JOURNEYMAN EXAM GUIDE · 10 MIN READ · UPDATED 2026-11-27

Journeyman Electrician Exam Questions and Answers (2023 NEC)

Two electricians on a lunch break sit on buckets by a gang box, one holding up a phone quiz with colored answer buttons while the other thinks, a tabbed code book between them.

Below are 10 original journeyman electrician exam questions and answers, each with a short explanation and the 2023 NEC section to look up. They cover the topics that show up on most state exams: ampacity, temperature correction, continuous loads, box fill, grounding, motors, voltage drop and dwelling load calculations. For a full timed set, take the free 50-question practice test.

Key takeaways

  • Most exam questions are either NEC lookups or code-based calculations.
  • Every answer below names the 2023 NEC section or table where you can confirm it.
  • The most common traps: using the nameplate instead of the motor table, the 90 °C column instead of the terminal rating, and forgetting clamps or device yokes in box fill.
  • Practice with your book open and a timer running, the way the real exam works in most states.
  • Check which NEC edition your state tests on; section numbers move between editions.

What kinds of questions are on the journeyman electrician exam?

Journeyman electrician exam questions fall into two groups: code lookups, where you find a rule in the NEC, and calculations, where you pull a value from an NEC table and do the math. Texas makes the split explicit with a 59-question NEC Knowledge portion and a 26-question Calculations portion, each timed separately. Michigan's bulletin lists topics such as grounding and bonding, overcurrent protection, wiring methods, services, motors, load calculations and box and raceway fill.

The 10 questions below are written in that style. They are our own questions, not copied from any real exam, and each has one correct answer. Conductors are copper unless stated, and all references are to the 2023 NEC.

How should you use these practice questions?

Cover the answer, set a timer for about two and a half minutes per question, and work each one with your code book open. Write down the section you used before you check. If you got the right answer from the wrong table, count it as a miss: on the real exam that habit will cost you on the next question.

Questions 1–3: conductors, correction and continuous loads

Question 1 (ampacity). A 72 A noncontinuous load is fed by three THHN copper conductors in EMT at 30 °C. The breaker and equipment terminals are rated 75 °C. What is the smallest conductor you may use? (A) 6 AWG (B) 4 AWG (C) 3 AWG (D) 2 AWG

Answer: (B) 4 AWG. THHN is a 90 °C wire, but the 75 °C terminals limit you to the 75 °C column. In that copper column 6 AWG is 65 A, which is too small, and 4 AWG is 85 A, which covers 72 A. Look it up: NEC 110.14(C)(1)(a) and Table 310.16.

Question 2 (temperature correction). Three 6 AWG THHN copper current-carrying conductors pass through a boiler room where the ambient is 45 °C. What is their ampacity after the ambient correction, before you check terminations? (A) 53.30 A (B) 60.00 A (C) 61.50 A (D) 65.25 A

Answer: (D) 65.25 A. Start in the 90 °C column, where 6 AWG copper is 75 A. The correction factor for 41–45 °C in that column is 0.87, so 75 × 0.87 = 65.25 A. Look it up: Table 310.15(B)(1)(1) and Table 310.16. The 2020 NEC numbered the correction table 310.15(B)(1).

Question 3 (continuous load). An individual 120 V branch circuit feeds one piece of fixed equipment that runs at 18 A for 8 hours at a stretch. What is the smallest standard overcurrent device allowed? (A) 15 A (B) 20 A (C) 25 A (D) 30 A

Answer: (C) 25 A. Three hours or more makes it a continuous load, so the device must be at least 125% of it: 18 × 1.25 = 22.5 A. The next standard size up is 25 A. Look it up: NEC 210.20(A) and 240.6(A), assuming a breaker not listed for 100% operation.

Questions 4–6: box fill and grounding

Question 4 (box fill). A metal device box with internal cable clamps has two 14/2 NM cables with ground. It holds a single-pole switch, and the two bare grounds are spliced to a pigtail for the switch. What is the minimum box volume? (A) 14.00 in.³ (B) 16.00 in.³ (C) 18.00 in.³ (D) 20.00 in.³

Answer: (B) 16.00 in.³. Each 14 AWG allowance is 2.00 in.³. Count four insulated conductors (8.00), one allowance for all the grounds (2.00), one for the clamps (2.00) and two for the switch yoke (4.00): 16.00 in.³. The pigtail stays in the box, so it counts zero. Look it up: NEC 314.16(B) and Table 314.16(B).

Question 5 (grounding electrode conductor). A 200 A service has 3/0 AWG copper service-entrance conductors. What is the minimum copper grounding electrode conductor to the metal underground water pipe? (A) 8 AWG (B) 6 AWG (C) 4 AWG (D) 2 AWG

Answer: (C) 4 AWG. The GEC is sized from the largest ungrounded service-entrance conductor, and 3/0 copper falls in the row that calls for 4 AWG copper. A water pipe is not a rod, plate, concrete-encased electrode or ground ring, so the smaller limits for those electrodes don't apply. Look it up: NEC 250.66 and Table 250.66.

Question 6 (equipment grounding conductor). A 60 A breaker protects 6 AWG copper feeder conductors to a subpanel in the same building. The conductors are not upsized. What is the minimum copper EGC? (A) 12 AWG (B) 10 AWG (C) 8 AWG (D) 6 AWG

Answer: (B) 10 AWG. The EGC is sized from the rating of the overcurrent device, not the circuit conductors, and the 60 A row calls for 10 AWG copper. The conductor size only matters if the ungrounded wires were upsized. Look it up: NEC 250.122(A) and Table 250.122.

4 wires 4 x 2.00Grounds 1 x 2.00Clamps 1 x 2.00Switch 2 x 2.0016.00 in.³

Questions 7–8: motor calculations

Question 7 (motor conductors). A 10 hp, 460 V, three-phase induction motor has 13 A on its nameplate. What is the minimum ampacity for its branch-circuit conductors? (A) 14.0 A (B) 16.1 A (C) 16.25 A (D) 17.5 A

Answer: (D) 17.5 A. Size motor conductors from the table full-load current, not the nameplate. Table 430.250 lists 14 A for 10 hp at 460 V, and the conductors must be rated at least 125% of that: 14 × 1.25 = 17.5 A. Look it up: NEC 430.6(A)(1), Table 430.250 and 430.22.

Question 8 (motor short-circuit protection). A 25 hp, 460 V, three-phase squirrel-cage motor (not Design B energy-efficient) is protected by an inverse time breaker. What is the largest standard breaker allowed without the higher exception limits? (A) 60 A (B) 80 A (C) 90 A (D) 110 A

Answer: (C) 90 A. Table 430.250 gives 34 A. An inverse time breaker may be 250% of that: 34 × 2.5 = 85 A. Since 85 A is not a standard size, the exception lets you go to the next standard size up, 90 A. Look it up: Table 430.250, Table 430.52(C)(1), 430.52(C)(1) Exception No. 1 and 240.6(A).

Questions 9–10: voltage drop and dwelling load

Question 9 (voltage drop). A 240 V single-phase circuit of 8 AWG copper feeds a 40 A load 150 ft (one way) from the panel. Using K = 12.9, what is the percent voltage drop? (A) 1.95% (B) 3.91% (C) 6.42% (D) 7.81%

Answer: (B) 3.91%. 8 AWG is 16,510 circular mils. VD = 2 × 12.9 × 40 × 150 ÷ 16,510 = 9.38 V, and 9.38 ÷ 240 = 3.91%. That is above the 3% branch-circuit recommendation in the informational note, so in the field you would usually upsize. Look it up: Chapter 9, Table 8 and the informational note in 210.19.

Question 10 (dwelling load). Using the 2023 NEC standard method, a 2,400 ft² house has the two required small-appliance circuits and one laundry circuit. What is the net general lighting, small-appliance and laundry demand? (A) 4,095 VA (B) 5,520 VA (C) 6,045 VA (D) 11,700 VA

Answer: (C) 6,045 VA. 2,400 × 3 VA = 7,200 VA, plus 1,500 VA for each of the three circuits = 11,700 VA. The first 3,000 VA counts at 100% and the remaining 8,700 VA at 35% (3,045 VA): 3,000 + 3,045 = 6,045 VA. Look it up: NEC 220.41, 220.52(A) and (B), and Table 220.45 (Table 220.42 in the 2020 NEC; load calculations move to Article 120 in the 2026 NEC).

Answer key: where to look in the 2023 NEC

Use this key to check your work and to practice going straight to the right table.

#TopicAnswer2023 NEC reference
1Ampacity with 75 °C terminals4 AWG110.14(C)(1)(a); Table 310.16
2Ambient temperature correction65.25 ATable 310.15(B)(1)(1); Table 310.16
3Continuous load OCPD25 A210.20(A); 240.6(A)
4Box fill16.00 in.³314.16(B); Table 314.16(B)
5Grounding electrode conductor4 AWG250.66; Table 250.66
6Equipment grounding conductor10 AWG250.122(A); Table 250.122
7Motor branch-circuit conductors17.5 A430.6(A)(1); Table 430.250; 430.22
8Motor inverse time breaker90 ATable 430.52(C)(1); 240.6(A)
9Voltage drop3.91%Chapter 9, Table 8; 210.19
10Dwelling lighting demand6,045 VA220.41; 220.52; Table 220.45

What mistakes do the wrong answers catch?

Exam writers build wrong choices from predictable slips. Knowing them is half the battle.

If you picked 16.25 A on Question 7, you used the 13 A nameplate instead of the table value. If you picked 14.00 in.³ on Question 4, you gave the switch one allowance instead of two. On Question 1, picking 6 AWG means you used the 90 °C column even though the terminals are rated 75 °C. On Question 3, 20 A is what you get when you forget the 125% rule for continuous loads.

  • Motors: use the Article 430 tables for conductors and protection, and the nameplate only for overloads.
  • Ampacity: start in the column that matches the insulation, then check the terminal rating.
  • Box fill: count clamps, the device yoke and the grounds, but not pigtails that never leave the box.
  • Editions: dwelling demand was Table 220.42 in 2020 and is Table 220.45 in 2023.

Where can you find a free journeyman electrician practice test?

Ten questions show you the style; a full practice test shows you whether you can hold the pace. Ohmward's free journeyman electrician practice test has 50 NEC and calculation questions with no sign-up, and every answer is explained with the 2023 NEC section to look up.

If calculations are your weak spot, work through the calculations guide and the formulas sheet first, then come back and test yourself under time.

Take the free journeyman practice test

50 exam-style NEC and calculation questions, no sign-up. Every answer comes with an explanation and the 2023 NEC section to look up, so you learn the book while you practice.

Take the free practice test →

Questions

Are these the real journeyman exam questions?

No. They are original practice questions written in the same style and checked against the 2023 NEC. Real exam items are not published, so use practice questions to learn the style and the book.

How many questions are on the journeyman electrician exam?

It depends on the state. For example, Michigan's exam has 80 questions, Iowa's has 88, Texas's has 85 and Oklahoma's has 100. Check your state guide for the exact count and time.

Is there a journeyman electrician practice test PDF?

This page works as a printable set: print it, cover the answers, and work through it with your code book. For timed practice with instant explanations, use the online practice test.

Which NEC edition should I study for practice questions?

The edition your state's exam uses. These questions use the 2023 NEC. Texas and Colorado have moved to the 2026 NEC, and Washington tests on the 2020 NEC, so check your candidate bulletin.

How do I get better at NEC code questions?

Practice finding answers through the index and the table of contents, write the section next to each answer, and review the full rule whenever you miss one. Timed practice tests show which topics slow you down.

Sources

Updated 2026-11-27. Section references are to the 2023 NEC. Ohmward is independent exam preparation, not affiliated with NFPA, any licensing board or testing company. NEC® is a registered trademark of the NFPA.