A 10 hp, 460 V, three-phase induction motor has a nameplate full-load current of 13 A. What minimum ampacity must its branch-circuit conductors have?
Given conditions
Continuous-duty, general-purpose induction motor
Report a problem with this question
See all 20 questions with answers and explanations
A 10 hp, 460 V, three-phase induction motor has a nameplate full-load current of 13 A. What minimum ampacity must its branch-circuit conductors have?
- 14.0 A
- 16.1 A
- 16.25 A
- 17.5 A
Answer: 17.5 A
Why: Conductor sizing starts from the table full-load current, not the nameplate (430.6(A)(1)). Table 430.250 gives 14 A for 10 hp at 460 V, and 430.22 requires conductors rated at least 125 % of that: 14 × 1.25 = 17.5 A. (NEC 430.6(A)(1), Table 430.250, 430.22)
A 20 A duplex receptacle on a single yoke is installed in a device box and connected to 12 AWG copper conductors. What volume allowance must be added to the box fill for the receptacle?
- 2.25 in.³
- 4.00 in.³
- 4.50 in.³
- 9.00 in.³
Answer: 4.50 in.³
Why: 314.16(B)(4) gives each yoke or strap holding a device a double volume allowance, based on the largest conductor connected to that device. Table 314.16(B) lists 12 AWG at 2.25 in.³, so the receptacle takes 2 × 2.25 = 4.50 in.³. It is per yoke, not per receptacle face. (NEC 314.16(B)(4), Table 314.16(B))
A 15 hp, three-phase induction motor is connected to a 208 V system and is rated 208 V. What minimum ampacity must its branch-circuit conductors have?
- 52.50 A
- 53.13 A
- 57.75 A
- 60.38 A
Answer: 57.75 A
Why: Use the 208 V column of Table 430.250, which lists 46.2 A for 15 hp. Branch-circuit conductors for one motor must be rated at least 125 % of that current (430.22): 46.2 × 1.25 = 57.75 A. (NEC Table 430.250, 430.22)
A 10 hp, 460 V, three-phase motor has a nameplate full-load current of 13 A and a service factor of 1.15. What is the maximum trip setting for a separate overload device, using the basic rule?
- 16.25 A
- 16.90 A
- 17.50 A
- 18.20 A
Answer: 16.25 A
Why: Overloads are sized from the nameplate current (430.6(A)(2)). With a service factor of 1.15 or more, 430.32(A)(1) allows up to 125 %: 13 × 1.25 = 16.25 A. (NEC 430.6(A)(2), 430.32(A)(1))
A load draws 100 kVA at a power factor of 0.8. How much real power does it use?
- 60 kW
- 80 kW
- 100 kW
- 125 kW
Answer: 80 kW
Why: Power factor is the share of apparent power that does real work: kW = kVA × PF = 100 × 0.8 = 80 kW. The remaining side of the triangle is √(100² − 80²) = 60 kVAR of reactive power.
A 75 kVA, three-phase, 480 V to 208Y/120 V transformer is protected on the primary side only. What is the largest standard primary breaker permitted by Table 450.3(B) and its notes?
- 90 A
- 100 A
- 110 A
- 125 A
Answer: 125 A
Why: Primary current is 75,000 ÷ (1.732 × 480) = 90.21 A. Primary-only protection for 9 A or more is 125 %: 90.21 × 1.25 = 112.77 A. Table 450.3(B) Note 1 permits the next higher standard size, 125 A. (NEC 450.3(B), Table 450.3(B), 240.6(A))
A receptacle reads 120 V on a true-RMS meter. What is the peak voltage of the sine wave?
- 84.9 V
- 169.7 V
- 240 V
- 339.4 V
Answer: 169.7 V
Why: Meters read RMS, the effective value. For a sine wave, peak = RMS × 1.414 (√2). So 120 × 1.414 = 169.7 V. The wave swings from +169.7 V to −169.7 V sixty times a second.
A single PV string uses modules with a short-circuit current (Isc) of 9.6 A. Using the 125 % method, what is the maximum circuit current for this string? (Round to two decimals.)
- 9.60 A
- 11.04 A
- 12.00 A
- 15.00 A
Answer: 12.00 A
Why: 690.8(A)(1) sets the maximum current of a PV string at 125 % of the module Isc. The extra 25 % covers sunlight stronger than the standard test condition, such as cold, clear days with reflected light. 9.6 A × 1.25 = 12.00 A. A second 125 % is applied later, when you size conductors and overcurrent devices. (NEC 690.8(A)(1))
A 25 kVA, single-phase transformer has a 480 V primary and a 240 V secondary. What is its full-load secondary current?
- 52.08 A
- 60.14 A
- 104.17 A
- 180.42 A
Answer: 104.17 A
Why: Single-phase current is VA ÷ volts, with no √3. On the 240 V side: 25,000 ÷ 240 = 104.17 A. The secondary current is twice the primary current because the voltage is half.
Under the 2023 NEC standard method, a 2,400 ft² dwelling has the two required small-appliance circuits and one laundry circuit. What is the net general lighting, small-appliance and laundry demand after Table 220.45?
- 4,095 VA
- 5,520 VA
- 6,045 VA
- 11,700 VA
Answer: 6,045 VA
Why: Start with 2,400 × 3 VA = 7,200 VA, then add 1,500 VA for each small-appliance and laundry circuit (220.52): 7,200 + 3,000 + 1,500 = 11,700 VA. Table 220.45 takes the first 3,000 VA at 100 % and the next portion, up to 120,000 VA, at 35 %: 3,000 + (8,700 × 0.35) = 6,045 VA. (NEC 220.41, 220.52(A), 220.52(B), Table 220.45) Edition note: 2023 NEC numbering. In the 2026 NEC, load calculations moved from Article 220 to Article 120. The dwelling demand tiers were Table 220.42 in the 2020 NEC and are Table 220.45 in 2023.
A 20 A multioutlet branch circuit supplies lighting outlets and fastened-in-place equipment. What is the maximum total rating of the fastened-in-place equipment, other than luminaires?
- 7.5 A
- 10 A
- 12 A
- 16 A
Answer: 10 A
Why: 210.23 limits the total rating of utilization equipment fastened in place, other than luminaires, to 50 % of the circuit rating when the circuit also supplies lighting or cord-and-plug equipment. 50 % of 20 A is 10 A. (NEC 210.23)
A 120 V branch circuit supplies a metal pole light in a parking lot. Which of these must not be counted on as the effective ground-fault current path for that circuit?
- The earth, through a ground rod at the pole
- An EMT raceway with listed set-screw fittings
- A copper wire-type equipment grounding conductor
- The metal armor of listed Type AC cable
Answer: The earth, through a ground rod at the pole
Why: 250.4(A)(5) says the earth is not to be considered an effective ground-fault current path. Soil resistance is far too high to let enough current flow to open the breaker. The fault path has to be an intentional, low-impedance metal path back to the source, such as EMT, a wire-type EGC, or AC cable armor, all of which 250.118 permits. (NEC 250.4(A)(5), 250.118)
A section says a wiring method 'shall be permitted' in a certain location. Under 90.5, what does that language mean?
- The method is allowed but not required
- The method is required in that location
- The method needs special permission first
- The text is explanatory and not enforceable
Answer: The method is allowed but not required
Why: Section 90.5 sorts code text into mandatory rules ('shall', 'shall not'), permissive rules ('shall be permitted', 'shall not be required') and explanatory material. A permissive rule allows an action without demanding it, so you may use the method but are not forced to. (NEC 90.5(A), 90.5(B))
An office building has an emergency system for egress lighting required by the building code. After normal power fails, within what time must the emergency system supply power?
- 10 seconds
- 30 seconds
- 60 seconds
- 90 seconds
Answer: 10 seconds
Why: 700.12 requires emergency lighting and power to be available within the time needed for the application, but no more than 10 seconds. Emergency systems protect life during evacuation, so people cannot be left in the dark for long. Legally required standby gets 60 seconds; optional standby has no time limit. (NEC 700.12)
Three 6 AWG THHN copper current-carrying conductors run through a boiler room with a 45 °C ambient. Using Table 310.15(B)(1)(1), what is the conductor's ampacity after ambient correction, before the termination check?
- 53.30 A
- 60.00 A
- 61.50 A
- 65.25 A
Answer: 65.25 A
Why: THHN is 90 °C, so start at 75 A (6 AWG copper, 90 °C column). The 41–45 °C row gives 0.87 in the 90 °C column: 75 × 0.87 = 65.25 A. The 110.14(C) termination check comes afterwards. (NEC Table 310.15(B)(1)(1), Table 310.16) Edition note: The 2023 NEC numbers the 30 °C-based correction table as Table 310.15(B)(1)(1); the 2020 edition called it Table 310.15(B)(1).
An exam question asks for the allowable ampacity of a 4 AWG copper THWN conductor in a raceway. Where will you find the answer most directly?
- Table 250.66
- Chapter 9, Table 8
- Table 314.16(A)
- Table 310.16
Answer: Table 310.16
Why: Allowable ampacities for insulated conductors in raceway, cable or earth are in Table 310.16, in Article 310, Conductors for General Wiring. Memorize this table's location; it is the most-used table on the exam. (NEC Table 310.16)
A 22 kW, 240 V, single-phase standby generator is rated at unity power factor. What minimum ampacity must the conductors from its output terminals to the first overcurrent device have?
- 60.9 A
- 91.7 A
- 105.4 A
- 114.6 A
Answer: 105.4 A
Why: Rated current is 22,000 ÷ 240 = 91.67 A. 445.13(A) requires these conductors to be rated at least 115 % of the nameplate current: 91.67 × 1.15 = 105.42 A, about 105.4 A. (NEC 445.13(A))
A textile mill has looms that throw off cotton lint and flyings, which collect on ledges and equipment. Under Article 500, how is this area classified?
- Class I, Group D
- Class II, Group G
- Class III
- Class II, Group E
Answer: Class III
Why: Class locations are sorted by what can burn. Class I is gases and vapors, Class II is combustible dust, and Class III is easily ignitible fibers and flyings such as cotton lint. Textile mills and cotton gins are the textbook Class III examples in 500.5(D). Class III has no material groups. (NEC 500.5(D))
A resistive water heater element rated 4,500 W at 240 V is connected to a 208 V circuit. If its resistance does not change, about how many watts does it produce?
- 3,380 W
- 3,900 W
- 4,500 W
- 5,192 W
Answer: 3,380 W
Why: The element's resistance is what stays fixed: R = 240² ÷ 4,500 = 12.8 Ω. At 208 V, P = 208² ÷ 12.8 = 43,264 ÷ 12.8 = 3,380 W, about 75 % of nameplate. Power follows the square of voltage, so a 13 % lower voltage costs about 25 % of the heat.
An inspector finds the neutral bonded to the enclosure in a feeder-supplied panelboard downstream of the service, in the same building. With that bond in place, where does part of the normal neutral current return to the service?
- On the EGCs, raceways, and other bonded metal
- Only into the earth through the ground rods
- Nowhere, since a bond carries only fault current
- Back through the ungrounded feeder conductors
Answer: On the EGCs, raceways, and other bonded metal
Why: The extra bond puts the feeder EGC, metal raceways, and any bonded piping in parallel with the neutral. Current divides among parallel paths, so part of the normal neutral current flows on metal that people touch. That's objectionable current under 250.6, and it's why 250.24(A)(5) and 250.142(B) prohibit the bond. (NEC 250.6(A), 250.24(A)(5), 250.142(B))