permits the next higher standard size, 125 A. (NEC 450.3(B), Table 450.3(B), 240.6(A))
A metal device box with internal cable clamps has two 14/2 NM cables with ground entering it. A single-pole switch is installed, and the two bare grounds are spliced with a pigtail to the switch. What minimum box volume is required?
- 14.00 in.³
- 16.00 in.³
- 18.00 in.³
- 20.00 in.³
Answer: 16.00 in.³
Why: Count by 314.16(B) at 2.00 in.³ for 14 AWG: four insulated conductors (8.00), one allowance for all grounds (2.00), one for the clamps (2.00), and two for the switch yoke (4.00). Total 16.00 in.³. The pigtail never leaves the box, so it counts zero. (NEC 314.16(B)(1), 314.16(B)(2), 314.16(B)(4), 314.16(B)(5), Table 314.16(B))
You are pouring a 1-1/2 in. trade size sealing fitting in a Class I, Division 1 location. The fitting has no marking that calls for a different depth. What is the minimum thickness of sealing compound?
- 5/8 in.
- 3/4 in.
- 1-1/2 in.
- 2 in.
Answer: 1-1/2 in.
Why: The compound must be at least as thick as the trade size of the sealing fitting, and never less than 5/8 in. (501.15(C)(3)). For a 1-1/2 in. fitting that means at least 1-1/2 in. of compound. The 5/8 in. figure is only the floor for very small fittings. (NEC 501.15(C)(3))
A single PV string uses modules with a short-circuit current (Isc) of 9.6 A. Using the 125 % method, what is the maximum circuit current for this string? (Round to two decimals.)
- 9.60 A
- 11.04 A
- 12.00 A
- 15.00 A
Answer: 12.00 A
Why: 690.8(A)(1) sets the maximum current of a PV string at 125 % of the module Isc. The extra 25 % covers sunlight stronger than the standard test condition, such as cold, clear days with reflected light. 9.6 A × 1.25 = 12.00 A. A second 125 % is applied later, when you size conductors and overcurrent devices. (NEC 690.8(A)(1))
You need the requirements for a rooftop solar photovoltaic system (Article 690). Which chapter of the NEC contains it?
- Chapter 5
- Chapter 6
- Chapter 7
- Chapter 8
Answer: Chapter 6
Why: Chapter 6 covers special equipment, including signs, elevators, EV charging, pools (680) and solar PV (690). The first digit of the article number is the chapter: 690 is in Chapter 6. (NEC Article 690, 90.3)
A 60 A circuit breaker protects 6 AWG copper feeder conductors to a subpanel in the same building. The conductors are not upsized. What minimum size copper equipment grounding conductor is required?
- 12 AWG
- 10 AWG
- 8 AWG
- 6 AWG
Answer: 10 AWG
Why: Table 250.122 sizes the EGC from the rating of the overcurrent device ahead of the circuit. The 60 A row calls for 10 AWG copper. The size of the circuit conductors doesn't set the EGC unless they were upsized (250.122(B)). (NEC 250.122(A), Table 250.122)
A section says a wiring method 'shall be permitted' in a certain location. Under 90.5, what does that language mean?
- The method is allowed but not required
- The method is required in that location
- The method needs special permission first
- The text is explanatory and not enforceable
Answer: The method is allowed but not required
Why: Section 90.5 sorts code text into mandatory rules ('shall', 'shall not'), permissive rules ('shall be permitted', 'shall not be required') and explanatory material. A permissive rule allows an action without demanding it, so you may use the method but are not forced to. (NEC 90.5(A), 90.5(B))
A 25 ft feeder tap is taken from a feeder protected by a 300 A breaker. Under 240.21(B)(2), what is the minimum ampacity of the tap conductors?
- 30 A
- 100 A
- 150 A
- 300 A
Answer: 100 A
Why: 240.21(B)(2) requires a 25-ft tap to have an ampacity of at least one-third of the feeder overcurrent device rating: 300 ÷ 3 = 100 A. The tap must also end in a single breaker or set of fuses that limits the load to the tap's ampacity. (NEC 240.21(B)(2))
A 120 V branch circuit supplies a metal pole light in a parking lot. Which of these must not be counted on as the effective ground-fault current path for that circuit?
- The earth, through a ground rod at the pole
- An EMT raceway with listed set-screw fittings
- A copper wire-type equipment grounding conductor
- The metal armor of listed Type AC cable
Answer: The earth, through a ground rod at the pole
Why: 250.4(A)(5) says the earth is not to be considered an effective ground-fault current path. Soil resistance is far too high to let enough current flow to open the breaker. The fault path has to be an intentional, low-impedance metal path back to the source, such as EMT, a wire-type EGC, or AC cable armor, all of which 250.118 permits. (NEC 250.4(A)(5), 250.118)
Under the 2023 NEC standard method, a 2,000 ft² one-family dwelling on a 120/240 V service has 2 small-appliance circuits, 1 laundry circuit, a 12 kW range, a 5 kW dryer, four fastened-in-place appliances totaling 8,100 VA, 10 kW of fixed electric heat, and a 6 kVA air conditioner. What is the calculated load in amperes?
- 128 A
- 130 A
- 136 A
- 145 A
Answer: 145 A
Why: General load: 6,000 + 3,000 + 1,500 = 10,500 VA, reduced by Table 220.45 to 3,000 + (7,500 × 0.35) = 5,625 VA. Add the range at 8,000 VA (Table 220.55, Column C), the dryer at 5,000 VA (220.54), the appliances at 8,100 × 0.75 = 6,075 VA (220.53), and the larger of heat or AC, 10,000 VA (220.51, 220.60). Total 34,700 VA ÷ 240 V = 144.58 A, which rounds to 145 A (220.5(B)). (NEC Table 220.45, 220.51, 220.53, 220.54, Table 220.55, 220.60, 220.5(B)) Edition note: 2023 NEC numbering. In the 2026 NEC, load calculations moved from Article 220 to Article 120. The dwelling demand tiers were Table 220.42 in the 2020 NEC and are Table 220.45 in 2023.
A coil with 0.1 H of inductance is connected to a 60 Hz supply. What is its inductive reactance?
- 6.0 Ω
- 18.8 Ω
- 37.7 Ω
- 377 Ω
Answer: 37.7 Ω
Why: XL = 2πfL. At 60 Hz, 2πf = 2 × 3.1416 × 60 = 377. Then XL = 377 × 0.1 = 37.7 Ω. Inductive reactance grows with both frequency and inductance.
A resistive water heater element has a resistance of 16 Ω and is connected to 240 V. How much current does it draw?
- 0.067 A
- 7.5 A
- 15 A
- 3,840 A
Answer: 15 A
Why: Ohm's law: current equals voltage divided by resistance, I = E ÷ R. Here 240 V ÷ 16 Ω = 15 A. Think of it as push divided by opposition: more volts push more amps, more ohms hold them back.
A 480Y/277 V panelboard has exposed live parts on one side of the working space and a concrete block wall on the other. What minimum depth of working space does Table 110.26(A)(1) require?
- 3 ft
- 3½ ft
- 4 ft
- 5 ft
Answer: 3½ ft
Why: Enter the table with voltage to ground: 277 V falls in the 151–1000 V row. Concrete, brick and tile walls are considered grounded, so live parts across from a block wall is Condition 2. The minimum depth is 3½ ft (1.0 m). (NEC 110.26(A)(1), Table 110.26(A)(1))
A storage room holds gasoline in closed, sealed drums. Vapors could escape only if a drum ruptured or leaked by accident. No dispensing happens in the room. How is the room classified?
- Class I, Division 1
- Class I, Division 2
- Class II, Division 2
- Class II, Division 1
Answer: Class I, Division 2
Why: Gasoline vapor makes it Class I. The division depends on how often an ignitible mixture is expected. Liquids kept in closed containers that release vapor only through accidental rupture or breakdown fit Division 2 in 500.5(B)(2). Division 1 is for places where the mixture exists in normal operation, such as open dispensing. (NEC 500.5(B)(2))
You are sizing the branch-circuit short-circuit and ground-fault protective device for a general-purpose three-phase squirrel-cage motor. Which current do you start from?
- The nameplate full-load current
- The locked-rotor current on the nameplate
- The full-load current from Table 430.250
- The service-factor current on the nameplate
Answer: The full-load current from Table 430.250
Why: 430.6(A)(1) sends you to the FLC tables for conductor ampacity, switch ratings and the short-circuit and ground-fault device. Table values are conservative and let the circuit be designed before the exact motor arrives. The nameplate value is used for separate overload protection. (NEC 430.6(A)(1), 430.6(A)(2), Table 430.250)
A 120 V, 2-wire branch circuit of 12 AWG copper runs 100 ft (one way) to a 16 A load. Using VD = 2KIL/CM with K = 12.9 and circular mils from Chapter 9, Table 8, what is the voltage drop?
- 3.16 V
- 3.98 V
- 5.47 V
- 6.32 V
Answer: 6.32 V
Why: 12 AWG is 6,530 cmil. VD = 2 × 12.9 × 16 × 100 ÷ 6,530 = 6.32 V, which is 5.3 % of 120 V, well above the recommended 3 %. The 2 accounts for current flowing out and back. (NEC Chapter 9, Table 8)
A 25 kVA, single-phase transformer has a 480 V primary and a 240 V secondary. What is its full-load secondary current?
- 52.08 A
- 60.14 A
- 104.17 A
- 180.42 A
Answer: 104.17 A
Why: Single-phase current is VA ÷ volts, with no √3. On the 240 V side: 25,000 ÷ 240 = 104.17 A. The secondary current is twice the primary current because the voltage is half.
A feeder supplies 90 A of continuous lighting load and no other load. The breaker is not listed for 100 % operation. What is the minimum standard breaker rating?
- 90 A
- 110 A
- 125 A
- 150 A
Answer: 125 A
Why: 215.3 requires the feeder overcurrent device to be at least 125 % of the continuous load: 90 × 1.25 = 112.5 A. 112.5 A isn't a standard rating, so go up to the next standard size in 240.6(A), 125 A. (NEC 215.3, 240.6(A))
Original practice questions written for Ohmward on the 2023 NEC — not real exam items.