Virginia Journeyman Electrician Practice Test
20 questions in the style of the Virginia journeyman exam (PSI): NEC rules, code navigation and calculations. Pick an answer, check it, and read why — with the section to look up.
The real Virginia exam: 70 questions in 3 h 30 min, open book, 2020 NEC. Full Virginia exam guide →
A storage room holds gasoline in closed, sealed drums. Vapors could escape only if a drum ruptured or leaked by accident. No dispensing happens in the room. How is the room classified?
Report a problem with this question
See all 20 questions with answers and explanations
A storage room holds gasoline in closed, sealed drums. Vapors could escape only if a drum ruptured or leaked by accident. No dispensing happens in the room. How is the room classified?
- Class I, Division 1
- Class I, Division 2
- Class II, Division 2
- Class II, Division 1
Answer: Class I, Division 2
Why: Gasoline vapor makes it Class I. The division depends on how often an ignitible mixture is expected. Liquids kept in closed containers that release vapor only through accidental rupture or breakdown fit Division 2 in 500.5(B)(2). Division 1 is for places where the mixture exists in normal operation, such as open dispensing. (NEC 500.5(B)(2))
A 20 A duplex receptacle on a single yoke is installed in a device box and connected to 12 AWG copper conductors. What volume allowance must be added to the box fill for the receptacle?
- 2.25 in.³
- 4.00 in.³
- 4.50 in.³
- 9.00 in.³
Answer: 4.50 in.³
Why: 314.16(B)(4) gives each yoke or strap holding a device a double volume allowance, based on the largest conductor connected to that device. Table 314.16(B) lists 12 AWG at 2.25 in.³, so the receptacle takes 2 × 2.25 = 4.50 in.³. It is per yoke, not per receptacle face. (NEC 314.16(B)(4), Table 314.16(B))
The supply frequency to a circuit rises from 50 Hz to 60 Hz. What happens to inductive reactance (XL) and capacitive reactance (XC)?
- XL rises and XC rises
- XL falls and XC rises
- XL falls and XC falls
- XL rises and XC falls
Answer: XL rises and XC falls
Why: XL = 2πfL, so it rises in step with frequency. XC = 1 ÷ (2πfC), so frequency is in the denominator and XC falls as frequency rises. Coils fight fast changes harder; capacitors pass them more easily.
Under the 2023 NEC standard method, a 2,400 ft² dwelling has the two required small-appliance circuits and one laundry circuit. What is the net general lighting, small-appliance and laundry demand after Table 220.45?
- 4,095 VA
- 5,520 VA
- 6,045 VA
- 11,700 VA
Answer: 6,045 VA
Why: Start with 2,400 × 3 VA = 7,200 VA, then add 1,500 VA for each small-appliance and laundry circuit (220.52): 7,200 + 3,000 + 1,500 = 11,700 VA. Table 220.45 takes the first 3,000 VA at 100 % and the next portion, up to 120,000 VA, at 35 %: 3,000 + (8,700 × 0.35) = 6,045 VA. (NEC 220.41, 220.52(A), 220.52(B), Table 220.45) Edition note: 2023 NEC numbering. In the 2026 NEC, load calculations moved from Article 220 to Article 120. The dwelling demand tiers were Table 220.42 in the 2020 NEC and are Table 220.45 in 2023.
Three 6 AWG THHN copper current-carrying conductors run through a boiler room with a 45 °C ambient. Using Table 310.15(B)(1)(1), what is the conductor's ampacity after ambient correction, before the termination check?
- 53.30 A
- 60.00 A
- 61.50 A
- 65.25 A
Answer: 65.25 A
Why: THHN is 90 °C, so start at 75 A (6 AWG copper, 90 °C column). The 41–45 °C row gives 0.87 in the 90 °C column: 75 × 0.87 = 65.25 A. The 110.14(C) termination check comes afterwards. (NEC Table 310.15(B)(1)(1), Table 310.16) Edition note: The 2023 NEC numbers the 30 °C-based correction table as Table 310.15(B)(1)(1); the 2020 edition called it Table 310.15(B)(1).
A coil with 0.1 H of inductance is connected to a 60 Hz supply. What is its inductive reactance?
- 6.0 Ω
- 18.8 Ω
- 37.7 Ω
- 377 Ω
Answer: 37.7 Ω
Why: XL = 2πfL. At 60 Hz, 2πf = 2 × 3.1416 × 60 = 377. Then XL = 377 × 0.1 = 37.7 Ω. Inductive reactance grows with both frequency and inductance.
A one-family dwelling has a 125 A, 120/240 V, single-phase service supplying the entire dwelling load. Using 310.12 with copper THWN-2 conductors, 75 °C terminations, and no adjustment or correction factors, what is the minimum ungrounded service-entrance conductor size?
- 3 AWG
- 2 AWG
- 1 AWG
- 1/0 AWG
Answer: 2 AWG
Why: 310.12 lets the conductors of a 120/240 V single-phase dwelling service be sized at 83 % of the service rating: 125 × 0.83 = 103.75 A. In the 75 °C copper column of Table 310.16, 3 AWG is 100 A (too small) and 2 AWG is 115 A. So 2 AWG copper is the minimum. (NEC 310.12, Table 310.16)
A resistive heater is moved from a 120 V circuit to a 240 V circuit. If its resistance stays the same, how does its power compare with before?
- One-quarter as much
- One-half as much
- Twice as much
- Four times as much
Answer: Four times as much
Why: With resistance fixed, P = E² ÷ R. Doubling E makes E² four times larger, so the heater makes four times the watts. Current doubles too (I = E ÷ R), and twice the volts times twice the amps is four times the power. That is why a 120 V heater on 240 V fails fast.
In a purely capacitive AC circuit, how does the current relate to the voltage?
- It lags the voltage by 90°
- It is in phase with the voltage
- It lags the voltage by 45°
- It leads the voltage by 90°
Answer: It leads the voltage by 90°
Why: A capacitor's current is greatest when the voltage is changing fastest, a quarter-cycle before the voltage peaks. So current leads voltage by 90°. Memory aid: ELI the ICE man. In C, I comes before E.
A 30 hp, 460 V, three-phase motor has a nameplate full-load current of 38 A. What minimum ampere rating must its disconnecting means have?
- 34.8 A
- 40.0 A
- 43.7 A
- 46.0 A
Answer: 46.0 A
Why: 430.110(A) requires the disconnect to be rated at least 115 % of the motor's full-load current, and 430.6(A)(1) says switch ratings come from the table. Table 430.250 gives 40 A: 40 × 1.15 = 46 A. (NEC 430.110(A), 430.6(A)(1), Table 430.250)
A 20 A multioutlet branch circuit supplies lighting outlets and fastened-in-place equipment. What is the maximum total rating of the fastened-in-place equipment, other than luminaires?
- 7.5 A
- 10 A
- 12 A
- 16 A
Answer: 10 A
Why: 210.23 limits the total rating of utilization equipment fastened in place, other than luminaires, to 50 % of the circuit rating when the circuit also supplies lighting or cord-and-plug equipment. 50 % of 20 A is 10 A. (NEC 210.23)
An exam question asks for the allowable ampacity of a 4 AWG copper THWN conductor in a raceway. Where will you find the answer most directly?
- Table 250.66
- Chapter 9, Table 8
- Table 314.16(A)
- Table 310.16
Answer: Table 310.16
Why: Allowable ampacities for insulated conductors in raceway, cable or earth are in Table 310.16, in Article 310, Conductors for General Wiring. Memorize this table's location; it is the most-used table on the exam. (NEC Table 310.16)
Under the 2023 NEC, a one-family dwelling has 1,800 ft² of living space (outside dimensions), a 400 ft² attached garage, and a 200 ft² open front porch. Using the standard method, what is the general lighting load before any demand factor?
- 5,400 VA
- 6,000 VA
- 6,600 VA
- 7,200 VA
Answer: 5,400 VA
Why: 220.41 assigns 3 VA per square foot to dwelling units, but 220.5(C) counts only floor area that is, or can become, living space, measured from outside dimensions. Garages, open porches, and unfinished space not adaptable for future use are left out. 1,800 ft² × 3 VA = 5,400 VA. (NEC 220.5(C), 220.41) Edition note: 2023 NEC numbering. In the 2026 NEC, load calculations moved from Article 220 to Article 120. In the 2020 NEC the 3 VA/ft² dwelling load was in 220.14(J) and floor area in 220.11.
A ceiling box with internal clamps and a luminaire stud has two 14/2 NM cables with ground entering it. The luminaire's two 18 AWG fixture wires and its grounding conductor come in from a domed canopy. What minimum box volume is required?
- 12.00 in.³
- 14.00 in.³
- 16.00 in.³
- 17.00 in.³
Answer: 14.00 in.³
Why: Four 14 AWG conductors take 8.00 in.³. Grounds, clamps and the stud each take one 2.00 in.³ allowance, adding 6.00. The fixture wires and the luminaire ground from a domed canopy may be left out (exception to 314.16(B)(1)). Total 14.00 in.³. (NEC 314.16(B)(1) Exception, 314.16(B)(3), Table 314.16(B))
A textile mill has looms that throw off cotton lint and flyings, which collect on ledges and equipment. Under Article 500, how is this area classified?
- Class I, Group D
- Class II, Group G
- Class III
- Class II, Group E
Answer: Class III
Why: Class locations are sorted by what can burn. Class I is gases and vapors, Class II is combustible dust, and Class III is easily ignitible fibers and flyings such as cotton lint. Textile mills and cotton gins are the textbook Class III examples in 500.5(D). Class III has no material groups. (NEC 500.5(D))
A 120 V branch circuit supplies a metal pole light in a parking lot. Which of these must not be counted on as the effective ground-fault current path for that circuit?
- The earth, through a ground rod at the pole
- An EMT raceway with listed set-screw fittings
- A copper wire-type equipment grounding conductor
- The metal armor of listed Type AC cable
Answer: The earth, through a ground rod at the pole
Why: 250.4(A)(5) says the earth is not to be considered an effective ground-fault current path. Soil resistance is far too high to let enough current flow to open the breaker. The fault path has to be an intentional, low-impedance metal path back to the source, such as EMT, a wire-type EGC, or AC cable armor, all of which 250.118 permits. (NEC 250.4(A)(5), 250.118)
Under the 2023 NEC optional method for a one-family dwelling (220.82), the first 10 kVA of the general load is taken at 100 %. At what percentage is the rest of the general load taken?
- 25 %
- 35 %
- 40 %
- 65 %
Answer: 40 %
Why: 220.82(B) takes the first 10 kVA of the general load at 100 % and everything above that at 40 %. Heating and air conditioning are not in that pile; they are added separately under 220.82(C). (NEC 220.82(B)) Edition note: 2023 NEC numbering. In the 2026 NEC, load calculations moved from Article 220 to Article 120.
A 4,500 W water heater element runs 3 hours a day for 30 days. Electricity costs $0.15 per kWh. What is the energy cost for the month?
- $2.03
- $20.25
- $60.75
- $60,750
Answer: $60.75
Why: Energy is power × time, billed in kilowatt-hours. Convert to kW first: 4,500 W = 4.5 kW. Energy = 4.5 kW × 3 h × 30 days = 405 kWh. Cost = 405 × $0.15 = $60.75.
A 120 V, 2-wire branch circuit of 12 AWG copper runs 100 ft (one way) to a 16 A load. Using VD = 2KIL/CM with K = 12.9 and circular mils from Chapter 9, Table 8, what is the voltage drop?
- 3.16 V
- 3.98 V
- 5.47 V
- 6.32 V
Answer: 6.32 V
Why: 12 AWG is 6,530 cmil. VD = 2 × 12.9 × 16 × 100 ÷ 6,530 = 6.32 V, which is 5.3 % of 120 V, well above the recommended 3 %. The 2 accounts for current flowing out and back. (NEC Chapter 9, Table 8)
A 480Y/277 V panelboard has exposed live parts on one side of the working space and a concrete block wall on the other. What minimum depth of working space does Table 110.26(A)(1) require?
- 3 ft
- 3½ ft
- 4 ft
- 5 ft
Answer: 3½ ft
Why: Enter the table with voltage to ground: 277 V falls in the 151–1000 V row. Concrete, brick and tile walls are considered grounded, so live parts across from a block wall is Condition 2. The minimum depth is 3½ ft (1.0 m). (NEC 110.26(A)(1), Table 110.26(A)(1))
Original practice questions written for Ohmward on the 2023 NEC — not real exam items.