NEC Motor Calculations: FLC, Conductors, Breakers, Overloads

NEC motor calculations start with the full-load current (FLC) from Table 430.248 (single-phase) or Table 430.250 (three-phase), not the nameplate, as 430.6(A)(1) requires. Branch-circuit conductors are sized at 125 % of that FLC (430.22), the breaker or fuse at the Table 430.52(C)(1) percentage (250 % for an inverse time breaker, 175 % for a dual-element fuse), and overloads at 115 % or 125 % of the nameplate current (430.32).
Key takeaways
- Use table FLC (Tables 430.248 and 430.250) for conductors, short-circuit protection and feeders; use nameplate FLA for overloads.
- Branch-circuit conductors: at least 125 % of table FLC (430.22).
- Short-circuit and ground-fault protection: Table 430.52(C)(1) — inverse time breaker 250 %, dual-element fuse 175 %, nontime-delay fuse 300 %, instantaneous trip 800 %.
- If that result isn't a standard size, you may go up to the next standard rating in 240.6(A).
- Overloads: 125 % of nameplate for service factor 1.15 or more or a 40 °C rise, 115 % for all others (430.32(A)(1)).
- Several motors on one feeder: 125 % of the largest FLC plus 100 % of the others (430.24).
Why do NEC motor calculations use table current, not nameplate?
A replacement motor may draw more current than the one it replaces. To keep wiring safe when motors get swapped, 430.6(A)(1) says to size conductors, short-circuit and ground-fault protection, and disconnects from the FLC in the NEC tables, based on horsepower and voltage. The nameplate current is used for overload protection, because overloads must match the actual motor.
This is the single most tested motor rule. If a question gives you both a nameplate amp rating and a horsepower, it is testing whether you know which one goes where.
NEC motor amps chart: single-phase FLC (Table 430.248)
Common values from Table 430.248 for single-phase AC motors. Read across from horsepower to the voltage column.
| HP | 115 V | 208 V | 230 V |
|---|---|---|---|
| 1/2 | 9.8 A | 5.4 A | 4.9 A |
| 3/4 | 13.8 A | 7.6 A | 6.9 A |
| 1 | 16 A | 8.8 A | 8 A |
| 1-1/2 | 20 A | 11 A | 10 A |
| 2 | 24 A | 13.2 A | 12 A |
| 3 | 34 A | 18.7 A | 17 A |
| 5 | 56 A | 30.8 A | 28 A |
| 7-1/2 | 80 A | 44 A | 40 A |
| 10 | 100 A | 55 A | 50 A |
| Excerpt — see NEC Table 430.248 for all sizes and voltages |
NEC motor HP chart: three-phase FLC (Table 430.250)
Common values from Table 430.250 for three-phase induction (squirrel-cage) motors.
| HP | 208 V | 230 V | 460 V |
|---|---|---|---|
| 1 | 4.6 A | 4.2 A | 2.1 A |
| 3 | 10.6 A | 9.6 A | 4.8 A |
| 5 | 16.7 A | 15.2 A | 7.6 A |
| 7-1/2 | 24.2 A | 22 A | 11 A |
| 10 | 30.8 A | 28 A | 14 A |
| 15 | 46.2 A | 42 A | 21 A |
| 25 | 74.8 A | 68 A | 34 A |
| 50 | 143 A | 130 A | 65 A |
| 100 | 273 A | 248 A | 124 A |
| Excerpt — see NEC Table 430.250 for all sizes and voltages |
How do you size motor branch-circuit conductors?
For a single motor, the branch-circuit conductors must have an ampacity of at least 125 % of the table FLC (430.22). The extra 25 % covers the heat from running near full load for long periods.
After you have the minimum ampacity, pick the conductor from Table 310.16, using the column that matches your terminations. The examples below assume copper conductors and 75 °C terminations at 30 °C ambient with no more than three current-carrying conductors.
How do you size the motor breaker or fuse?
Short-circuit and ground-fault protection is sized from Table 430.52(C)(1). Multiply the table FLC by the percentage for the protective device type. For single-phase motors and squirrel-cage motors other than Design B energy-efficient, the percentages are:
- If the result is not a standard size, 430.52(C)(1) Exception No. 1 lets you use the next higher standard rating from 240.6(A).
- Standard ratings in that range include 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125 and 150 A.
- Overload protection is a separate device (usually the heaters or electronic overload in the starter). The breaker protects against short circuits and ground faults, not overloads.
| Protective device | Maximum % of FLC |
|---|---|
| Nontime-delay fuse | 300 % |
| Dual-element (time-delay) fuse | 175 % |
| Instantaneous trip breaker | 800 % |
| Inverse time breaker | 250 % |
| Excerpt — see NEC Table 430.52(C)(1) for other motor types | — |
How are motor overloads sized?
Overloads protect the motor from running too hot. Under 430.32(A)(1), size them from the nameplate full-load current: 125 % for a motor with a marked service factor of 1.15 or more, or a marked temperature rise of 40 °C or less, and 115 % for all other motors.
If that setting won't let the motor start, 430.32(C) allows a higher setting within limits. Exam questions almost always ask for the basic 115 % or 125 % value.
Worked NEC motor calculation examples
Example 1 — single-phase motor. A 7-1/2 hp, 230 V single-phase motor has a nameplate current of 38 A and a service factor of 1.15. Table 430.248 FLC = 40 A. Conductors: 40 × 1.25 = 50 A, so 8 AWG copper (50 A in the 75 °C column) works. Inverse time breaker: 40 × 250 % = 100 A, a standard size. Dual-element fuse: 40 × 175 % = 70 A, a standard size. Nontime-delay fuse: 40 × 300 % = 120 A, so the next standard size up is 125 A. Overloads: service factor 1.15 → 125 % × 38 A nameplate = 47.5 A.
Example 2 — three-phase motor. A 25 hp, 460 V three-phase squirrel-cage motor has a nameplate current of 32 A and a service factor of 1.0. Table 430.250 FLC = 34 A. Conductors: 34 × 1.25 = 42.5 A, so 8 AWG copper (50 A at 75 °C). Inverse time breaker: 34 × 250 % = 85 A, not a standard size, so the next standard size up is 90 A. Dual-element fuse: 34 × 175 % = 59.5 A, round up to 60 A. Overloads: service factor 1.0 → 115 % × 32 A = 36.8 A.
Example 3 — several motors on one feeder (motor load calculation). A 208 V three-phase feeder supplies a 10 hp, a 5 hp and a 3 hp motor. Table 430.250 FLCs: 30.8 A, 16.7 A and 10.6 A. Under 430.24, take 125 % of the largest plus 100 % of the rest: (30.8 × 1.25) + 16.7 + 10.6 = 38.5 + 27.3 = 65.8 A. 6 AWG copper is only 65 A at 75 °C, so the feeder needs 4 AWG copper (85 A). The feeder breaker is a separate step under 430.62, based on the largest branch-circuit device plus the other motors' FLCs.
What are the most common motor calculation mistakes?
For quick formulas you can keep in your head, the formula sheet lists the motor rules alongside Ohm's law and three-phase power.
- Using nameplate current to size conductors or the breaker. Use the table.
- Using table current to size overloads. Use the nameplate.
- Applying 125 % to every motor on a feeder. Only the largest gets 125 % under 430.24.
- Rounding an overload setting up to a standard breaker size. Overloads are set to the calculated value, not to 240.6(A) ratings.
- Using the 230 V column for a 208 V motor. Tables 430.248 and 430.250 have separate 200 V and 208 V columns.
Put the motor rules to work
Motor questions mix tables, percentages and rounding rules. Practice them timed in the free journeyman practice test.
Take the free practice test →Questions
Do you use nameplate or table FLC for motor calculations?
Use the table FLC from Tables 430.248 and 430.250 for conductors, short-circuit and ground-fault protection and feeders (430.6(A)(1)). Use the nameplate current for overload protection (430.32).
What size breaker do I need for a motor?
Multiply the table FLC by 250 % for an inverse time breaker (Table 430.52(C)(1)). If the result isn't a standard size, you may use the next higher standard rating in 240.6(A).
Why are motor conductors sized at 125 %?
430.22 requires branch-circuit conductors for a single continuous-duty motor to have an ampacity of at least 125 % of the motor's table full-load current.
How do you calculate the load for several motors?
Under 430.24, add 125 % of the largest motor's table FLC to 100 % of the FLCs of all the other motors, plus any other loads on the feeder.
What is the difference between 115 % and 125 % overload sizing?
Motors with a service factor of 1.15 or more, or a marked temperature rise of 40 °C or less, get 125 % of nameplate current. All other motors get 115 % (430.32(A)(1)).
Sources
- NFPA 70, National Electrical Code — code development page ↗ — official NEC edition information; section numbers are from NFPA 70-2023
- NFPA free access to codes and standards ↗ — where to read Article 430 at no cost