What calculations are on the journeyman electrician exam?

An electrician in a hi-vis vest works a calculator on a pickup tailgate beside a sketch of boxes and conduit runs, a multimeter and a coil of wire, with a commercial building under construction behind her.

The journeyman electrician exam tests a predictable set of calculations: Ohm's law and power, conductor ampacity with correction and adjustment, voltage drop, box fill, conduit fill, dwelling unit loads, motor circuits, and transformer currents. Each one pairs a short formula with a specific NEC table, so the skill is knowing which table to open and applying it in the right order.

Ohm's law and power

Ohm's law ties voltage, current, and resistance together: E = I × R. Power adds P = E × I. With those two you can find any value from any other two, and they sit underneath almost every other calculation on the exam.

Example: a 1,500 W heater on 120 V draws I = P ÷ E = 1,500 ÷ 120 = 12.5 A. Its resistance is R = E ÷ I = 120 ÷ 12.5 = 9.6 Ω.

Ampacity with correction and adjustment

Start with Table 310.16. If the ambient temperature isn't 30°C (86°F), apply a correction factor from 310.15(B). If a raceway or cable holds more than three current-carrying conductors, apply an adjustment factor from Table 310.15(C)(1). Then make sure the result doesn't exceed what the terminations allow under 110.14(C).

Example: four current-carrying 6 AWG THHN copper conductors in one conduit at an ambient of 40°C. The 90°C column of Table 310.16 gives 75 A. The correction factor for 36–40°C in the 90°C column is 0.91, and four to six conductors take 80%. So 75 × 0.91 × 0.80 = 54.6 A. That's below the 65 A in the 75°C column, so the termination limit doesn't control and the conductor's ampacity is 54.6 A.

Voltage drop

For a single-phase circuit, VD = 2 × K × I × L ÷ CM, where K is about 12.9 for copper, L is the one-way length in feet, and CM is the conductor's area in circular mils from Chapter 9, Table 8. For three-phase circuits, replace the 2 with 1.732. The NEC's recommendation of 3% for a branch circuit and 5% total appears in informational notes, so it's a design guideline rather than an enforceable rule.

Example: a 120 V branch circuit carries 16 A over 100 ft one way on 12 AWG copper (6,530 cmil). VD = 2 × 12.9 × 16 × 100 ÷ 6,530 = 6.3 V, which is about 5.3% of 120 V. To get under 3%, you'd step up to a larger conductor.

Box fill

Box fill is in 314.16. Count conductor equivalents, multiply by the volume per conductor from Table 314.16(B), and compare to the box volume from Table 314.16(A) or the volume marked on the box. Each conductor that originates outside the box counts as one. A device yoke counts as two, based on the largest conductor connected to it. Up to four equipment grounding conductors together count as one, based on the largest, and internal cable clamps together count as one.

Example: a box has two 12/2 NM cables with grounds, internal clamps, and one receptacle. That's 4 insulated conductors + 2 for the receptacle + 1 for the grounds + 1 for the clamps = 8. At 2.25 in³ per 12 AWG conductor, you need at least 8 × 2.25 = 18.0 in³.

Conduit fill

Conduit fill uses Chapter 9. Table 1 sets the maximum fill: 53% for one conductor, 31% for two, and 40% for over two. Table 4 gives the internal area of each raceway type and trade size, and Table 5 gives the area of each insulated conductor. Divide the allowable area by the conductor area. When every conductor is the same size, Annex C tables give the answer directly.

Example: how many 12 AWG THHN conductors fit in 3/4 in. EMT? Table 4 lists 0.213 in² at 40% fill, and Table 5 lists 0.0133 in² for 12 AWG THHN. 0.213 ÷ 0.0133 = 16 conductors, which matches Annex C.

Dwelling unit loads

Under the 2023 NEC, the general lighting load for a dwelling unit is 3 VA per square foot under 220.41. Add 1,500 VA for each small-appliance branch circuit (at least two) and 1,500 VA for the laundry circuit, then apply the demand factors in Table 220.45: the first 3,000 VA at 100%, 3,001 to 120,000 VA at 35%, and the rest at 25%.

Example: a 2,000 ft² house has 2,000 × 3 = 6,000 VA of lighting, plus 3,000 VA for two small-appliance circuits and 1,500 VA for laundry, for 10,500 VA. After demand: 3,000 + (7,500 × 0.35) = 5,625 VA. Fixed appliances, cooking equipment under 220.55, dryers, and heating or air conditioning are added on top of that.

Motor circuits

For most motor calculations, 430.6(A)(1) says to use the full-load current from the NEC tables, not the nameplate: Table 430.248 for single-phase and Table 430.250 for three-phase. Branch-circuit conductors for a single motor are sized at 125% of that current under 430.22. Short-circuit and ground-fault protection is sized from Table 430.52(C)(1), which allows, for example, 250% for an inverse time breaker and 175% for a dual-element time-delay fuse.

Example: a 10 hp, 460 V three-phase motor has a full-load current of 14 A in Table 430.250. Conductors must carry at least 14 × 1.25 = 17.5 A. An inverse time breaker can be up to 14 × 2.5 = 35 A, which is a standard size in 240.6(A).

Transformers

Transformer current is I = VA ÷ E for single-phase and I = VA ÷ (E × 1.732) for three-phase. Overcurrent protection for transformers rated 1,000 volts and less is in 450.3(B) and its table.

Example: a 75 kVA three-phase transformer with a 480 V primary and a 208Y/120 V secondary. Primary current is 75,000 ÷ (480 × 1.732) = 90.2 A. Secondary current is 75,000 ÷ (208 × 1.732) = 208.2 A. With primary-only protection, Table 450.3(B) allows 125% of primary current, or 112.8 A, and its notes permit the next higher standard size, 125 A.

These eight types cover the large majority of exam math. Ohmward's interactive lessons walk through each one step by step, which is the easiest way to get them routine before test day.

Check yourself

Take the free 50-question journeyman practice test — every answer explained with the NEC section to look up.

Start the free practice test →

Questions

How many calculation questions are on the journeyman exam?

It varies by state. Texas, for example, has a separately timed Calculations portion with 26 questions, 24 of them scored. Other states mix calculations into one exam; your bulletin's content outline shows the topics.

Do I use nameplate current or table current for motors?

For conductor and short-circuit protection sizing, use the table values in Tables 430.248 and 430.250, as required by 430.6(A)(1). Motor overload protection under 430.32 is based on the nameplate current.

Which column of Table 310.16 should I use?

You can start derating from the column that matches the conductor's insulation rating, but the final ampacity can't exceed the rating of the lowest-rated termination under 110.14(C).

Where is the dwelling general lighting load in the 2023 NEC?

In 220.41, at 3 VA per square foot, with the demand factors in Table 220.45. Older editions numbered these differently, and the 2026 NEC moves load calculations to Article 120.

What calculator can I use?

Most bulletins require a silent, non-programmable calculator, and some provide an on-screen one. Practice with the same type you'll use on test day.