Ampacity Chart for Copper Wire: NEC Table 310.16 Explained

The NEC ampacity chart for copper wire is Table 310.16. It lists how many amps each size can carry in its 60 °C, 75 °C and 90 °C insulation columns, assuming a 30 °C (86 °F) ambient and no more than three current-carrying conductors together. For example, 10 AWG copper is 30 A, 35 A and 40 A in those columns, but the terminals (110.14(C)), the small-conductor limits (240.4(D)) and any derating decide what you can actually use.
Key takeaways
- Table 310.16 assumes 30 °C ambient and no more than three current-carrying conductors.
- The insulation picks the starting column; the terminal rating caps the answer (110.14(C)).
- 14, 12 and 10 AWG copper are limited to 15, 20 and 30 A overcurrent protection (240.4(D)).
- Hot locations take a correction factor; more than three current-carrying conductors take an adjustment factor.
- Apply both factors to the insulation column, then compare with the terminal column and use the smaller.
What does the ampacity chart for copper wire show?
Ampacity is the current a conductor can carry continuously without exceeding its insulation temperature rating. Table 310.16 gives allowable ampacities for insulated conductors in a raceway, cable or directly buried, with copper on the left half and aluminum on the right.
Each half has three columns. 60 °C covers insulation like TW, 75 °C covers THW and THWN, and 90 °C covers THHN, THWN-2 and XHHW-2. The same size carries more current in a higher column because its insulation tolerates more heat.
The excerpt below shows the copper columns for the sizes you see most on the job and on the exam.
| Copper size — excerpt | 60 °C (A) | 75 °C (A) | 90 °C (A) |
|---|---|---|---|
| 14 AWG | 15 | 20 | 25 |
| 12 AWG | 20 | 25 | 30 |
| 10 AWG | 30 | 35 | 40 |
| 8 AWG | 40 | 50 | 55 |
| 6 AWG | 55 | 65 | 75 |
| 4 AWG | 70 | 85 | 95 |
| 3 AWG | 85 | 100 | 115 |
| 2 AWG | 95 | 115 | 130 |
| 1 AWG | 110 | 130 | 145 |
| 1/0 AWG | 125 | 150 | 170 |
Which ampacity column do you use?
Start with the conductor's insulation, but finish at the terminal. Under 110.14(C)(1), circuits rated 100 A or less, or using 14 through 1 AWG conductors, are limited to the 60 °C column unless the equipment is listed and marked for 75 °C. Circuits over 100 A, or conductors larger than 1 AWG, use the 75 °C column.
Worked example: a 50 A noncontinuous load on THHN copper, three conductors, 30 °C. With unmarked terminals, the 60 °C column applies: 8 AWG is only 40 A, so you need 6 AWG at 55 A. With terminals marked 75 °C, 8 AWG at 50 A carries the load, so 8 AWG works.
Continuous loads add one more step before the table: the conductor must carry 125 % of the continuous load (210.19(A) for branch circuits, 215.2(A) for feeders).
Why can't 12 AWG copper go on a 30 A breaker?
The 90 °C column shows 12 AWG copper at 30 A, and that tempts a lot of candidates. But 240.4(D) limits overcurrent protection for small conductors: 14 AWG copper to 15 A, 12 AWG copper to 20 A and 10 AWG copper to 30 A, unless a specific exception applies (motor circuits and some other loads have their own rules).
So the 90 °C value for small wire is useful only as a starting point for derating. The breaker size stays capped.
How do correction and adjustment factors change ampacity?
If the ambient temperature is above 30 °C, multiply by a correction factor from Table 310.15(B)(1)(1), read in the same temperature column you started from. If a raceway or cable holds more than three current-carrying conductors, multiply by an adjustment factor from Table 310.15(C)(1). Equipment grounding conductors never count, and a neutral that carries only the unbalanced current of its own circuit usually doesn't (310.15(E) and (F)).
Adjustment factors by number of current-carrying conductors: 4–6 → 80 %, 7–9 → 70 %, 10–20 → 50 %, 21–30 → 45 %, 31–40 → 40 %, 41 and up → 35 %.
| Ambient °C — excerpt | 60 °C col. | 75 °C col. | 90 °C col. |
|---|---|---|---|
| 31–35 | 0.91 | 0.94 | 0.96 |
| 36–40 | 0.82 | 0.88 | 0.91 |
| 41–45 | 0.71 | 0.82 | 0.87 |
| 46–50 | 0.58 | 0.75 | 0.82 |
Worked example: seven 8 AWG THHN conductors at 45 °C
A raceway in a hot mechanical room holds seven current-carrying 8 AWG THHN copper conductors. Ambient is 45 °C and the terminals are rated 75 °C.
- Step 1 — start in the 90 °C column: 8 AWG copper = 55 A.
- Step 2 — correction for 41–45 °C, 90 °C column: 0.87.
- Step 3 — adjustment for 7–9 conductors: 0.70.
- Step 4 — 55 × 0.87 × 0.70 = 33.495, about 33.5 A.
- Step 5 — terminal check: 8 AWG in the 75 °C column = 50 A. Use the smaller value.
- Answer: about 33.5 A. The derating, not the lug, controls here.
Worked example: sizing wire for a 40 A load with derating
You need to carry 40 A with six current-carrying THHN copper conductors in one raceway, at 40 °C, landing on 75 °C terminals. Try sizes from small to large.
- 10 AWG: 40 A (90 °C) × 0.91 × 0.80 = 29.12 A. Too small.
- 8 AWG: 55 A (90 °C) × 0.91 × 0.80 = 40.04 A. Carries the load.
- Terminal check: 8 AWG at 75 °C = 50 A, also at least 40 A.
- Answer: 8 AWG copper.
What ampacity mistakes cost points on the exam?
Most wrong answers on ampacity questions come from a handful of slips, not from hard math. Run through this list before you lock in an answer.
- Mixing columns: starting at 90 °C but reading the 75 °C correction factor. Keep one column through the multiplication.
- Skipping the terminal check: a derated value can still be higher than the 60 °C or 75 °C value, and then the terminal value wins.
- Counting the equipment grounding conductor as current-carrying. It never counts for adjustment.
- Forgetting that the adjustment factor depends on the total count in the raceway, not the count per circuit.
- Using the 90 °C value of 12 AWG copper to justify a 30 A breaker. 240.4(D) still caps it at 20 A.
How do you read Table 310.16 fast on exam day?
- Tab the page; copper is on the left, aluminum on the right.
- Circle the insulation type in the question first: that is your starting column.
- Check the terminal rating, or apply the 60 °C / 75 °C defaults from 110.14(C)(1).
- Look for heat and bundling words: rooftop, boiler room, attic, more than three conductors.
- For 14–10 AWG, check the 240.4(D) caps before you pick the breaker.
Test your ampacity skills
Ampacity and derating questions appear on every journeyman exam. Practice them with the NEC reference shown for each answer.
Take the free practice test →Questions
What is the ampacity of 10 AWG copper wire?
Table 310.16 lists 30 A at 60 °C, 35 A at 75 °C and 40 A at 90 °C. Its overcurrent protection is limited to 30 A by 240.4(D) unless an exception applies.
What size copper wire for 200 amps?
With 75 °C terminations and no derating, 3/0 AWG copper (200 A in the 75 °C column of Table 310.16). Dwelling services and feeders can use 310.12 instead, so check which rule the question is about.
What ambient temperature is Table 310.16 based on?
30 °C (86 °F). At higher ambient temperatures you apply a correction factor from Table 310.15(B)(1)(1).
Can I use the 90 °C column for THHN?
Only as the starting point for correction and adjustment. The final ampacity cannot exceed the column that matches the lowest-rated termination, usually 60 °C or 75 °C.
Does the ground wire count as a current-carrying conductor?
No. Equipment grounding and bonding conductors are never counted for adjustment factors, though they do count in conduit fill.
Sources
- NFPA 70, National Electrical Code (2023 edition) — official NFPA page ↗ — Table 310.16; 310.15(B), Table 310.15(B)(1)(1); 310.15(C), Table 310.15(C)(1); 310.15(E), (F); 110.14(C); 240.4(D); 210.19(A); 215.2(A); 310.12 (2023 edition)
Updated 2026-11-27. Section references are to the 2023 NEC. Ohmward is independent exam preparation, not affiliated with NFPA, any licensing board or testing company. NEC® is a registered trademark of the NFPA.