Minnesota Journeyman Electrician Practice Test
20 questions in the style of the Minnesota journeyman exam (State-run (DLI)): NEC rules, code navigation and calculations. Pick an answer, check it, and read why — with the section to look up.
A 10 hp, 460 V, three-phase induction motor has a nameplate full-load current of 13 A. What minimum ampacity must its branch-circuit conductors have?
Given conditions
Continuous-duty, general-purpose induction motor
Report a problem with this question
See all 20 questions with answers and explanations
A 10 hp, 460 V, three-phase induction motor has a nameplate full-load current of 13 A. What minimum ampacity must its branch-circuit conductors have?
- 14.0 A
- 16.1 A
- 16.25 A
- 17.5 A
Answer: 17.5 A
Why: Conductor sizing starts from the table full-load current, not the nameplate (430.6(A)(1)). Table 430.250 gives 14 A for 10 hp at 460 V, and 430.22 requires conductors rated at least 125 % of that: 14 × 1.25 = 17.5 A. (NEC 430.6(A)(1), Table 430.250, 430.22)
Five THHN conductors will be installed in a 60 ft run of EMT between two panelboards. What maximum percentage of the EMT's cross-sectional area may the conductors fill?
- 31 %
- 40 %
- 53 %
- 60 %
Answer: 40 %
Why: Chapter 9, Table 1 allows 40 % fill when a raceway holds more than two conductors. 53 % is for one conductor, 31 % for two, and 60 % only for nipples 24 in. or shorter. A 60 ft run is a full raceway, so 40 % applies. (NEC Chapter 9, Table 1)
A 15 hp, three-phase induction motor is connected to a 208 V system and is rated 208 V. What minimum ampacity must its branch-circuit conductors have?
- 52.50 A
- 53.13 A
- 57.75 A
- 60.38 A
Answer: 57.75 A
Why: Use the 208 V column of Table 430.250, which lists 46.2 A for 15 hp. Branch-circuit conductors for one motor must be rated at least 125 % of that current (430.22): 46.2 × 1.25 = 57.75 A. (NEC Table 430.250, 430.22)
A 20 A multioutlet branch circuit supplies lighting outlets and fastened-in-place equipment. What is the maximum total rating of the fastened-in-place equipment, other than luminaires?
- 7.5 A
- 10 A
- 12 A
- 16 A
Answer: 10 A
Why: 210.23 limits the total rating of utilization equipment fastened in place, other than luminaires, to 50 % of the circuit rating when the circuit also supplies lighting or cord-and-plug equipment. 50 % of 20 A is 10 A. (NEC 210.23)
A ceiling box with internal clamps and a luminaire stud has two 14/2 NM cables with ground entering it. The luminaire's two 18 AWG fixture wires and its grounding conductor come in from a domed canopy. What minimum box volume is required?
- 12.00 in.³
- 14.00 in.³
- 16.00 in.³
- 17.00 in.³
Answer: 14.00 in.³
Why: Four 14 AWG conductors take 8.00 in.³. Grounds, clamps and the stud each take one 2.00 in.³ allowance, adding 6.00. The fixture wires and the luminaire ground from a domed canopy may be left out (exception to 314.16(B)(1)). Total 14.00 in.³. (NEC 314.16(B)(1) Exception, 314.16(B)(3), Table 314.16(B))
A 6 AWG THWN copper conductor (75 °C terminations, no correction or adjustment) supplies a single fixed 55 A noncontinuous load on an individual branch circuit. What is the largest breaker that may protect it?
- 60 A
- 70 A
- 75 A
- 80 A
Answer: 70 A
Why: 6 AWG copper at 75 °C is 65 A, which isn't a standard rating. 240.4(B) lets you use the next higher standard rating, 70 A, because the circuit doesn't supply multiple receptacles for portable loads and the rating is under 800 A. (NEC 240.4(B), 240.6(A), Table 310.16)
In a dwelling, which 120 V, 15 A receptacle requires GFCI protection under 210.8(A)?
- A receptacle beside the bed in a bedroom
- A receptacle in an upstairs hallway
- A receptacle in the dining room
- A receptacle in an unfinished basement
Answer: A receptacle in an unfinished basement
Why: Basements are on the 210.8(A) list of dwelling locations where 125 V through 250 V receptacles need GFCI protection. Bedrooms, hallways and dining rooms are not on the list, though they do need AFCI protection under 210.12. (NEC 210.8(A))
Under the 2023 NEC optional method for a one-family dwelling (220.82), the first 10 kVA of the general load is taken at 100 %. At what percentage is the rest of the general load taken?
- 25 %
- 35 %
- 40 %
- 65 %
Answer: 40 %
Why: 220.82(B) takes the first 10 kVA of the general load at 100 % and everything above that at 40 %. Heating and air conditioning are not in that pile; they are added separately under 220.82(C). (NEC 220.82(B)) Edition note: 2023 NEC numbering. In the 2026 NEC, load calculations moved from Article 220 to Article 120.
A 250 kcmil THWN-2 copper feeder lands on switchboard lugs that carry no temperature marking. There are three current-carrying conductors at a 30 °C ambient. What ampacity may be used for this conductor?
- 205 A
- 215 A
- 230 A
- 255 A
Answer: 255 A
Why: For conductors larger than 1 AWG (or circuits over 100 A), 110.14(C)(1)(b) lets you use the 75 °C column even without a marking. 250 kcmil copper is 255 A at 75 °C in Table 310.16. The 90 °C value of 290 A is not usable at these terminations. (NEC 110.14(C)(1)(b), Table 310.16)
A 10 hp, 460 V, three-phase motor has a nameplate full-load current of 13 A and a service factor of 1.15. What is the maximum trip setting for a separate overload device, using the basic rule?
- 16.25 A
- 16.90 A
- 17.50 A
- 18.20 A
Answer: 16.25 A
Why: Overloads are sized from the nameplate current (430.6(A)(2)). With a service factor of 1.15 or more, 430.32(A)(1) allows up to 125 %: 13 × 1.25 = 16.25 A. (NEC 430.6(A)(2), 430.32(A)(1))
A 120 V individual branch circuit supplies one piece of fixed equipment that draws 18 A for 8 hours at a time, and no other load. What minimum standard-size overcurrent device does 210.20(A) require?
- 15 A
- 20 A
- 25 A
- 30 A
Answer: 25 A
Why: The equipment runs 3 hours or more, so it is a continuous load. 210.20(A) requires the overcurrent device to be at least the noncontinuous load plus 125 % of the continuous load: 18 A × 1.25 = 22.5 A. The next standard size in 240.6(A) is 25 A, which is permitted because this is an individual branch circuit (210.3). (NEC 210.20(A), 240.6(A), 210.3)
A 20 A multioutlet branch circuit supplies lighting and receptacles. What is the maximum rating of one cord-and-plug-connected appliance that is not fastened in place?
- 10 A
- 12 A
- 16 A
- 20 A
Answer: 16 A
Why: 210.23 limits a single cord-and-plug-connected item not fastened in place to 80 % of the branch-circuit rating. 80 % of 20 A is 16 A. (NEC 210.23)
Which receptacle ratings are permitted on a 40 A branch circuit with more than one receptacle?
- 40 A only
- 30 A or 40 A
- 50 A only
- 40 A or 50 A
Answer: 40 A or 50 A
Why: Table 210.21(B)(3) lists the receptacle ratings for each circuit size: 15 A → 15 A; 20 A → 15 or 20 A; 30 A → 30 A; 40 A → 40 or 50 A; 50 A → 50 A. A 40 A circuit takes 40 A or 50 A receptacles. (NEC Table 210.21(B)(3))
The supply frequency to a circuit rises from 50 Hz to 60 Hz. What happens to inductive reactance (XL) and capacitive reactance (XC)?
- XL rises and XC rises
- XL falls and XC rises
- XL falls and XC falls
- XL rises and XC falls
Answer: XL rises and XC falls
Why: XL = 2πfL, so it rises in step with frequency. XC = 1 ÷ (2πfC), so frequency is in the denominator and XC falls as frequency rises. Coils fight fast changes harder; capacitors pass them more easily.
Article 100 defines a continuous load as one where the maximum current is expected to continue for how long?
- 30 minutes or more
- 1 hour or more
- 2 hours or more
- 3 hours or more
Answer: 3 hours or more
Why: Article 100 defines a continuous load as a load where the maximum current is expected to continue for 3 hours or more. Store lighting, office lighting and EV charging are typical examples. (NEC Article 100 (Continuous Load))
In which installation is the next-size-up allowance of 240.4(B) NOT permitted?
- A multioutlet receptacle branch circuit for portable loads
- A feeder with 140 A ampacity protected by a 150 A breaker
- An individual branch circuit to one fixed appliance
- A feeder with 475 A ampacity protected at 500 A
Answer: A multioutlet receptacle branch circuit for portable loads
Why: 240.4(B)(1) excludes branch circuits that supply more than one receptacle for cord-and-plug-connected portable loads. Any plug on that circuit could draw up to the breaker rating, so the breaker must not exceed the conductor ampacity. (NEC 240.4(B)(1))
You are pouring a 1-1/2 in. trade size sealing fitting in a Class I, Division 1 location. The fitting has no marking that calls for a different depth. What is the minimum thickness of sealing compound?
- 5/8 in.
- 3/4 in.
- 1-1/2 in.
- 2 in.
Answer: 1-1/2 in.
Why: The compound must be at least as thick as the trade size of the sealing fitting, and never less than 5/8 in. (501.15(C)(3)). For a 1-1/2 in. fitting that means at least 1-1/2 in. of compound. The 5/8 in. figure is only the floor for very small fittings. (NEC 501.15(C)(3))
A 75 kVA, three-phase, 480 V to 208Y/120 V transformer is protected on the primary side only. What is the largest standard primary breaker permitted by Table 450.3(B) and its notes?
- 90 A
- 100 A
- 110 A
- 125 A
Answer: 125 A
Why: Primary current is 75,000 ÷ (1.732 × 480) = 90.21 A. Primary-only protection for 9 A or more is 125 %: 90.21 × 1.25 = 112.77 A. Table 450.3(B) Note 1 permits the next higher standard size, 125 A. (NEC 450.3(B), Table 450.3(B), 240.6(A))
Under the 2023 NEC standard method, what demand load is used for a single 14 kW household electric range in a one-family dwelling?
- 8.0 kW
- 8.8 kW
- 10.5 kW
- 14.0 kW
Answer: 8.8 kW
Why: Table 220.55 Column C gives 8 kW for one range rated not over 12 kW. Note 1 raises the Column C value by 5 % for each kW (or major fraction) above 12 kW. A 14 kW range is 2 kW over, so 8 kW × 1.10 = 8.8 kW. (NEC 220.55, Table 220.55) Edition note: 2023 NEC numbering. In the 2026 NEC, load calculations moved from Article 220 to Article 120.
A 30 A branch circuit uses 10 AWG THHN copper. Neither the breaker nor the receptacle terminals carry any temperature marking. Which ampacity column of Table 310.16 limits this conductor?
- The 60 °C column
- The 75 °C column
- The 90 °C column
- Any column, if the load is noncontinuous
Answer: The 60 °C column
Why: For circuits rated 100 A or less, or conductors 14 through 1 AWG, 110.14(C)(1)(a) assumes 60 °C terminations unless the equipment is listed and marked for a higher rating. 10 AWG copper is 30 A in the 60 °C column, which happens to match this 30 A circuit. (NEC 110.14(C)(1)(a), Table 310.16)
Original practice questions written for Ohmward on the 2023 NEC — not real exam items.