Voltage Drop Formula: Single- and Three-Phase, With Examples

The voltage drop formula for a single-phase circuit is VD = 2 × K × I × L ÷ CM, and for a balanced three-phase circuit it is VD = 1.732 × K × I × L ÷ CM. K is about 12.9 for copper and 21.2 for aluminum, I is the load in amps, L is the one-way length in feet and CM is the conductor area in circular mils from NEC Chapter 9, Table 8. Divide VD by the source voltage to get the percent drop.
Key takeaways
- Single-phase: VD = 2KIL ÷ CM. Three-phase: VD = 1.732KIL ÷ CM.
- K ≈ 12.9 for copper, 21.2 for aluminum; CM comes from Chapter 9, Table 8.
- L is the one-way length. The 2 (or 1.732) already accounts for the return path.
- 3 % per branch circuit or feeder and 5 % total are informational-note recommendations, not requirements.
- To size for drop, solve for CM: CM = 2KIL ÷ allowed VD, then pick the next size up.
What is the voltage drop formula?
Every foot of wire has resistance, so current through it uses up some voltage before it reaches the load. The voltage drop calculation on the journeyman exam uses the circular-mil method, built from four inputs you can always find.
K is the approximate resistance of a one-circular-mil-foot conductor: about 12.9 Ω for copper and 21.2 Ω for aluminum. These are common approximations, not NEC table values; if an exam question gives you a different K, use theirs. CM is the conductor's area in circular mils from Chapter 9, Table 8.
- Single-phase (and two-wire DC): VD = 2 × K × I × L ÷ CM
- Three-phase, balanced: VD = 1.732 × K × I × L ÷ CM
- Percent drop = VD ÷ source voltage × 100
- Voltage at the load = source voltage − VD
| Size — excerpt of Chapter 9, Table 8 | Area (circular mils) |
|---|---|
| 14 AWG | 4,110 |
| 12 AWG | 6,530 |
| 10 AWG | 10,380 |
| 8 AWG | 16,510 |
| 6 AWG | 26,240 |
| 4 AWG | 41,740 |
| 2 AWG | 66,360 |
| 1 AWG | 83,690 |
| 1/0 AWG | 105,600 |
| 3/0 AWG | 167,800 |
Why is it 2 for single-phase and 1.732 for three-phase?
In a single-phase or two-wire circuit, current flows out on one conductor and back on the other, so the total wire length is twice the one-way distance. The 2 in the formula takes care of that. Do not also double L.
In a balanced three-phase circuit, the currents in the three phases are 120° apart, and the line-to-line drop works out to √3 (1.732) times the drop in one conductor. So you replace the 2 with 1.732. Never use both.
Worked example: single-phase voltage drop calculation
A 240 V single-phase circuit feeds a 30 A load 125 ft away on 10 AWG copper.
- Step 1 — CM for 10 AWG: 10,380.
- Step 2 — VD = 2 × 12.9 × 30 × 125 ÷ 10,380 = 9.32 V.
- Step 3 — percent: 9.32 ÷ 240 × 100 = 3.88 %.
- Step 4 — voltage at the load: 240 − 9.32 = 230.7 V.
- Result: above the 3 % recommendation. Try 8 AWG (16,510 cmil): 2 × 12.9 × 30 × 125 ÷ 16,510 = 5.86 V, or 2.44 %. 8 AWG meets 3 %.
Worked example: voltage drop formula for 3 phase
A 480 V three-phase motor feeder carries 60 A over 250 ft on 4 AWG conductors.
- Copper: VD = 1.732 × 12.9 × 60 × 250 ÷ 41,740 = 8.03 V, which is 8.03 ÷ 480 = 1.67 %. Load voltage 472 V.
- Aluminum, same size: VD = 1.732 × 21.2 × 60 × 250 ÷ 41,740 = 13.2 V, which is 2.75 %. Load voltage 466.8 V.
- Both are under 3 % here, but aluminum drops about 64 % more because its K is higher. Check ampacity separately in Table 310.16; voltage drop never replaces it.
How do you size a conductor for voltage drop?
Flip the formula to find the minimum circular mils: CM = 2 × K × I × L ÷ allowed VD (single-phase) or 1.732 × K × I × L ÷ allowed VD (three-phase). Then pick the first size in Chapter 9, Table 8 at or above that number, and compare it with the size ampacity requires. The larger size wins.
Worked example: a 208 V three-phase feeder, 80 A, 300 ft one way, copper, designed for 3 % drop.
- Step 1 — allowed VD: 208 × 0.03 = 6.24 V.
- Step 2 — CM = 1.732 × 12.9 × 80 × 300 ÷ 6.24 = 85,934 cmil.
- Step 3 — next size up in Table 8: 1 AWG is 83,690 (too small), so 1/0 AWG at 105,600.
- Check: 1/0 gives 5.08 V, or 2.44 %. 1 AWG would give 6.41 V, or 3.08 %.
- Step 4 — with terminals rated 75 °C, ampacity alone would allow 4 AWG copper (85 A) for 80 A; with 60 °C terminals (the 110.14(C)(1) default at 100 A or less) it would take 3 AWG. Either way voltage drop controls: 1/0 AWG copper.
- In aluminum, the same run needs 3/0 AWG (5.25 V, 2.52 %); 2/0 aluminum gives 3.18 %.
Is 3 % voltage drop an NEC requirement?
Not for ordinary branch circuits and feeders. The 2023 NEC places the recommendation in informational notes: one under 210.19 for branch circuits and one under 215.2 for feeders. They suggest sizing to keep the drop at 3 % or less on a branch circuit or feeder, and 5 % or less in total to the farthest outlet.
Informational notes explain; they are not enforceable requirements (90.5(C)). Engineers, specifications and exam questions still use these numbers all the time, so learn them. A few articles do set enforceable limits for special equipment, such as fire pumps in 695.7, so read the question for the type of equipment.
Note that the voltage drop guidance stays in the informational notes, so its exact note number can shift between code editions. Look up Voltage drop in your code book's index to find it fast.
What mistakes ruin a voltage drop calculation?
- Doubling L and also using 2. The 2 is the return path.
- Using 2 on a three-phase question, or 1.732 on a single-phase one.
- Taking CM from the wrong table. Circular mils are in Chapter 9, Table 8, not Table 5.
- Dividing VD by the load voltage instead of the source voltage for the percent.
- Stopping at voltage drop. The conductor still has to meet ampacity, terminal and 240.4(D) limits.
Practice voltage drop questions
Voltage drop is a favorite calculation question. Work exam-style problems with every step explained.
Take the free practice test →Questions
What is K in the voltage drop formula?
K is the approximate resistance of a conductor one circular mil in area and one foot long. Use about 12.9 for copper and 21.2 for aluminum unless the question gives you a value.
Do I use one-way or round-trip length?
One-way. The 2 in the single-phase formula, or the 1.732 in the three-phase formula, already accounts for the conductors carrying current back.
Does the voltage drop formula work for DC?
Yes. A two-wire DC circuit uses the same single-phase form, VD = 2 × K × I × L ÷ CM, because current flows out and back on two conductors.
How do I calculate percent voltage drop?
Divide the voltage drop by the source voltage and multiply by 100. For example, 9.32 V on a 240 V circuit is 3.88 %.
Where are circular mils in the NEC?
In Chapter 9, Table 8 (conductor properties), which lists the area of each size in circular mils along with DC resistance.
Sources
- NFPA 70, National Electrical Code (2023 edition) — official NFPA page ↗ — Informational notes to 210.19 and 215.2; 90.5(C); 695.7; Chapter 9, Table 8; Table 310.16 (2023 edition)
Updated 2026-11-27. Section references are to the 2023 NEC. Ohmward is independent exam preparation, not affiliated with NFPA, any licensing board or testing company. NEC® is a registered trademark of the NFPA.