Washington Journeyman Electrician Practice Test
20 questions in the style of the Washington journeyman exam (PSI): NEC rules, code navigation and calculations. Pick an answer, check it, and read why — with the section to look up.
The real Washington exam: 77 questions in 4 h, open book, 2020 NEC. Full Washington exam guide →
Resistors of 10 Ω, 20 Ω and 30 Ω are connected in series across 120 V. What is the voltage across the 30 Ω resistor?
Report a problem with this question
See all 20 questions with answers and explanations
Resistors of 10 Ω, 20 Ω and 30 Ω are connected in series across 120 V. What is the voltage across the 30 Ω resistor?
- 20 V
- 40 V
- 60 V
- 120 V
Answer: 60 V
Why: In series the resistances add: 10 + 20 + 30 = 60 Ω, and the same current flows through each: 120 ÷ 60 = 2 A. The drop across the 30 Ω resistor is 2 A × 30 Ω = 60 V. The biggest resistor takes the biggest share, and the drops (20 + 40 + 60) add back to 120 V.
A 120 V ungrounded conductor faults to a metal sign whose only connection to anything is a ground rod. The total path through the earth back to the utility's grounded conductor measures 25 Ω, and the circuit breaker is rated 20 A. Ignoring wire resistance, about how much fault current flows?
- 0.21 A
- 4.8 A
- 20 A
- 3,000 A
Answer: 4.8 A
Why: Ohm's law: I = E ÷ R = 120 V ÷ 25 Ω = 4.8 A. That's far below the breaker's 20 A rating, so the breaker never trips and the sign stays energized. This is exactly why 250.4(A)(5) says the earth can't be the effective ground-fault current path. (NEC 250.4(A)(5))
An inspector finds the neutral bonded to the enclosure in a feeder-supplied panelboard downstream of the service, in the same building. With that bond in place, where does part of the normal neutral current return to the service?
- On the EGCs, raceways, and other bonded metal
- Only into the earth through the ground rods
- Nowhere, since a bond carries only fault current
- Back through the ungrounded feeder conductors
Answer: On the EGCs, raceways, and other bonded metal
Why: The extra bond puts the feeder EGC, metal raceways, and any bonded piping in parallel with the neutral. Current divides among parallel paths, so part of the normal neutral current flows on metal that people touch. That's objectionable current under 250.6, and it's why 250.24(A)(5) and 250.142(B) prohibit the bond. (NEC 250.6(A), 250.24(A)(5), 250.142(B))
You're setting a feeder-supplied panelboard in the same building as the service. The feeder has two ungrounded conductors, a neutral, and an EGC. The panel ships with a green bonding screw for the neutral bar. What do you do with the screw?
- Install it so the neutral bar is bonded to the can
- Install it, but only if a ground rod is added here
- Install it, but only if the feeder lacks an EGC
- Leave it out and keep the neutral bar isolated
Answer: Leave it out and keep the neutral bar isolated
Why: Past the service disconnect, the grounded conductor may not be connected to equipment grounding (250.24(A)(5), 250.142(B)). The neutral bar stays isolated, and the EGCs land on a separate equipment grounding bar bonded to the enclosure (408.40). The only neutral-to-ground bond is the main bonding jumper at the service. (NEC 250.24(A)(5), 250.142(B), 408.40)
A branch circuit supplies 36 A of continuous load and 8 A of noncontinuous load. The breaker is not listed for 100 % operation. What is the minimum standard breaker rating?
- 40 A
- 45 A
- 50 A
- 60 A
Answer: 60 A
Why: 210.20(A): at least 125 % of the continuous load plus 100 % of the noncontinuous load. 36 × 1.25 = 45 A, plus 8 A = 53 A. The next standard rating at or above 53 A is 60 A. (NEC 210.20(A), 240.6(A))
A 6 AWG THWN copper conductor (75 °C terminations, no correction or adjustment) supplies a single fixed 55 A noncontinuous load on an individual branch circuit. What is the largest breaker that may protect it?
- 60 A
- 70 A
- 75 A
- 80 A
Answer: 70 A
Why: 6 AWG copper at 75 °C is 65 A, which isn't a standard rating. 240.4(B) lets you use the next higher standard rating, 70 A, because the circuit doesn't supply multiple receptacles for portable loads and the rating is under 800 A. (NEC 240.4(B), 240.6(A), Table 310.16)
A coil with 0.1 H of inductance is connected to a 60 Hz supply. What is its inductive reactance?
- 6.0 Ω
- 18.8 Ω
- 37.7 Ω
- 377 Ω
Answer: 37.7 Ω
Why: XL = 2πfL. At 60 Hz, 2πf = 2 × 3.1416 × 60 = 377. Then XL = 377 × 0.1 = 37.7 Ω. Inductive reactance grows with both frequency and inductance.
A feeder supplies 90 A of continuous lighting load and no other load. The breaker is not listed for 100 % operation. What is the minimum standard breaker rating?
- 90 A
- 110 A
- 125 A
- 150 A
Answer: 125 A
Why: 215.3 requires the feeder overcurrent device to be at least 125 % of the continuous load: 90 × 1.25 = 112.5 A. 112.5 A isn't a standard rating, so go up to the next standard size in 240.6(A), 125 A. (NEC 215.3, 240.6(A))
A 75 kVA, three-phase transformer is rated 480 V delta primary, 208Y/120 V secondary. What is its full-load primary current?
- 90.21 A
- 156.25 A
- 208.18 A
- 270.63 A
Answer: 90.21 A
Why: Three-phase current is VA ÷ (1.732 × line volts). On the primary: 75,000 ÷ (1.732 × 480) = 75,000 ÷ 831.36 = 90.21 A.
A 20 A duplex receptacle on a single yoke is installed in a device box and connected to 12 AWG copper conductors. What volume allowance must be added to the box fill for the receptacle?
- 2.25 in.³
- 4.00 in.³
- 4.50 in.³
- 9.00 in.³
Answer: 4.50 in.³
Why: 314.16(B)(4) gives each yoke or strap holding a device a double volume allowance, based on the largest conductor connected to that device. Table 314.16(B) lists 12 AWG at 2.25 in.³, so the receptacle takes 2 × 2.25 = 4.50 in.³. It is per yoke, not per receptacle face. (NEC 314.16(B)(4), Table 314.16(B))
A 30 A branch circuit uses 10 AWG THHN copper. Neither the breaker nor the receptacle terminals carry any temperature marking. Which ampacity column of Table 310.16 limits this conductor?
- The 60 °C column
- The 75 °C column
- The 90 °C column
- Any column, if the load is noncontinuous
Answer: The 60 °C column
Why: For circuits rated 100 A or less, or conductors 14 through 1 AWG, 110.14(C)(1)(a) assumes 60 °C terminations unless the equipment is listed and marked for a higher rating. 10 AWG copper is 30 A in the 60 °C column, which happens to match this 30 A circuit. (NEC 110.14(C)(1)(a), Table 310.16)
A ceiling box with internal clamps and a luminaire stud has two 14/2 NM cables with ground entering it. The luminaire's two 18 AWG fixture wires and its grounding conductor come in from a domed canopy. What minimum box volume is required?
- 12.00 in.³
- 14.00 in.³
- 16.00 in.³
- 17.00 in.³
Answer: 14.00 in.³
Why: Four 14 AWG conductors take 8.00 in.³. Grounds, clamps and the stud each take one 2.00 in.³ allowance, adding 6.00. The fixture wires and the luminaire ground from a domed canopy may be left out (exception to 314.16(B)(1)). Total 14.00 in.³. (NEC 314.16(B)(1) Exception, 314.16(B)(3), Table 314.16(B))
A one-family dwelling has a 125 A, 120/240 V, single-phase service supplying the entire dwelling load. Using 310.12 with copper THWN-2 conductors, 75 °C terminations, and no adjustment or correction factors, what is the minimum ungrounded service-entrance conductor size?
- 3 AWG
- 2 AWG
- 1 AWG
- 1/0 AWG
Answer: 2 AWG
Why: 310.12 lets the conductors of a 120/240 V single-phase dwelling service be sized at 83 % of the service rating: 125 × 0.83 = 103.75 A. In the 75 °C copper column of Table 310.16, 3 AWG is 100 A (too small) and 2 AWG is 115 A. So 2 AWG copper is the minimum. (NEC 310.12, Table 310.16)
Under the 2023 NEC optional method for a one-family dwelling (220.82), the first 10 kVA of the general load is taken at 100 %. At what percentage is the rest of the general load taken?
- 25 %
- 35 %
- 40 %
- 65 %
Answer: 40 %
Why: 220.82(B) takes the first 10 kVA of the general load at 100 % and everything above that at 40 %. Heating and air conditioning are not in that pile; they are added separately under 220.82(C). (NEC 220.82(B)) Edition note: 2023 NEC numbering. In the 2026 NEC, load calculations moved from Article 220 to Article 120.
A 20 A multioutlet branch circuit supplies lighting outlets and fastened-in-place equipment. What is the maximum total rating of the fastened-in-place equipment, other than luminaires?
- 7.5 A
- 10 A
- 12 A
- 16 A
Answer: 10 A
Why: 210.23 limits the total rating of utilization equipment fastened in place, other than luminaires, to 50 % of the circuit rating when the circuit also supplies lighting or cord-and-plug equipment. 50 % of 20 A is 10 A. (NEC 210.23)
A balanced three-phase, 208 V load draws 150 A on each line. How many kVA does it draw?
- 18.0 kVA
- 31.2 kVA
- 54.0 kVA
- 93.6 kVA
Answer: 54.0 kVA
Why: Three-phase kVA = 1.732 × line volts × line amps ÷ 1,000 = 1.732 × 208 × 150 ÷ 1,000 = 54.04 kVA, which rounds to 54.0 kVA. The same answer comes from 3 × 120 V × 150 A per phase.
A general-purpose branch circuit uses 12 AWG THHN copper with 75 °C terminations. No correction or adjustment applies, and no special exception (such as a motor circuit) is involved. What is the largest overcurrent device permitted?
- 15 A
- 20 A
- 25 A
- 30 A
Answer: 20 A
Why: Table 310.16 lists 12 AWG copper at 25 A (75 °C) and 30 A (90 °C), but 240.4(D) caps the overcurrent protection of 12 AWG copper at 20 A. The small-conductor rule wins unless a specific section such as 240.4(G) permits otherwise. (NEC 240.4(D), Table 310.16)
Under the 2023 NEC standard method, what demand load is used for a single 14 kW household electric range in a one-family dwelling?
- 8.0 kW
- 8.8 kW
- 10.5 kW
- 14.0 kW
Answer: 8.8 kW
Why: Table 220.55 Column C gives 8 kW for one range rated not over 12 kW. Note 1 raises the Column C value by 5 % for each kW (or major fraction) above 12 kW. A 14 kW range is 2 kW over, so 8 kW × 1.10 = 8.8 kW. (NEC 220.55, Table 220.55) Edition note: 2023 NEC numbering. In the 2026 NEC, load calculations moved from Article 220 to Article 120.
On a 480 V, three-phase, four-wire wye system, what voltage should you measure from any phase conductor to the neutral?
- 277 V
- 339 V
- 480 V
- 831 V
Answer: 277 V
Why: In a wye, line voltage = phase voltage × 1.732, so phase voltage = 480 ÷ 1.732 = 277 V. That's why the system is called 480Y/277 V and why 277 V lighting runs phase to neutral.
An exam question asks for the allowable ampacity of a 4 AWG copper THWN conductor in a raceway. Where will you find the answer most directly?
- Table 250.66
- Chapter 9, Table 8
- Table 314.16(A)
- Table 310.16
Answer: Table 310.16
Why: Allowable ampacities for insulated conductors in raceway, cable or earth are in Table 310.16, in Article 310, Conductors for General Wiring. Memorize this table's location; it is the most-used table on the exam. (NEC Table 310.16)
Original practice questions written for Ohmward on the 2023 NEC — not real exam items.