Tennessee Journeyman Electrician Practice Test

20 questions in the style of the Tennessee journeyman exam (Prov): NEC rules, code navigation and calculations. Pick an answer, check it, and read why — with the section to look up.

The real Tennessee exam: 40 questions in 2 h, open book, 2017 NEC. Full Tennessee exam guide →

Question 1 of 20Conductors & ampacity
PUT IT INTO PRACTICE

A 30 A branch circuit uses 10 AWG THHN copper. Neither the breaker nor the receptacle terminals carry any temperature marking. Which ampacity column of Table 310.16 limits this conductor?

Select your answer
Report a problem with this question

Describe the content issue. Do not include private patient or workplace information.

Pick an answer and check it.

See all 20 questions with answers and explanations
  1. A 30 A branch circuit uses 10 AWG THHN copper. Neither the breaker nor the receptacle terminals carry any temperature marking. Which ampacity column of Table 310.16 limits this conductor?

    • The 60 °C column
    • The 75 °C column
    • The 90 °C column
    • Any column, if the load is noncontinuous

    Answer: The 60 °C column

    Why: For circuits rated 100 A or less, or conductors 14 through 1 AWG, 110.14(C)(1)(a) assumes 60 °C terminations unless the equipment is listed and marked for a higher rating. 10 AWG copper is 30 A in the 60 °C column, which happens to match this 30 A circuit. (NEC 110.14(C)(1)(a), Table 310.16)

  2. A one-family dwelling has a 125 A, 120/240 V, single-phase service supplying the entire dwelling load. Using 310.12 with copper THWN-2 conductors, 75 °C terminations, and no adjustment or correction factors, what is the minimum ungrounded service-entrance conductor size?

    • 3 AWG
    • 2 AWG
    • 1 AWG
    • 1/0 AWG

    Answer: 2 AWG

    Why: 310.12 lets the conductors of a 120/240 V single-phase dwelling service be sized at 83 % of the service rating: 125 × 0.83 = 103.75 A. In the 75 °C copper column of Table 310.16, 3 AWG is 100 A (too small) and 2 AWG is 115 A. So 2 AWG copper is the minimum. (NEC 310.12, Table 310.16)

  3. A 20 A multioutlet branch circuit supplies lighting outlets and fastened-in-place equipment. What is the maximum total rating of the fastened-in-place equipment, other than luminaires?

    • 7.5 A
    • 10 A
    • 12 A
    • 16 A

    Answer: 10 A

    Why: 210.23 limits the total rating of utilization equipment fastened in place, other than luminaires, to 50 % of the circuit rating when the circuit also supplies lighting or cord-and-plug equipment. 50 % of 20 A is 10 A. (NEC 210.23)

  4. A 4,500 W water heater element runs 3 hours a day for 30 days. Electricity costs $0.15 per kWh. What is the energy cost for the month?

    • $2.03
    • $20.25
    • $60.75
    • $60,750

    Answer: $60.75

    Why: Energy is power × time, billed in kilowatt-hours. Convert to kW first: 4,500 W = 4.5 kW. Energy = 4.5 kW × 3 h × 30 days = 405 kWh. Cost = 405 × $0.15 = $60.75.

  5. An exam question asks for the allowable ampacity of a 4 AWG copper THWN conductor in a raceway. Where will you find the answer most directly?

    • Table 250.66
    • Chapter 9, Table 8
    • Table 314.16(A)
    • Table 310.16

    Answer: Table 310.16

    Why: Allowable ampacities for insulated conductors in raceway, cable or earth are in Table 310.16, in Article 310, Conductors for General Wiring. Memorize this table's location; it is the most-used table on the exam. (NEC Table 310.16)

  6. A balanced three-phase, 208 V load draws 150 A on each line. How many kVA does it draw?

    • 18.0 kVA
    • 31.2 kVA
    • 54.0 kVA
    • 93.6 kVA

    Answer: 54.0 kVA

    Why: Three-phase kVA = 1.732 × line volts × line amps ÷ 1,000 = 1.732 × 208 × 150 ÷ 1,000 = 54.04 kVA, which rounds to 54.0 kVA. The same answer comes from 3 × 120 V × 150 A per phase.

  7. A new in-ground pool is installed at a single-family home. At least one 125 V, 15 or 20 A general-purpose receptacle is required near the pool. Between what distances from the inside wall of the pool must it be located?

    • 5 ft and 10 ft
    • 5 ft and 20 ft
    • 6 ft and 10 ft
    • 6 ft and 20 ft

    Answer: 6 ft and 20 ft

    Why: 680.22(A)(1) requires at least one general-purpose receptacle at a dwelling pool so nobody runs an extension cord across the deck. It must sit no closer than 6 ft and no farther than 20 ft from the inside wall, and no higher than 6 ft 6 in. above the deck. It is also GFCI protected because it is within 20 ft. (NEC 680.22(A)(1))

  8. A 120 V, 2-wire branch circuit of 12 AWG copper runs 100 ft (one way) to a 16 A load. Using VD = 2KIL/CM with K = 12.9 and circular mils from Chapter 9, Table 8, what is the voltage drop?

    • 3.16 V
    • 3.98 V
    • 5.47 V
    • 6.32 V

    Answer: 6.32 V

    Why: 12 AWG is 6,530 cmil. VD = 2 × 12.9 × 16 × 100 ÷ 6,530 = 6.32 V, which is 5.3 % of 120 V, well above the recommended 3 %. The 2 accounts for current flowing out and back. (NEC Chapter 9, Table 8)

  9. A 120 V ungrounded conductor faults to a metal sign whose only connection to anything is a ground rod. The total path through the earth back to the utility's grounded conductor measures 25 Ω, and the circuit breaker is rated 20 A. Ignoring wire resistance, about how much fault current flows?

    • 0.21 A
    • 4.8 A
    • 20 A
    • 3,000 A

    Answer: 4.8 A

    Why: Ohm's law: I = E ÷ R = 120 V ÷ 25 Ω = 4.8 A. That's far below the breaker's 20 A rating, so the breaker never trips and the sign stays energized. This is exactly why 250.4(A)(5) says the earth can't be the effective ground-fault current path. (NEC 250.4(A)(5))

  10. A 10 hp, 460 V, three-phase motor has a nameplate full-load current of 13 A and a service factor of 1.15. What is the maximum trip setting for a separate overload device, using the basic rule?

    • 16.25 A
    • 16.90 A
    • 17.50 A
    • 18.20 A

    Answer: 16.25 A

    Why: Overloads are sized from the nameplate current (430.6(A)(2)). With a service factor of 1.15 or more, 430.32(A)(1) allows up to 125 %: 13 × 1.25 = 16.25 A. (NEC 430.6(A)(2), 430.32(A)(1))

  11. You're setting a feeder-supplied panelboard in the same building as the service. The feeder has two ungrounded conductors, a neutral, and an EGC. The panel ships with a green bonding screw for the neutral bar. What do you do with the screw?

    • Install it so the neutral bar is bonded to the can
    • Install it, but only if a ground rod is added here
    • Install it, but only if the feeder lacks an EGC
    • Leave it out and keep the neutral bar isolated

    Answer: Leave it out and keep the neutral bar isolated

    Why: Past the service disconnect, the grounded conductor may not be connected to equipment grounding (250.24(A)(5), 250.142(B)). The neutral bar stays isolated, and the EGCs land on a separate equipment grounding bar bonded to the enclosure (408.40). The only neutral-to-ground bond is the main bonding jumper at the service. (NEC 250.24(A)(5), 250.142(B), 408.40)

  12. A branch circuit supplies 36 A of continuous load and 8 A of noncontinuous load. The breaker is not listed for 100 % operation. What is the minimum standard breaker rating?

    • 40 A
    • 45 A
    • 50 A
    • 60 A

    Answer: 60 A

    Why: 210.20(A): at least 125 % of the continuous load plus 100 % of the noncontinuous load. 36 × 1.25 = 45 A, plus 8 A = 53 A. The next standard rating at or above 53 A is 60 A. (NEC 210.20(A), 240.6(A))

  13. Under the 2023 NEC standard method, what demand load is used for a single 14 kW household electric range in a one-family dwelling?

    • 8.0 kW
    • 8.8 kW
    • 10.5 kW
    • 14.0 kW

    Answer: 8.8 kW

    Why: Table 220.55 Column C gives 8 kW for one range rated not over 12 kW. Note 1 raises the Column C value by 5 % for each kW (or major fraction) above 12 kW. A 14 kW range is 2 kW over, so 8 kW × 1.10 = 8.8 kW. (NEC 220.55, Table 220.55) Edition note: 2023 NEC numbering. In the 2026 NEC, load calculations moved from Article 220 to Article 120.

  14. In a dwelling, which 120 V, 15 A receptacle requires GFCI protection under 210.8(A)?

    • A receptacle beside the bed in a bedroom
    • A receptacle in an upstairs hallway
    • A receptacle in the dining room
    • A receptacle in an unfinished basement

    Answer: A receptacle in an unfinished basement

    Why: Basements are on the 210.8(A) list of dwelling locations where 125 V through 250 V receptacles need GFCI protection. Bedrooms, hallways and dining rooms are not on the list, though they do need AFCI protection under 210.12. (NEC 210.8(A))

  15. A 25 kVA, single-phase transformer has a 480 V primary and a 240 V secondary. What is its full-load secondary current?

    • 52.08 A
    • 60.14 A
    • 104.17 A
    • 180.42 A

    Answer: 104.17 A

    Why: Single-phase current is VA ÷ volts, with no √3. On the 240 V side: 25,000 ÷ 240 = 104.17 A. The secondary current is twice the primary current because the voltage is half.

  16. Along an unbroken living room wall, what is the maximum distance from any point on the floor line to the nearest receptacle outlet?

    • 4 ft
    • 6 ft
    • 10 ft
    • 12 ft

    Answer: 6 ft

    Why: 210.52(A)(1) requires receptacles placed so that no point along the floor line of any wall space is more than 6 ft from a receptacle outlet. That allows receptacles up to 12 ft apart. (NEC 210.52(A)(1))

  17. A 480Y/277 V panelboard has exposed live parts on one side of the working space and a concrete block wall on the other. What minimum depth of working space does Table 110.26(A)(1) require?

    • 3 ft
    • 3½ ft
    • 4 ft
    • 5 ft

    Answer: 3½ ft

    Why: Enter the table with voltage to ground: 277 V falls in the 151–1000 V row. Concrete, brick and tile walls are considered grounded, so live parts across from a block wall is Condition 2. The minimum depth is 3½ ft (1.0 m). (NEC 110.26(A)(1), Table 110.26(A)(1))

  18. An office building has an emergency system for egress lighting required by the building code. After normal power fails, within what time must the emergency system supply power?

    • 10 seconds
    • 30 seconds
    • 60 seconds
    • 90 seconds

    Answer: 10 seconds

    Why: 700.12 requires emergency lighting and power to be available within the time needed for the application, but no more than 10 seconds. Emergency systems protect life during evacuation, so people cannot be left in the dark for long. Legally required standby gets 60 seconds; optional standby has no time limit. (NEC 700.12)

  19. Article 100 defines a continuous load as one where the maximum current is expected to continue for how long?

    • 30 minutes or more
    • 1 hour or more
    • 2 hours or more
    • 3 hours or more

    Answer: 3 hours or more

    Why: Article 100 defines a continuous load as a load where the maximum current is expected to continue for 3 hours or more. Store lighting, office lighting and EV charging are typical examples. (NEC Article 100 (Continuous Load))

  20. The general lighting in a retail store runs at full load from 8 a.m. to 10 p.m. every day. Under Article 100, how is this load classified?

    • Noncontinuous load
    • Intermittent duty
    • Periodic duty
    • Continuous load

    Answer: Continuous load

    Why: Article 100 defines a continuous load as one where maximum current is expected to continue for 3 hours or more. Store lighting that runs all day easily qualifies, so it gets the 125 % sizing rules for conductors and overcurrent devices. (NEC Article 100, Continuous Load)